Dunkirk PSB-3D Installation, Operation & Maintenance Manual Download Page 8

8

SYSTEM PIPING

Consider near boiler piping as part of the boiler for proper 

water level control and to produce dry steam. 
Correct near boiler piping is crucial to proper operation of 

boiler and heating system.
Follow these recommendations carefully.

1. 

Place boiler in selected location as near chimney as 

possible. 

2. 

Install safety valve. Figure 3 and Warning on Page 7.
• Install union, if used, close to safety valve outlet.
• Install elbows close to safety valve outlet and 

downstream of union (if used).

3. 

Boiler is equipped with two 2½" supply connections 

and two 2½" return connections, one each on both left 

and right sides of boiler. Plug unused connections with 

furnished 2½" plug (furnished).

4. 

When using both supply tappings to pipe system as 

shown in Figure 5, Page 10.

• Fit headers with header offsets, swing joints, or equip 

with expansion joints, so thermal expansion and 

contraction of header does not damage boiler. Do not 

weld headers.

• Place system takeoffs from header between equalizer 

and riser to header nearest equalizer. System takeoffs 

must never be between two risers. If steam main goes 

in two directions, place two takeoffs from header, one 

for each main.

5. 

System takeoffs from the header must never be 

bullheaded. If the steam main goes in two directions, 

there must be two takeoffs from

 the header, one for each 

main.

6. 

All boilers in gravity return systems must be equipped 

with a Hartford Loop as shown in Figure 5.

7. 

When piping the vertical risers from the boiler to the 

header, the bottom of the header must be a minimum 

of 24 inches above the water level line on the right side 

of the boiler.

8. 

Steam riser(s) and header shall be 2½” pipe size. 

9. 

Equalizer line shall be minimum 1½” pipe size.

10. 

The near boiler piping shall include a 2½” tee with a 

plug located on the supply line as shown for skimming 

(i.e. surface blowdown).

11. 

The near boiler piping shall include a 1-1/2 ball valve 

in the return piping as shown for bottom blowdown and 

draining.

12. 

For gravity return systems, the bottom of the lowest 

steam carrying pipe, be it a dry return, or the end of the 

steam main, must be at least 28” above the normal water 

level line on the right side of the boiler. This is known as 

“Dimension A.”

13. 

For pumped return systems, follow the condensate 

pump or boiler feed pump manufacturer’s instructions 

for proper installation and hookup.

14. 

In connecting the cold water supply to the water inlet 

valve, make sure that a clean water supply is available. 

When the water supply is from a well or pump, a sand 

strainer should be installed at the pump.

For Use With Cooling Units

Install boiler, when used in connection with refrigeration 

system, so chilled medium is piped in parallel with boiler 

with appropriate valves to prevent chilled medium from 

entering the boiler. See Figure 6.

 P/N 14683003, Rev. D [08/03/2015]

Summary of Contents for PSB-3D

Page 1: ...NANCE MANUAL P N 14683003 Rev D 08 03 2015 ECR International Inc 2201 Dwyer Avenue Utica NY 13501 www ecrinternational com MODEL PSB Electronic Intermittent Ignition MODELS PSB 3D PSB 3DP PSB 4D PSB 4...

Page 2: ...sions Inches Intermittent Ignition w Vent Damper Flue Diameter A Width PSB 3D 5 11 PSB 4D 6 14 PSB 5D 6 17 PSB 6D 7 21 PSB 7D 7 24 PSB 8D 7 27 PSB 9D 7 30 Add 5 to height for Vent Damper 1 Add model n...

Page 3: ...et AHRI Rating Mbh Net AHRI Rating Sq Ft 1 PSB 3D 3 Natural Gas 75 62 82 7 47 196 Propane 70 58 82 7 44 183 1 PSB 4D 4 Natural Gas 112 91 82 0 68 283 Propane 105 85 80 4 64 267 1 PSB 5D 5 Natural Gas...

Page 4: ...urring any obligation whatsoever Introduction Boiler is designed for use in closed heating systems where all steam is returned as condensate and make up water is minimal Boiler is not designed for or...

Page 5: ...appliance with improper methods or materials could result in death or serious injury due to fire or to asphyxiation from poisonous gases such as carbon monoxide which is odorless and invisible WARNING...

Page 6: ...se Boiler location should not interfere with proper circulation of air Introduce outside air if normal infiltration does not provide necessary air Fresh Air for Combustion on page 11 6 Notify owner to...

Page 7: ...struction in discharge line Terminate freely to atmosphere where any discharge will be clearly visible and at no risk of freezing Allow complete drainage of valve and discharge line Install safety val...

Page 8: ...r one for each main 6 All boilers in gravity return systems must be equipped with a Hartford Loop as shown in Figure 5 7 When piping the vertical risers from the boiler to the header the bottom of the...

Page 9: ...9 Figure 4 Recommended Near Boiler Piping Using One Supply Tapping SYSTEM PIPING P N 14683003 Rev D 08 03 2015...

Page 10: ...IPING Figure 6 Chilled Water Piping VALVES A B OPEN FOR HEATING CLOSE FOR COOLING VALVES C D CLOSE FOR HEATING OPEN FOR COOLING Figure 5 Recommended Near Boiler Piping Using Two Supply Tappings P N 14...

Page 11: ...oom volume is greater than 21 cubic feet divided by ACH air changes per hour x Total Input Mbh C Refer to National Fuel Gas Code for opening requirements between connected indoor spaces All Outdoor Ai...

Page 12: ...er than 3 4 the chimney height HT Figure 7 page 13 Vent Pipe Fasten sections of vent pipe with 3 sheet metal screws at each joint to make piping rigid Support horizontal portions of vent system to pre...

Page 13: ...appliance to their previous conditions of use 7 Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code ANSI Z223 1 NFPA 54...

Page 14: ...damper troubleshooting guide refer to manual packaged with vent damper Horizontal Installation To Boiler Vent Damper To Chimney NO NO YES YES Flow Install vent damper with actuator to sides of vent o...

Page 15: ...ssive vibrations and prevent strain on gas connection Gas valve will not support piping weight Use thread joint compound pipe dope suitable for natural and liquefied petroleum gas Install field source...

Page 16: ...es are black One wire is located on secondary of 24 volt transformer second wire is located on pressure limit control F Boilers with CG400 probe type low water cut off one wire is green and is located...

Page 17: ...y and turn clockwise to OFF Do not force For Your Safety Read Before Operating WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal i...

Page 18: ...of boiler Determine water level when boiler is off and cold when all water in the system is inside the boiler and return piping below water line and everything above water line is air no steam When b...

Page 19: ...softer blue outer mantel with no yellow Remain still when observing main burner flames Check main burner orifices burner throat and flame ports for dust and lint obstruction if flame appearance is not...

Page 20: ...n thermostat to call for heat C Gas valve opens for approximately 10 seconds time delay on probe type LWCO gas valve will close and red indicator illuminates on LWCO D When water is restored it waits...

Page 21: ...ection from boiler drain valve to safe discharge point outside Shut off gas burners open drain valve allow all of water in boiler to drain out Close drain valve Allow boiler to cool slowly refill boil...

Page 22: ...RTV silicone to four mounting surface flanges of flue collector Mount flue collector on heat exchanger Tighten nuts and bolts 6 Seal front edge and four corners of flue collector to heat exchanger wit...

Page 23: ...t switch blown Have your service technician check heat exchanger for blockage Chimney flue is blocked Spill switch contacts open requiring manual reset of spill switch Have your service technician che...

Page 24: ...t be replaced it must be replaced with type 105 C Thermoplastic wire or its equivalent Figure 13 Wiring Diagrams For Boilers With CG400 Probe Type Low Water Cut Off Shown CG400 PS802 CG400 N 2 H 1 C P...

Page 25: ...nal wire as supplied with this appliance must be replaced it must be replaced with type 105 C Thermoplastic wire or its equivalent Figure 17 Wiring Diagrams For Boilers With 67D 1 Float Type Low Water...

Page 26: ...water feeder maybe used with either of the low water cutoffs listed Water feeder maintains safe minimum water level Keeps boiler running by compensating for minor evaporative steam leaks and prevents...

Page 27: ...27 REPAIR PARTS P N 14683003 Rev D 08 03 2015...

Page 28: ...28 REPAIR PARTS P N 14683003 Rev D 08 03 2015...

Page 29: ...29 REPAIR PARTS P N 14683003 Rev D 08 03 2015...

Page 30: ...30 REPAIR PARTS Safety Relief Valve 14 11 NPT X 4 Nipple PF 033 02 CG400 LOW WATER CUT OFF 240009340 P N 14683003 Rev D 08 03 2015...

Page 31: ...31 Date Service Performed Company Name Tech Initials Company Address Phone P N 14683003 Rev D 08 03 2015...

Page 32: ...reases This feature is equipped with an override which is provided primarily to permit the use of an external energy management system that serves the same function THIS OVERRIDE MUST NOT BE USED UNLE...

Reviews: