APT3500 Smart Pressure Transmitter
Operation Manual M3500-EO1G
29 DUON System Co., Ltd.
ENG_PV
Engineering PV Mode. Converted PV is indicated in the set-
up Engineering Range.
- Whenever ZERO Button is pushed, LCD Mode is changed, and after choosing the desired
mode, use SPAN Button to save set-up values.
-
Decimal Place : Set up decimal place of the numerical value displayed on LCD.
- Executing the menu to put Zero+Span button.
- Moving to the next menu to put Zero button when 1 TRIM message appear.
- Moving to the next menu to put Zero button when 2 Setup message appear.
- Moving to the sub directory to put Span button when 3 LCD message appear.
- Moving to the next menu to put Zero button when 31 LCD-MD message appear.
- Executing the function to put Span button when 32 DEC-PL message appear.
- When Decimal Place function excuted, the type of decimal place will be appear on the
secondline of LCD as below.
Display
Explanation
Max. Value
AUTO
Target value will be displayed
automatically (Former Display Type)
9999
5-0
None decimal place
9999
4-1
Display one decimal place
9999.9
3-2
Display two decimal place
999.99
2-3
Display three decimal place
99.999
1-4
Display four decimal place
9.9999
- Firstly, 0.0 will be display on the first line of LCD.
- Decimal place will be change whenever put the Zero button. Saving the setting value to put
Span button after select the required decimal palce.
- The set value will be applicable for displaying PV value and Engineering value. 3-2 format will
be displayed for mA and % regardless any setting.
- LCD_OV message and current setting Unit will be displayed when over the LCD limitvalue.
-
Change Engineering URV : Set up URV (Upper Range Value) which is used in LCD Engineering
Mode.
- Executing the menu to put Zero+Span button.