CONDUCTOR PRETREATMENT 

 

All  kinds  of  copper  conductors  can  be  clamped  without  treatment.    DO  NOT  solder  tin  stranded  conductors.    The  solder  yields  and 
fractures under high pressure.  The result is increased contact resistance and excessive temperature rise.  Additionally, corrosion has 
been observed due to the fluxes.   Notch fractures at the transition from the rigid tinned part to the flexible conductors are also possible.  
Ferrules  can  be  used  as  a  protection  when  wiring  stranded  conductors.    Copper  ferrules  prevent  the  current  transfer  from  being 
influenced by dissimilar metals and remove the risk of corrosion.  Always use the correct tool to crimp the ferrule. 

 

RECOMMENDED COPPER WIRE SIZE FOR CURRENT CAPACITY 

 

(Insulated Wire, Single Conductor in free air) 

 

Current Level in Amperes 

<7 AMPERES 

Wire Size 

20 AWG Up to 5 feet 

18 AWG Up to 10 feet 

14  AMPERES 

18 AWG Up to 5 feet 

16 AWG Up to 10 feet 

20  AMPERES 

16 AWG Up to 5 feet 

14 AWG Up to 10 feet 

30  AMPERES 

14 AWG Up to 5 feet 

12 AWG Up to 10 feet 

40  AMPERES 

12 AWG Up to 5 feet 

10 AWG Up to 10 feet 

50  AMPERES 

10 AWG Up to 5 feet 

8  AWG Up to 10 feet 

70  AMPERES 

8 AWG Up to 5 feet 

6 AWG Up to 10 feet 

100 AMPERES 

6 AWG Up to 5 feet 

4 AWG Up to 10 feet 

   

 

 

 
 

 

 
 

 
 

 
 
 

 
 

 
 

 
 

 
 

 
 

 

Summary of Contents for LPB-24

Page 1: ...pted The DC output operating voltage from the internal battery and AC charger circuitry is delivered to the red and black jacks located on the rear panel The power supply DC output is protected against inadvertent shorts and overloads by a thermal circuit breaker SPECIFICATIONS Operational DC Voltage 24 VDC nominal Maximum Current continuous 7 Amps Max 5 Amps Cont AC Input voltage range 90 264 VAC...

Page 2: ...ovides seamless transfer of DC power to the load If the battery becomes depleted the charging circuit will recharge the battery once AC power is restored Let battery charge for 24 hours prior to installing to ensure the battery is fully charged Power switch needs to be ON BATTERY LIFE The length of time the battery will provide power depends on the current draw demand of the load Typically based o...

Page 3: ...rules prevent the current transfer from being influenced by dissimilar metals and remove the risk of corrosion Always use the correct tool to crimp the ferrule RECOMMENDED COPPER WIRE SIZE FOR CURRENT CAPACITY Insulated Wire Single Conductor in free air Current Level in Amperes 7 AMPERES Wire Size 20 AWG Up to 5 feet 18 AWG Up to 10 feet 14 AMPERES 18 AWG Up to 5 feet 16 AWG Up to 10 feet 20 AMPER...

Page 4: ... of such changes DuraComm requires any product needing in or out of warranty service to be returned to DuraComm All requests for warranty service must be accompanied by proof of purchase such as bill of sale with purchase date identified DuraComm is not responsible for any expenses or payments incurred for the removal of the product from its place of use transportation or shipping expenses to the ...

Reviews: