Note:

Connections when Positive Safety is off

Note:

Connections when Positive Safety is on

*1mm2 CSA cable only

Power Supply

230V AC

Lamp

GS300M wiring schematic

Sensor Installation

The sensors must be mounted as shown below with the 

sintered head pointing vertically down. When replacing 

sensors never seperate a sensing head from its PCB. The 

sensor will have been calibrated using this particular board 

and therefore will not function correctly with any other.

Electrical Installation

The GS300M is a safety device designed to give audible 

alarms and automatically provide latched electrical isolation 

of associated gas safety shut off valves in the event of a gas 

leak or build up of toxic gases. 

The sensors can be located up to 100m from the gas detector. 

Cable size should be 1mm

2

 CSA. If the sensor cables are 

run separately in specific conduit it is not essential to use 

screened cable but if the cables are routed through conduit 

or trunking containing other wiring the use of screened cable 

is advisable. The wiring should be performed by a qualified 

person in accordance with current regulations. The plug-in 

terminal rail makes installation easy and quick. Do not mount 

close to any heat source or in an area where moisture is 

likely to effect operation. The IP rating of this unit is IP44. 

Sensors should be positioned as shown below. 

If  you  require  any  guidance  on  this  please  call  Duomo 

technical support on +44 1905 797989.

Important Notes

Always check the wiring before powering up the system. 

Do not test this sensor with anything other than Duomo test 

gas (See 'GS300M Operation' section for further information). 

Concentrations above this will damage the sensor and 

shorten sensor life. 

The installation of this gas detector does not release 

the user from observing all the regulations concerning 

the characteristics of the installation and the use 

of gas appliances; the ventilation of the protected 

environment and the removal of products of combustion.  

Duomo will not be held responsible or liable for any damage 

caused to people, property or animals resulting from incorrect 

connection, installation or application of this gas detector.  To 

ensure correct function after installation Duomo provide a 

commissioning service using calibrated test gases. For this 

service call +44 1905 797989.

Summary of Contents for GS300M

Page 1: ...ure looks for return sensor voltage and ensures correct functionality The GS300M controller is compatible with all the Duomo conventional sensors SPECIFICATION Power Power Supply 230VAC 50Hz 10 Secondary Battery 12VDC 10 Max 2 2Ah Battery Charger Charger Capacity 2 2Ah Power Consumption 11W Maximum 13 8V Relay Contact Range 10A resistive Alarm Settings Pre Alarm No 1 8 LEL 120ppm Pre Alarm No 2 13...

Page 2: ...rough a BMS The relay driving techonogy de energized when triggered will ensure a prompt indication even in case of mains power failure The GS300M has two plug in terminal blocks One is for the incoming mains supply and alarm circuit wiring and the second is for connecting the sensor wiring This reduces the chance of incorrect site wiring The front panel has two overload lights which indicate when...

Page 3: ...r fault condition 9 TEST When pressed checks the sequence and function of GS300M Press and hold to initiate a full function test release once controller is in alarm state required Will eventually activate all relays and their associated outputs 10 1st PRE ALARM Illuminates at 8 LEL Explosive or 120ppm Toxic gas concentration LED illuminates and the Pre Alarm relay 1 is actuated 11 2nd PRE ALARM Il...

Page 4: ... the 1st 3 double DIP switches Toxic or explosive levels These are labelled as GAS or CO on PCB The symbols on the front fascia of the detector are EN standard symbols and refer to any explosive or toxic gas If toxic gas e g carbon monoxide is to be sensed on a given zone move the switch to the CO position If explosive e g natural gas LPG hydrogen etc move the switch to the GAS position Example sh...

Page 5: ...ring should be performed by a qualified person in accordance with current regulations The plug in terminal rail makes installation easy and quick Do not mount close to any heat source or in an area where moisture is likely to effect operation The IP rating of this unit is IP44 Sensors should be positioned as shown below If you require any guidance on this please call Duomo technical support on 44 ...

Page 6: ...nge 0 300ppm Working Temperature 10 C to 60 C Autosetting Yes Protective Rating IP55 Approvals EN50270 EN45544 1 3 Compliant Technical Specification Gas es Detected Carbon Monoxide Dimensions Width 100mm Height 100mm Depth 60mm Display N A Sensor Technology Electrochemical Settings Preset to TWA and STEL Standards Output Signal 4 20mA Sensor range 0 300ppm Working Temperature 15 C to 40 C Autosett...

Page 7: ...iance Technical Specification Gas es Detected Oxygen Dimensions Width 100mm Height 100mm Depth 60mm Sensor Technology Optical Fluorescence based Settings 19 5 or 18 5 of O2 depletion 22 5 23 5 excess Output Signal 4 20mA Sensor range 0 25 Working Temperature 30 C to 60 C Autosetting Yes Protective Rating IP64 Approvals EN50104 and EN50270 Compliant Technical Specification Gas es Detected Methane o...

Page 8: ... ALARM outputs listed in step a are all deactivated Relay LED and Terminal connections Pre Alarm no 2 relay actuated 2nd ALARM LED illuminates and Terminal 8 and 9 will be connected c At 20 LEL 300ppm reading The Main Alarm relay is actuated MAIN ALARM LED illuminates and Terminal 10 and 11 will be connected and terminals 10 and 12 will be broken and the audible alarm will continue to sound With P...

Page 9: ...in the open position The function of the alarm relays both the Pre Alarm and the Main Alarm can be checked by pressing the TEST button on the detector fascia Check that the main alarm action is configured for a latching alarm Switch 2 on 5th DIP switch See Configuring the GS300M There is no supply to the solenoid valve The Main Alarm relay is a volt free contact therfore you must connect the live ...

Page 10: ...cessful A Duomo Commissioning Certificate is provided A certificate from the original maufacturer ensures that the commisioning or servicing carried out is at a high professional standard by a competent and qualified service engineer It is prudent to make electrical connection to the detector terminal plus when withdrawn and leave the plug off the detector so that the Duomo Engineer is the first t...

Page 11: ...t 01905 797989 e sales duomo co uk w www duomo co uk 11 Notes ...

Page 12: ...cestershire WR9 9AH GAS SAFETY CONTROLS DuomoUK linkedin com company duomo uk GS300M 20072021 rev4 This document is protected by copyright No changes by others are permitted without prior authorisation by Duomo UK Ltd Duomo UK Ltd reserve the right to modify and revise this datasheet without notification ...

Reviews: