Dunkirk DPFG Series Supplemental Venting Instruction Download Page 3

3

!  

!  

VENTING INSTRUCTIONS

P/N# 240005665, Rev. 1.1 [05/06]

FRESH AIR FOR COMBUSTION - CHIMNEY VENTED BOILERS

WARNING

Be  sure  to  provide  enough  fresh  air  for 

combustion.  Enough  air  ensures  proper 

combustion and assures that no hazard will 

develop due to the lack of oxygen.

Ventilation  of  the  boiler  room  must  be  adequate  to 

provide  sufficient  air  to  properly  support  combustion 

per the latest revision of the National Fuel Gas Code, 

ANSI Z223.1, Section 5.3.

When a boiler is located in an unconfined space in a 

building or conventional construction frame, masonry 

or  metal  building,  infiltration  normally  is  adequate  to 

provide  air  for  combustion  and  ventilation.  However, 

if the equipment is located in a building of unusually 

tight  construction  (See  the  National  Fuel  Gas  Code, 

ANSI Z223.1, Section 1.7), the boiler area should be 

considered  as  a  confined  space.  In  this  case  air  for 

combustion and ventilation shall be provided according 

to  Part  5.  If  there  is  any  doubt,  install  air  supply 

provisions in accordance with the latest revision of the 

National Fuel Gas Code.

You must provide for enough fresh air to assure proper 

combustion. The fire in the boiler uses oxygen. It must 

have a continuous supply. The air in a house contains 

only enough oxygen to supply the burner for a short 

time. Outside air must enter the house to replace that 

used by the burner. Study following two examples to 

determine your fresh air requirements.

BOILER IN UNCONFINED SPACE

If your boiler is in an open area (unpartitioned basement) 

in  a  conventional  house,  the  air  that  leaks  through 

the cracks around doors and windows will usually be 

adequate  to  provide  air  for  combustion.  The  doors 

should not fit tightly. Do not caulk the cracks around 

the windows.
An  unconfined  space  is  defined  as  a  space  whose 

volume is not less than 50 cubic feet per 1,000 Btu per 

hour of the total input rating of all appliances installed 

in the space.

BOILER IN CONFINED SPACE

ALL AIR FROM INSIDE BUILDING: 

The confined 

space shall be provided with two permanent openings 

communicating  directly  with  an  additional  room(s) 

of  sufficient  volume  so  that  the  combined  volume 

of  all  spaces  meets  the  criteria  for  an  unconfined 

space. The total input of all combustion equipment 

installed in the combined space shall be considered 

in  making  this  determination.  Each  opening  shall 

have a minimum free area of one square inch per 

1,000  Btu  per  hour  of  the  total  input  rating  of  all 

combustion equipment in the confined space but not 

less than 100 square inches. One opening shall be 

within 12 inches of the top and one within 12 inches 

of the bottom of the enclosure. See

 Figure #1

.

Example: 

Your boiler is rated at 100,000 Btu per 

hour. The water heater is rated at 30,000 Btu per 

hour. The total is 130,000 Btu per hour. You need 

two grilles, each with 130 square inches of FREE 

opening.  Metal  grilles  have  about  60%  FREE 

area. To find the louvered area needed, multiply 

the FREE area required by 1.7 (130 x 1.7 = 221.0 

sq. in. louvered area). In this example, two grilles, 

each  having  an  8”  x  30”  (240  sq.  in.)  louvered 

area  would  be  used.  Figure  1  shows  the  grille 

locations.

ALL AIR FROM OUTDOORS: 

The confined space 

shall be provided with two permanent openings, one 

commencing  within  12  inches  of  the  top  and  one 

commencing within 12 inches of the bottom of the 

enclosure. The openings shall communicate directly, 

FIG.  1  – AIR  OPENINGS  FOR  CLOSET  OR  UTILITY 

ROOM INSTALLATIONS

Summary of Contents for DPFG Series

Page 1: ...be released into living areas This may cause serious bodily injury or property damage Vent performance may also be af fected by improper assembly Install separate vents for forced exhaust appliances...

Page 2: ......

Page 3: ...ill usually be adequate to provide air for combustion The doors should not t tightly Do not caulk the cracks around the windows An uncon ned space is de ned as a space whose volume is not less than 50...

Page 4: ...s Vents and Solid Fuel Burning Appliances These codes contain information on special gas vents for Category II III and IV appliances vent sizing location air space clearances to combustibles and safe...

Page 5: ...venting system for proper size and horizontal pitch and determine there is no blockage or restriction leakage corrosion and other de ciencies which could cause an unsafe condition 3 Insofar as is prac...

Page 6: ...ing and walls near ue pip with reproof insulation Where two or more appliances vent into a common ue the area of the common ue must be at least equal to the area of the largest ue plus 50 percent of t...

Page 7: ...mber of elbows 6 Do not connect to replace ue 7 The end of ue pipe must be ush with the inside face of chimney ue 8 Support the ue pipe rigidly with substantial hangers plus three sheet metal screws a...

Page 8: ...take piping A B Vent shall not be used in the vent system The exhaust terminal included in the FDVS kit is a model FDVS stainless steel vent hood Located on an exterior wall of the building the exhaus...

Page 9: ...amaged by exhausted ue gas FIG 5 EXTERIOR EXHAUST TERMINAL LOCATIONS NOTES Location of the termination of the vent pipe shall be in accordance with the National Fuel Gas Code A N S I Z223 1 see requir...

Page 10: ...room oor C When a vacuum relief is not used note that exhaust fans in use might create a vacuum within the building which can cause improper combustion Consult factory for assistance as required D Se...

Page 11: ...Clay pipe must pitch downward away from foundation to per foot 3 Con guration of transition from tee to topper is dependent on the type of the topper selected and the level of the nished grade Topper...

Reviews: