DuraComm HE1U-1248-BBLVD Owner'S Manual Download Page 2

 

2

 of 5 

August 19, 2016

 

BATTERY BACK UP & CHARGER  

Auto-revert to Battery or Power Supply ................................................................. provided by dual Shottky diode in OR configuration 
Maximum Output Current in Battery Mode ..................................................................................... 40 Amps (limited by Shottky diode)  
Maximum Charge Voltage ...................................................................................................................................................... 55.6 VDC 
 

 

LOW VOLTAGE DISCONNECT with RELAY 

 

Maximum Interrupt Current / continuous current ............................................................................................................... 40 Amps DC 
Disconnect Voltage ................................................................................................................................................................... 42 VDC 
Reconnect Voltage .................................................................................................................................................................... 50 VDC 
Disconnect Delay ..................................................................................................... 2 minutes @ less than preset disconnect voltage 

 

 

INSTALLER NOTES 
  

NOTE:  DO NOT

 block any of the cooling vents on the sides and top and always allow adequate ventilation by not installing the unit 

inside tightly closed spaces.  Physical mounting position is not critical but the cooling vents must not be blocked.  

NOTE:

 The outputs are 

NOT 

referenced to the chassis.  

The Modular System can be used either positive or negative ground.

  

 

 
FRONT PANEL LAYOUT 
 

Power Supply Module ON/OFF

Manual Battery Disconnect Switch

Load Power

 

 
 
 

 

 