Duomo CO100Ar Manual Download Page 4

Technical Specifications

Power supply

12-24V DC +/- 10% from detector

Electrical input

50mA @ 13.8V

External protection rating

IP55

Linear output

4mA @ 0ppm, 20mA @ 300ppm

Working temperature

-15

o

C to 40

o

C

Sensor type

Electrochemical

Detection precision

+/- 10% of detected level

CE certification

No. 96125

Detection

0 to 300ppm

Response time

<10 seconds

Interconnecting cable size

1mm csa

Material used for housing

Aluminium

Dimensions

100 x 130 x 60

Function check period

6 months

Guarantee

3 years

Commissioning

It is strongly recommended that this sensor should be commissioned by Duomo Commissioning Engineers or
engineers approved by Duomo to carry out this work. A quotation for commissioning or service will be
provided upon request. Contact our service department by;

Telephone - 01905 797989

Fax - 01905 774296

Email - [email protected]

The benefits of this equipment being commissioned by Duomo are:

The 3 year guarantee period will start from the date of commissioning and not from the date of manufacture

On board spares. If for whatever reason this equipment doesn't function correctly Duomo engineers will
carry spares to ensure that the commissioning is successful
A Duomo Commissioning Certificate is provided

It is prudent to make electrical connection to the sensor terminal plug when withdrawn and leave the plug
disconnected from the sensor so that the Duomo Engineer is the first to power up the unit on site. This allows
wiring to be checked prior to commissioning and avoids damage due to incorrect connection. Guarantees for
this product will become void if damage is caused by the installer.

w: www.duomo.co.uk

-

e: [email protected]

-

t: 01905 797989

-

f: 01905 774296

|

©

 

Duomo

 

(UK)

 

Ltd.

 

20

16

Electrical Installation

If the CO100Ar is to be used to monitor possible leakage of carbon monoxide in boiler rooms due to spillage or
damaged or unsuitable flue systems, it is advisable to connect the sensor directly to a Duomo gas control panel.
These are safety devices and are designed to give audible alarms and automatically provide latched electrical
isolation of associated gas safety shut off valves.

The CO100Ar is also suitable for carbon monoxide sensing in car parks and can be connected either to Duomo
gas control panels or to Building Management Systems (BMS). The sensor can be located up to 100m from the
gas detector. Cable size should be 1mm csa. If the sensor cables are run seperately in specific conduit it is not
essential to use screened cable.

However, if the cables are routed through conduit or trunking containing other wiring the use of screened cable
is advisable. The wiring should be performed by a qualified person in accordance with current regulations. The
plug in terminal rail makes installation easy and quick.

Summary of Contents for CO100Ar

Page 1: ...a time weighted average output The sensor automatically calculates carbon monoxide concentration relative to time Time Weighted Average and will give a 20mA output from terminal 3 should the carbon monoxide levels remain above predetermined levels for extended periods This is useful when carbon monoxide levels are likely to drop rapidly when extract fans are boosted Thus the TWA threshold may not ...

Page 2: ...as appliances the ventilation of the environment and the elimination of combustion products in accordance with local recommendations regulations and byelaws For any damage caused to people property or animals resulting from incorrect connection installation or application of this gas detector Duomo will not be held responsible or liable 1600 Replacing Sensor When replacing sensors NEVER seperate a...

Page 3: ...ind the cause of the alarm If the alarm sound remains constant and the cause is not evident or possible to eliminate turn off the emergency isolation valves to the area and contact your gas provider emergency line They will advice accordingly 1 2 3 1 2 3 5 4 6 7 8 FAULT RELAY ALARM RELAY w www duomo co uk e sales duomo co uk t 01905 797989 f 01905 774296 Duomo UK Ltd 2016 TWA Alarm Reaction Times ...

Page 4: ...sor terminal plug when withdrawn and leave the plug disconnected from the sensor so that the Duomo Engineer is the first to power up the unit on site This allows wiring to be checked prior to commissioning and avoids damage due to incorrect connection Guarantees for this product will become void if damage is caused by the installer w www duomo co uk e sales duomo co uk t 01905 797989 f 01905 77429...