3308120.XXX GENESIS AIR FILTRATION SYSTEM

D. REGISTER REQUIREMENTS AS FOLLOWS:

Min.

Max.

1. Distance from Duct End

5"

8'

2. Distance from End of Elbow 15"

3. Distance between Registers 24”

4. Total Number Required

8

12

5. Min. No. required per Run

2

6. Min. Free Area per Register 14 sq. in.

E. The Duct material must meet or exceed any agency

or RVIA Standard that may be in existence at the
time the RV is produced.

F. All Discharge Air Ducts must be properly insulated to

prevent condensation from forming on their surfaces or
adjacent surfaces during operation of the air conditioner/
heat pump. This insulation must be R-7 minimum.

G. Ducts and their joints must be insulated and sealed to

prevent condensation from forming on adjacent surfaces
during operation of the air conditioner/heat pump.

4. AIR DISTRIBUTION SYSTEM

INSTALLATION

Dometic Corporation recommends the basic configuration
shown in FIG. 1 for installing this air conditioner/heat pump
system. We have found by testing, that this configuration
works best in most applications of this air conditioner/heat
pump system.

It is the responsibility of the Installer of this system to review
each RV floor plan and determine the following:

A. Duct size
B. Duct layout
C. Register size
D. Register locations
E. Thermostat location.

These items must be determined in conjunction with the Air
Distribution System Sizing and Design Requirements listed
in Section 3

 

of this manual.

Important:

  Alternate configurations and methods

may be used which still allow the air conditioner/heat
pump to operate properly.  However, these alternate
configurations and methods must be approved by
Dometic Corporation in writing.

The following instructions are based upon the use of
Dometic Genesis Air Filtration System No. 3308120.XXX.

A.

Before preparing the ceiling opening, the type of system
options must be decided upon. Read all of the instruc-
tions packaged with the system options before
beginning the installation
.

B. ROOF AND CEILING OPENING PREPARATION

1. A 14-1/4" x 14-1/4" (±1/8") opening must be cut

through the roof and ceiling of the RV. This opening
must be located between the roof and reinforcing
members.

C. DUCT SIZING REQUIREMENTS AS FOLLOWS:

NOTE: Duct sizes listed are inside dimensions.

    Min.            Max.

1. Duct Depth

2.00"

2-1/2"

2. Duct Width

8.00"

10.00"

3. Total Duct Length

15'

40'

4.  Duct Length (Short Run)

1/3 Total Length

CENTER DUCT (Penguin 620 & 630 Series Only

Controls In Roof Package)

Min.

Max.

1. Duct Depth

2.00"

2.00"

2. Duct Width

8.00"

8.00"

3. Total Duct Length

15'

40'

4.  Duct Length (Short Run)

1/3 Total Length

H. Return Air to the air conditioner/heat pump must be

filtered to prevent dirt accumulation on air conditioner/
heat pump cooling surface.

I.

Total System Static Air Pressure
This is to be determined with the air conditioner/heat
pump blower operating on High Speed and return air filter
and grill in place. It is measured in inches of water
Column.

0.55 - 0.90 In. W.C. 579 Series
0.40 - 1.10 In. W.C. 590, 591, 595 Series
0.12 - 0.65 In. W.C. 600, 630 Series

It is the responsibility of the installer to in-
sure the ductwork will not collapse or bend
during and after the installation. Dometic
Corporation will not be liable for roof struc-
tural or ceiling damage due to improperly
insulated, sealed or collapsed ductwork.

CAUTION

2. Mark a 14-1/4" x 14-1/4" (±1/8") square on the roof and

carefully cut the opening.

3. Using the roof opening as a guide, cut the matching

hole in the ceiling.

4. The opening created must be framed and sealed to

provide adequate support and prevent air from being
drawn from the roof cavity. Lumber 3/4" or more in
thicknessmust be used. Remember to provide an
entrance hole for power supplies and system wires as
needed.

WARNING

!

There may be electrical wiring between the
roof and the ceiling. Disconnect 115 volt AC
power cord and the positive (+) 12 volt DC
terminal at the supply battery. Failure to fol-
low this instruction may create a shock haz-
ard causing death or severe personal injury.

Summary of Contents for GENESIS 3308120.XXX

Page 1: ...dge Ontario CANADA N3H 2N7 519 653 4390 For Service Center Assistance Call 800 544 4881 3308120 XXX GENESIS AIR FILTRATION SYSTEM FOR 57XXX SERIES 59XXX SERIES 600XXX SERIES 620XXX SERIES 630XXX SERIES AIR CONDITIONERS HEAT PUMPS USED WITH 3109226 005 ELECTRONIC CONTROL KIT 3109407 001 ELECTRONIC CONTROL KIT 3107541 009 ANALOG CONTROL KIT 3107541 017 ANALOG CONTROL KIT 3107546 008 ANALOG CONTROL K...

Page 2: ...2 3308120 XXX GENESIS AIR FILTRATION SYSTEM NOTES ...

Page 3: ...cessorieslikeA Eoutdoorpatioandwindowawnings willreduceheatgainbyremovingthedirectexposureto the sun They also add a nice area to enjoy company during the cool of the evening C Condensation Note The manufacturer of this Genesis Air Filtration System will not be responsible for damage caused by condensed moisture on ceilings or other surfaces Air contains moisture and this moisture tends to condens...

Page 4: ...rconditioner two thirdsfromfrontofRVandcentered from side to side It is preferred that the air conditioner heat pump be installed in a relatively flat and level roof sectionmeasuredwiththeRVparkedonalevelsurface Improper installation may damage equip ment could endanger life cause serious in jury and or property damage WARNING 3 AIR DISTRIBUTION SYSTEM SIZING DESIGN The Installer of this air condi...

Page 5: ...ns packaged with the system options before beginning the installation B ROOFANDCEILINGOPENINGPREPARATION 1 A 14 1 4 x 14 1 4 1 8 opening must be cut through the roof and ceiling of the RV This opening must be located between the roof and reinforcing members C DUCTSIZINGREQUIREMENTSASFOLLOWS NOTE Duct sizes listed are inside dimensions Min Max 1 Duct Depth 2 00 2 1 2 2 Duct Width 8 00 10 00 3 Total...

Page 6: ...will damage the roof gasket Note If center duct system is being used be sure to installductadaptertothebottomofthebasepan before unitisplacedoveropening Ductadapter3100342 XXX and 3100262 XXX can be used Alternate methods of duct connection are available for installation however they must be approved in writing by Dometic C Locate the foam divider and insert it corner to corner in the 14 1 4 x 14 ...

Page 7: ...peoffofthedividerandplace it on the center of the rear edge of return air opening on the ceiling template See figure 7 FIG 8B Penguin Models Lay Control Box Flat On Top Of Ceiling Template Control Box Two Screws Vehicle Front FIG 8A Brisk Air Models Mount Control Box on Edge To The Flange on Ceiling Template Control Box Three Screws Vehicle Front FIG 7 Foam Divider Ceiling Template Center And Stic...

Page 8: ... from the supply control box and filter indicator See figure 9 Note Number 10 cabinet screw can be used to replace the two front screws and pull the plastic return air cover to the ceiling when the ceiling material is hard 1 If solar panel is installed see instructions pack aged with solar panel option I Tighten the screws holding the return air cover Slide the filter from the right side looking t...

Reviews: