CONDUCTOR PRETREATMENT 

 

All  kinds  of  copper  conductors  can  be  clamped  without  treatment.    DO  NOT  solder  tin  stranded  conductors.    The  solder  yields  and 
fractures under high pressure.  The result is increased contact resistance and excessive temperature rise.  Additionally, corrosion has 
been observed due to the fluxes.   Notch fractures at the transition from the rigid tinned part to the flexible conductors are also possible.  
Ferrules  can  be  used  as  a  protection  when  wiring  stranded  conductors.    Copper  ferrules  prevent  the  current  transfer  from  being 
influenced by dissimilar metals and remove the risk of corrosion.  Always use the correct tool to crimp the ferrule. 

 

 

RECOMMENDED COPPER WIRE SIZE FOR CURRENT CAPACITY 

 

(Insulated Wire, Single Conductor in free air) 

 

Current Level in Amperes 

<7 AMPERES 

Wire Size 

20 AWG Up to 5 feet 

18 AWG Up to 10 feet 

14  AMPERES 

18 AWG Up to 5 feet 

16 AWG Up to 10 feet 

20  AMPERES 

16 AWG Up to 5 feet 

14 AWG Up to 10 feet 

30  AMPERES 

14 AWG Up to 5 feet 

12 AWG Up to 10 feet 

40  AMPERES 

12 AWG Up to 5 feet 

10 AWG Up to 10 feet 

50  AMPERES 

10 AWG Up to 5 feet 

8  AWG Up to 10 feet 

70  AMPERES 

8 AWG Up to 5 feet 

6 AWG Up to 10 feet 

100 AMPERES 

6 AWG Up to 5 feet 

4 AWG Up to 10 feet 

   

 

 

 
 
 

 

 

 
 
 

 
 
 
 
 