Sensor Orientation

The sensors must be mounted as shown below with the sintered head pointing vertically down. 

Sensor Positioning

The SGM595 sensor should be mounted in accordance 

with certain considerations. Do not position next 

to burners, heaters or ovens where temperatures 

above the room ambient may be experienced. It is, if 

possible, better to mount the sensors on the opposite 

wall. This is, of course, dependant on the size of the

protected area.

LPG is heavier than air, therefore the SGM595 sensor 

should be mounted 30cm from the lowest point on 

floor of the protected area. Natural Gas is lighter than 

air and the SGM595 should be mounted 30cm from 

the highest point from ceiling of the protected area.

If you require assistance regarding locating sensors 

please call our Droitwich factory on (01905) 797989 

or email us: [email protected]

Important Notes

Always check the wiring before powering up the system. 

When  replacing  sensors  never  seperate  a  sensing  head  from  its  PCB.  The  sensor  will  have  been  calibrated  using  this 

particular board and therefore will not function correctly with any other.

Do not test this sensor with anything other than Duomo test gas. Concentrations above this will damage the sensor and 

shorten sensor life. 

The installation of this gas sensor does not release the user from observing all the regulations concerning the characteristics 

of the installation and use of gas appliance, the ventalation of the protected environment and the removal of the products 

of combustion. Duomo (UK) will not be held responsible or liable for any damage caused to people, property or animals 

resulting from incorrect connection, installation or application of this gas sensor.

To ensure correct function after installation Duomo provide a commissioning service using calibrated test gases. For this 

service call +44 1905 797989.

Summary of Contents for SGM595

Page 1: ...rise then the main alarm relay is activated to break the electrical supply to a safety shut off valve and is fixed at 20 LEL of Natural Gas or LPG The SGM595 microprocessor conducts both self diagnostics and automatically calibrates the sensor when ambient conditions vary thus avoiding false alarms SGM595 Natural Gas Propane Sensor 4 20mA IP55 Propane Natural Gas SPECIFICATION Power Power Supply 1...

Page 2: ...maging the sensor Disabling the sensor or the controller must be carried out by a suitably trained technician Every year a more accurate check must be performed by qualified personnel Please call Duomo UK on 01905 797989 Overall Dimensions mm Important Notes IMPORTANT Assembly maintenance of the appliance must be carried out by qualified personnel and in accordance with applicable laws and regulat...

Page 3: ...ON LED This LED illuminates Green when power is ON and the sensor has a power supply from the controller Flashing red indicates gas is being detected Constant red indicates alarm state Constant Amber indicates fault condition DIAGNOSTIC PORT This can be connected to a A hand held datalogger that can printout information about the sensor serial number powering up information sensor condition alarm ...

Page 4: ...0V 230V 230V 230V 4 20mA Input Self Diagnostic Manual Test Internal Alarm Emergency Stop Function Alarm Stages Pre Alarm Main Alarm 1st Alarm 2nd Alarm Main Alarm 1st Alarm 2nd Alarm Main Alarm 1st Alarm 2nd Alarm Main Alarm 1st Alarm 2nd Alarm Main Alarm Pre Alarm Main Alarm O2 Monitoring Positive Safety IP Rating IP42 IP44 IP44 IP44 IP44 IP65 Extended Guarantee 3 Year 3 Year 3 Year 3 Year 3 Year...

Page 5: ...tory on 01905 797989 or email us sales duomo co uk Important Notes Always check the wiring before powering up the system When replacing sensors never seperate a sensing head from its PCB The sensor will have been calibrated using this particular board and therefore will not function correctly with any other Do not test this sensor with anything other than Duomo test gas Concentrations above this w...

Page 6: ...shooting and FAQs become apparent If your issue is not listed here please call Duomo UK on 01905 797989 and inform us so we can list your issue and associated solution here In case of alarm Extinguish any naked flames Do not switch lights or electrical devices on or off Open all windows and door to increase ventalation If the ALARM LED is off the levels of gas have dropped A responsible qualified ...

Page 7: ...g is successful A Duomo Commissioning Certificate is provided A certificate from the original maufacturer ensures that the commisioning or servicing carried out is at a high professional standard by a competent and qualified service engineer It is prudent to make electrical connection to the detector terminal plus when withdrawn and leave the plug off the detector so that the Duomo Engineer is the...

Page 8: ...cestershire WR9 9AH DuomoUK linkedin com company duomo uk SGM595 11032021 rev2 This document is protected by copyright No changes by others are permitted without prior authorisation by Duomo UK Ltd Duomo UK Ltd reserve the right to modify and revise this datasheet without notification GAS SAFETY CONTROLS ...

Reviews: