Lower floor/basement
In areas where the CO2 is stored or
distributed in Below Grade locations
such as Lower Floors and Basements,
it is essential to have Warning Lamps/
Horn Strobes before the entrance to
the area.
In enclosed spaces Warning Lamps/
Horn Strobes must be placed outside
of each entrance.
Enclosed Spaces
CO2 detection distance
It is very important to be aware that a
CO2 Sensor can only monitor the CO2
concentration in the proximity of the
sensor. Therefore it is essential to place
the sensor correctly within 5 metres /
15 feet from the distribution point were
a CO2 leak is possible.
15 Feet
5 Meters