background image

7

INTRODUCTION

DuroMax Power Equipment is headquartered in Ontario, California and is the industry’s leader in 
Dual Fuel portable generator technology. In addition to a full assortment of portable generators 
ranging from digital inverters to large 15,000-watt portable standby units, their product line 
includes pressure washers, engines, pumps, and accessories.

The foundation of our company is built on quality, reliability, durability, and customer service. At 
DuroMax our vision is simple, we are committed to Powering Everyone... Anywhere! 

STOP

Please do not return

to the store.

DuroMax representatives are ready to help you 

with any questions, concerns, or issues about your 

new product. We can guide you through assembly, 

start up, and how to operate your new generator. 

We want you to be able to put your new generator 

to use right away!

CALL US BEFORE YOU CONSIDER

RETURNING THE PRODUCT!

1-844-DUROMAX

TOLL-FREE

Engines that are certified to comply with U.S. EPA emission regulations for SORE (Small off Road 
Equipment), are certified to operate on regular unleaded gasoline and may include the following 
emission control systems: (EM) Engine Modifications and (TWC) Three-Way Catalyst (if so equipped).

Notice Regarding Emissions

Summary of Contents for XP12000EH

Page 1: ...ort to ensure the accuracy of the information in this manual We reserve the right to change this product at any time without prior notice Gasoline Propane Tank Not Included XP12000EH U S E R M A N U A L 5800 Ontario Mills Pkwy Ontario CA 91764 USA www duromaxpower com Call our Customer Care Team Toll Free 8 5 pm PST Mon Fri 844 DUROMAX ...

Page 2: ......

Page 3: ...ormation 12 Carbon Monoxide Safety 13 Introduction 4 Check the Oil 30 Check the Gas Level 31 Starting the Generator Using Gasoline 32 Starting the Generator Using Propane 34 Starting the Generator Using Recoil Start 38 Starting the Generator 3 Shipping Braces 21 Wheel Kit Installation 22 Connect the Battery 24 Adding Oil 25 Adding Gasoline 26 Grounding the Generator 27 High Altitude Operation 27 G...

Page 4: ...ter 56 Spark Plug Maintenance 58 Emptying the Gas Tank 60 Cleaning the Fuel Filter Cup 62 Transporting the Generator 63 Storing the Generator for Same Day Use 64 Storing the Generator for Use Within 30 Days 65 Storing the Generator for Longer Than 30 Days 66 Specifications 68 78 Basic Troubleshooting 70 Changing Inspecting the Carbon Brushes 71 Changing Inspecting the AVR 73 Wiring Diagram 76 Main...

Page 5: ......

Page 6: ...y unavailable Equipment like table saws sanders and work lights are a necessity and portable power can play a critical role in getting a job done successfully and efficiently DUROMAX FOR PLAY Camping outdoors in a remote location can get one in touch with nature and allow them to forget the stress of the day to day grind Here portable power can provide comfort as well as safety With portable power...

Page 7: ... Powering Everyone Anywhere STOP Please do not return to the store DuroMax representatives are ready to help you with any questions concerns or issues about your new product We can guide you through assembly start up and how to operate your new generator We want you to be able to put your new generator to use right away CALL US BEFORE YOU CONSIDER RETURNING THE PRODUCT 1 844 DUROMAX TOLL FREE Engi...

Page 8: ... 65 C Do not touch hot surfaces Pay attention to warning labels on the generator denoting hot parts of the machine Allow generator to cool several minutes after use before touching engine or areas which heat during use GENERAL SAFETY PROCEDURES Please familiarize yourself with the following safety symbols and words DANGER Indicates a hazard that will result in serious injury or death if instructio...

Page 9: ...lve to the off position and disconnect the spark plug WARNING This generator produces a powerful voltage which can result in electrocution ALWAYS ground the generator before using it see the Grounding the Generator portion of the PREPARlNG THE GENERATOR FOR USE section The generator should only be plugged into electrical devices either directly or with an extension cord NEVER connect to a building...

Page 10: ...DURES 10 In addition to the above safety notices please familiarize yourself with the safety and hazard markings on the generator DANGER DO NOT OVERFILL THE GAS TANK OVERFILLING CAN RESULT IN A FIRE EXPLOSION OR DEATH 1 5 ...

Page 11: ...11 DON T TOUCH CAUTION HIGH TEMPERATURE DANGER HOT EXHAUST KEEP SAFE DISTANCE DON T TOUCH BURN RISK CARBON MONOXIDE SAFE DISTANCE ...

Page 12: ...ice in the future If you have a paper receipt staple it here for easy reference If you purchased the unit online save the email receipt where you can access it and record your details here for convenience in the future Purchase Date ____________________________________________ Order Number ____________________________________________ Retailer Name _____________________________________________ Seri...

Page 13: ...utely mandatory to keep your family safe from carbon monoxide But there s even more you can do By educating yourself about all carbon monoxide risks you ll be better prepared to protect your family from this colorless odorless threat Visit takeyourgeneratoroutside com for more information ...

Page 14: ...14 ...

Page 15: ...15 GENERATOR COMPONENTS To help you get familiar with your new DuroMax generator please see this component section for easy reference on all the generator s individual features ...

Page 16: ...el in the gasoline tank 4 Fuel Cap Allows access to fill the gasoline tank 5 Circuit Breaker Resettable switch that protects the generator from electrical overload 6 120 240V 4 Prong Twist Lock Use to connect electrical devices that run 120 or 240 Volt 60Hz single phase AC current NEMA L14 30 7 Ground Terminal Connect a ground wire here to properly ground the generator 8 120V 3 Prong Receptacle Us...

Page 17: ...g Provides ignition to the engine 18 Muffler Reduces engine emissions and reduces noise 19 Propane Connector Connects the LPG tank to the LPG Regulator Intended for use with a LPG source of 3 PSI or more 20 120V 3 Prong Twist Lock Use to connect electrical devices that run 120 Volt 60 Hz single phase AC current L5 30 21 50A Receptacle Use to connect electrical devices that run 120 or 240 Volt 60Hz...

Page 18: ...mage shown Double Sided Screw Driver Oil Funnel w Hose Spanner Spark Plug Wrench Plug Ends Phillips and slot blade screwdriver used for generator maintenance Used to add oil to the generator without messy spills Assorted wrenches used in generator maintenance and assembly 10mm 12mm 13mm 15mm and 17mm 19mm Used in spark plug maintenance inspection and installation Plug heads for the receptacles fou...

Page 19: ...GENERATOR SETUP Proper setup of your generator will get you going as soon as possible while making sure you and your equipment are safe and cared for 19 ...

Page 20: ...20 ...

Page 21: ...side down on the pad 1 Remove braces a The shipping braces prevent engine movement 2 Note Shipping braces can be thrown away they will not be needed again CAUTION NEVER attempt this if you have put fuel or oil in the generator during shipment Flip the generator over and remove the brightly colored braces between the motor and the frame and the wood brace under the generator ...

Page 22: ...e with the provided lock nuts 1 Install wheels a Place the wheels onto the axles 4 Install wheel axles a Place the smallest washer onto the wheel axle bolts b Insert wheel axle bolts through the frame and secure with the provided nut and wrenches 2 Install inside wheel washers a Place one of the large washers onto the axles 3 ...

Page 23: ...e the other large washers onto the axles 5 Install handles a Attach the handles to the brackets on the frame using the provided bolts and nuts 7 Install cotter pins a Place the cotter pin through the hole at the end of the axle and bend it out to secure the wheel 6 CAUTION Do not over tighten the handles it will prevent free movement ...

Page 24: ...ove and behind the battery One side is connected to ground and the other end needs to be connected to the battery b Route the free end to the negative battery terminal 2 Connect the negative cable a Push the black rubber boot up the wire to expose the connector b Securely connect the free end of the battery cable to the negative battery terminal using the screw and nut from the battery with the sc...

Page 25: ...iller dipstick cap from the engine c Using a funnel add the appropriate amount of oil into the crankcase You will know the crankcase is full when the oil level has reached the lower lip of the opening you have just poured the oil into d Replace the oil filler cap Engine oil recommended SAE 10W 30 Viscosity varies with regions and temperatures Choose your oil viscosity using the chart to the left A...

Page 26: ...s smoothly use only FRESH UNLEADED GAS WITH AN OCTANE RATING OF 87 OR HIGHER Never use an oil gasoline mixture Never use old gas Avoid getting dirt or water in the fuel tank Gas can age in the tank and make it hard to start up the generator in the future Never store generator for extended periods of time with fuel in the tank Model Number XP12000EH Gas Tank Capacity 8 3 US gal 31 L DANGER DO NOT O...

Page 27: ...epower will decrease by about 3 5 for each 1 000 foot 300 meter increase in altitude The effect of altitude on horsepower will be greater than this if no carburetor modification is made When the carburetor has been modified for high altitude operation the air fuel mixture will be too lean for low altitude use Operation at altitudes below 3 000 feet 900 meters with a modified carburetor may cause t...

Page 28: ...28 ...

Page 29: ...e are still steps you should take to prepare it for operation each time you use it IMPORTANT At this point you should be familiar with the procedures described in the first portion of this section entitled GENERATOR SETUP If you have not yet read this section go back and read it now ...

Page 30: ...ient amount To check the oil level a Make sure the generator is on a level surface b Unscrew the oil filler dipstick cap c With a dry cloth wipe the oil off of the stick on the inside of the cap d Insert the dipstick as if you were replacing the cap and then remove it again There should now be oil on the stick If there is no oil on the stick or oil only at the very end of the stick you should add ...

Page 31: ...OVERFILL THE GAS TANK OVERFILLING CAN RESULT IN A FIRE EXPLOSION OR DEATH 1 5 WARNING Gasoline and gasoline fumes are highly flammable Do not fill the tank near an open flame Always allow the engine to cool for several minutes before refueling DO NOT overfill the fuel tank Fuel expands when shaken or heated ALWAYS leave 11 2 space or more at the top of the tank ALWAYS use fresh fuel or stabilized ...

Page 32: ...er clockwise to the vertical position to turn on the gas supply The choke lever is located above the air filter to the left of the recoil start Slide the lever to the left to cut the air supply and allow more gas into the engine to start 2 3 Turn idle control OFF The idle control is located on the top center of the main power panel Turn the switch OFF to prevent the unit from trying to idle down b...

Page 33: ... Connect The breaker is located on the right side of the front power panel Flip the breaker up to allow the power to flow to the receptacles Connect your devices to the receptacles on the front panel Start with the largest loads first 7 Turn engine switch to START The key switch is located on the left side of the front power panel Insert the key and turn to the START position to start the generato...

Page 34: ... the carburetor 2 Turn idle control OFF The idle control is located on the top center of the main power panel Turn the switch OFF to prevent the unit from trying to idle down before the engine is warmed up 4 STARTING THE GENERATOR CONTINUED Starting the Generator Using Propane Connect propane hose and tank The propane regulator is located on the frame of the generator below the OHV valve cover Ens...

Page 35: ...gine switch to START The key switch is located on the left side of the front power panel Insert the key and turn to the START position to start the generator Allow the key to return to the run position once started 6 5 Turn breaker ON Connect The breaker is located on the right side of the front power panel Flip the breaker up to allow the power to flow to the receptacles Connect your devices to t...

Page 36: ... engine performance for several minutes 3 If the propane gas leaks shut off the LPG supply first and then quickly unplug or turn off any electrical devices powered by the unit 4 When stopping the engine unplug or turn off any electrical devices turn off the Main Circuit Breaker and then turn off the LPG Supply After the engine has stopped turn the Battery Switch to the OFF position CAUTION Disconn...

Page 37: ...37 ...

Page 38: ...nerator 1 Close choke Turn engine switch to ON The choke lever is located above the air filter to the left of the recoil start Slide the lever to the left to cut the air supply and allow more gas into the engine to start The key switch is located on the left side of the front power panel Insert the key and turn to the ON position 3 4 Select your fuel If using gasoline see step 2 on pg 32 If using ...

Page 39: ...il start The recoil start is located on the left side panel next to the air filter Pull the recoil handle slowly until resistance is felt then quickly pull the recoil handle until fully extended 6 CAUTION Release the recoil handle only after the cord has retracted Releasing the recoil handle while extended may cause harm to yourself or your equipment Turn idle control OFF The idle control is locat...

Page 40: ...40 ...

Page 41: ... still steps you should take to prepare it for operation each time you use it IMPORTANT At this point you should be familiar with the procedures described in the first portion of this section entitled GENERATOR SETUP if you have not yet read this section go back and read it now 41 ...

Page 42: ...to draw from the generator If this number exceeds the rated wattage of the generator DO NOT connect all these devices Select a combination of electrical devices which has a total rated wattage lower than or equal to the rated wattage of the generator Fuel Source Rated Running Wattage Surge Peak Wattage Gasoline 9500 12000 Propane 9025 11400 42 You may connect electrical devices running on AC curre...

Page 43: ...ectric drill 600 900 Television 500 0 Deep freezer 500 800 Garage door opener 480 600 Stereo 400 0 Box fan 300 600 Clock radio 300 0 Security system 180 0 DVD Player 100 0 Common light bulb 75 0 CAUTION The generator can only run at its surge wattage capacity for a very short time Connect only electrical devices requiring a rated running wattage equal to or less than the rated wattage of the gener...

Page 44: ......

Page 45: ...ly switches power over to your generator during an outage Requires an electrician to install Once you choose which circuits you want to power you re locked into your configuration Interlock kit Choose what circuits you want to run Requires an electrician to install but you have the flexibility of switching up your circuits depending on your power needs More hands on and some electrical knowledge i...

Page 46: ...acle Plug in devices Turn breaker ON Turn on connected devices Plug in devices to the appropriate receptacle When using the generator balance the load as closely as possible Placing more load on one side of the circuit will reduce the breaker trip period Flip the circuit breaker up to the ON position to allow power to the receptacles Start or turn on appliances starting with the biggest loads firs...

Page 47: ...7200 10 10 10 8 NR 40 4800 9600 8 8 6 6 NR 50 6000 12000 6 6 6 NR NR NR NOT RECOMMENDED Gauge based on twisted copper wire Length 120V 15A 240V 30A 240V 50A 14 Gauge 12 Gauge 10 Gauge 6 Gauge Single Outlet Single Outlet Triple Outlet Single Outlet Triple Outlet L14 30P L14 30R 14 50P CS6364 10 ft XP3010GC 15 ft XP5015GC 25 ft XPC14025A XPC12025A XPC12025C XPC10025A XPC10025C XP3025GC XP5025GC 50 f...

Page 48: ...ive terminal on the battery Connect the free end of the positive wire to the positive receptacle outlet on the generator The start switch is located on the left side of the front power panel Insert key and move to the start position to start the generator Allow the switch to return to the run position once started 1 2 3 48 Connect negative receptacle Carefully connect the free end of the negative ...

Page 49: ... charging a battery DANGER Always wear protective goggles and rubber gloves when charging a battery DANGER If battery acid gets on your skin flush with water If battery acid gets in your eyes flush with water and call a physician immediately DANGER If battery acid is swallowed drink large quantities of milk and call a Physician immediately CAUTION Never try to jump start a car with your generator ...

Page 50: ... generator select the 120V ONLY position to double the 120V amperage and automatically balance the load Idle control The idle control feature lowers the RPM of the generator when there is no load to save gas and decrease engine noise When a load is applied the engine will resume normal speed to provide usable power Turn on the idle control when using intermittent loads like power tools and air com...

Page 51: ...e and storage of your generator are essential to ensure trouble free use of your generator when you need it By following the maintenance and care requirements you can keep your generator running smoothly and efficiently for years to come 51 ...

Page 52: ... CHECK CHECK CHANGE CHANGE SEDIMENT CUP CLEAN CLEAN SPARK PLUG CLEAN ADJUST CLEAN ADJUST SPARK ARRESTOR CHECK CLEAN IDLE SPEED CHECK ADJUST VALVE CLEARANCE CHECK ADJUST FUEL TUBE CHECK CHECK REPLACE FUEL TANK FILTER CLEAN COMBUSTION CHAMBER CLEAN WARNING Improper maintenance or failure to correct a problem before operation can cause a malfunction in which you can be seriously injured or killed Alw...

Page 53: ...n Period As the best practice for any new combustion motor it s recommended to perform the break in procedure as follows Run the generator for the first 6 8 hours on conventional oil then change the oil After the break in period synthetic oil may be used During the break in period of the first 6 8 hours keep the generator load under 50 for optimal results Check and clean the air filter if necessar...

Page 54: ...el a Make sure the generator is on a level surface b Unscrew the oil filler dipstick cap c With a dry cloth wipe the oil off of the stick on the inside of the cap d Insert the dipstick as if you were replacing the cap and then remove it again There should now be oil on the stick If there is no oil on the stick or oil only at the very end of the stick you should add oil until the engine crankcase i...

Page 55: ...ecessary to drain the oil from the crankcase if it has become contaminated with water or dirt 3 Remove drain plug Using a 12 mm hex wrench unscrew the oil drain plug which is located on the crankcase underneath the oil filler dipstick cap Allow all the oil to drain from the generator 1 Drain oil Drain oil into an approved oil disposal container Contact your local auto parts store for information o...

Page 56: ...elements from the casing Wipe the dirt from inside the empty air cleaner casing 1 2 3 Routine maintenance of the air cleaner helps maintain proper airflow to the carburetor Check that the air cleaner is free of excessive dirt after every use CAUTION Improper maintenance may cause less air to enter the engine or dirty air to enter the engine causing overheating and engine wear Cleaning the Air Filt...

Page 57: ...lace the cover 7 Washcleanerelement Wash the sponge like elements in household dish detergent and warm water 4 Drycleanerelement Pat dry on a dry cloth and allow the elements to dry completely 5 6 Addengineoiltoelements Soak the dry elements in a small amount of engine oil Ring out any excess oil ...

Page 58: ...ark plug cap to remove it Unscrew the spark plug from the generator using the spark plug wrench included with this product Visually inspect the spark plug If it is cracked or chipped discard and replace it with a new spark plug We recommend using an F6RTC spark plug such as NGK BPR6ES 1 2 3 CAUTION Improper maintenance may cause reduced fuel economy misfires trouble starting or damage to the spark...

Page 59: ...n and re gap If you are re using the spark plug use a wire brush to clean any dirt from around the spark plug base and then re gap the spark plug 5 Install spark plug Replace spark plug cap Screw the spark plug back into its place on the generator using the spark plug wrench Replace the spark plug cap 6 7 ...

Page 60: ...the fuel system components If you have been using gasoline in your generator before storing your generator for extended periods of time you should drain your generator fuel tank of gasoline Shut fuel valve OFF Remove fuel filter cup Empty fuel filter cup Turn the fuel valve to the OFF position Remove the fuel filter cup see Removing the Fuel Filter Cup later in this section Empty the fuel filter c...

Page 61: ... valve to the ON position Drain all the gas from the generator 4 Shut fuel valve OFF Replace fuel filter cup Store emptied gas Turn the fuel valve to the OFF position Reinstall the fuel filter cup Store the emptied gasoline in a suitable place and add fuel stabilizer to keep fuel fresh and usable 5 6 7 ...

Page 62: ...valve to the OFF position 1 Cleaning the Fuel Filter Cup Remove fuel filter cup Clean filter cup Replace fuel filter cup Unscrew the fuel filter cup from the fuel valve using a wrench Clean the cup of all sediment using a rag or brush Reinstall the fuel filter cup 2 3 4 ...

Page 63: ...e Gas Tank on page 60 61 Pull on spark plug cap to disconnect spark plug from ignition wire 1 2 CAUTION Do not obstruct any ventilation openings and keep the generator in a cool dry area CAUTION Never place any type of storage cover on the generator while it is still hot Transporting the Generator ...

Page 64: ...n fuel valve OFF Store Turn the fuel valve clockwise to the horizontal position to shut off the flow of gasoline to the carburetor then store the generator CAUTION Do not obstruct any ventilation openings and keep the generator in a cool dry area 4 64 Turn the main breaker OFF Run the generator Move the main breaker to the OFF position Allow the generator to run for 3 5 minutes 1 2 ...

Page 65: ...Day Use on page 64 1 Shut fuel valve OFF and run dry Turn the key switch OFF Add fuel stabilizer and store Shut the fuel valve OFF and allow generator to run until it stalls out Turn the key switch counter clockwise to the OFF position to shut the generator off Add fuel stabilizer to gas remaining in tank and store generator 2 3 4 65 ...

Page 66: ...e 64 1 Shut fuel valve OFF and run dry Empty the gas tank Shut the fuel valve OFF and allow generator to run until it stalls out Fully drain your gas tank as shown in Emptying the Gas Tank on page 60 61 2 4 MAINTENANCE AND CARE CONTINUED 66 Turn the key switch OFF Turn the key switch counter clockwise to the OFF position to shut the generator off 3 ...

Page 67: ...der Remove battery and charge Remove spark plug as shown in Spark Plug Maintenance on page 58 Add 2 tablespoons of 10W 30 motor oil directly into the spark plug hole and pull the recoil to lubricate cylinder After lubricating cylinder reinstall the spark plug Remove the generator battery and place it on a 12V battery tender indoors 6 7 8 67 ...

Page 68: ...0 5 fl oz 1 2 L Bore 92 mm Stroke 69 mm Engine Speed 3600 rpm Oil Cooling Type Splash Bearing Type Stainless steel ball bearing Cylinder Sleeve Cast iron sleeve Fuel Delivery System Carburetor Valve Type OHV Engine Type 4 Stroke Engine Cooling Type Forced air Run Time 50 Gasoline 8 hr Run Time 50 Propane 7 hr 40 lb Starting Type Electric Recoil Noise Level 74 dB Neutral System Floating AC Rated Fr...

Page 69: ...TROUBLESHOOTING This section of the manual is to help you troubleshoot problems with your generator 69 ...

Page 70: ...level Move the generator to a level surface Oil is low Add change the oil Engine runs but there is no electrical output The circuit breaker is Off Turn On circuit breaker Wiring connection is bad Replace extension cord s Device connected to generator is malfunctioning Disconnect malfunctioning device The generator runs but does not support all electrical devices connected Generator is overloaded D...

Page 71: ...bon brushes are wearable parts and should be inspected every 250 running hours Remove generator cover Remove bolt from brush Disconnect AVR wires Remove the 2 bolts of the generator cover then pull the cover off the generator Remove the bolt holding the carbon brush Remove the two wires from the AVR on the carbon brush 1 2 3 71 ...

Page 72: ...Inspecting the Carbon Brushes Cont Install new brush Install new carbon brush with bolt 4 Connect AVR wires Insert and connect the 2 wires from the AVR be sure to connect and correctly 5 6 Replace generator cover Replace the back cover of the generator and secure it with the 2 bolts ...

Page 73: ...rator If the generator is overheated or overloaded the AVR may be damaged and require replacement Remove generator cover Remove AVR bolts Disconnect AVR wire clip Remove the 2 bolts of the generator cover then pull the cover off the generator Remove the 2 bolts holding the AVR Disconnect the wire clip 1 2 3 ...

Page 74: ... AVR wire clip Reconnect the wire clip 7 Disconnect wires from brush Remove the 2 wires from the AVR on the carbon brush 4 Install new AVR Install the new AVR with the 2 bolts 5 6 Reconnect wires to brush Insert and connect the 2 wires from the AVR be sure to connect and correctly ...

Page 75: ...75 Replace generator cover Replace the back cover of the generator and secure it with the 2 bolts 8 ...

Page 76: ...76 M WIRING DIAGRAM ...

Page 77: ...77 ...

Page 78: ...ES EXPRESSED OR IMPLIED U S EPA AND CALIFORNIA EMISSION CONTROL WARRANTY STATEMENT YOUR WARRANTY RIGHTS AND OBLIGATIONS The California Air Resources Board The United States Environmental Protection Agency US EPA and DuroMax Power Equipment are pleased to explain the emission control system warranty on your 2022 2023 year small off road engine In the United States and California new small off road ...

Page 79: ... 1 844 387 6629 WEBSITE www duromaxpower com ADDRESS 5800 Ontario Mills Pkwy Ontario CA 91764 This telephone number is only for the engines which the company name DuroMax Power Equipment on the emission label DEFECTS WARRANTY REQUIREMENTS a The warranty period begins on the date the engine or equipment is delivered to an ultimate purchaser b General Emissions Warranty Coverage DuroMax Power Equipm...

Page 80: ...ovisions of Subsection 4 above warranty services or repairs must be provided at all DuroMax Power Equipment distribution centers that are franchised to service the subject engines 6 The owner must not be charged for diagnostic labor that leads to the determination that a warranted part is in fact defective provided that such diagnostic work is performed at a warranty station 7 DuroMax Power Equipm...

Page 81: ...retor spacer if applicable ii EGR rate feedback and control system 5 Air Injection System i An air pump or pulse valve ii Valves affecting the distribution of flow iii Distribution manifold 6 Catalyst or Thermal Reactor System i Catalytic converter ii Thermal reactor iii Exhaust manifold 7 Particulate Controls i Traps filters precipitators and any other device used to capture particulate emissions...

Page 82: ...are your lifeline in the event of an emergency Should you have any problems please contact our customer service department DUROMAX POWER EQUIPMENT 5800 Ontario Mills Parkway Ontario CA 91764 Customer Service 844 DUROMAX Customer Service Hours 8 5 pm PST Mon Fri Website www duromaxpower com Email customerservice duromaxpower com ...

Page 83: ...83 ...

Page 84: ...5800 Ontario Mills Parkway Ontario CA 91764 United States 844 DUROMAX REV XP12000EH 06272022 ...

Reviews: