Dunham-Bush Smart-Vent Instructions Manual Download Page 2

 

 

Page 2 of 8 

 

 

Diagram 2: Smart-Vent network panel dimensions and weight 
 

 

Summary of Contents for Smart-Vent

Page 1: ...is ordered and supplied as a separate accessory to Smart Vector room units and includes an external air temperature sensor supplied loose for installation and wiring on site Diagram 1 Smart Vent netwo...

Page 2: ...Page 2 of 8 Diagram 2 Smart Vent network panel dimensions and weight...

Page 3: ...The panel can be fixed to a vertical wall surface using normal fixings that are suitable for wall construction 3 2 It is recommended that the panel is sited between 1 0 1 5m above floor level in a loc...

Page 4: ...Page 4 of 8 Diagram 3 Typical wiring diagram for Smart Vent network panel NOTE ALWAYS USE WIRING DIAGRAM ENCLOSED WITH THE PANEL...

Page 5: ...isplay numbered 1 to 8 See diagram 4 A switch is on in the up position 4 4 Switch nos 1 5 are used to set the network address switch no 6 is not used switch nos 7 and 8 are used to set the baud rate a...

Page 6: ...settings Baud rate is 19200 Modbus address is 100 If required select the setting and enter these settings 5 5 Select Return to return to Main Screen 5 6 Select the calendar icon to enter the Calendar...

Page 7: ...are run at full speed for 30 minutes prior to start of daytime occupied schedule On all Smart Vector units the fresh air dampers fully open and fans run to purge treated spaces with fresh air Individ...

Page 8: ...W ON OPEN 06 15 MID OFF OFF OFF LOW LOW OFF CLOSED 06 15 MID OFF ON OFF LOW HIGH OFF CLOSED NTFC 17 15 MID OFF OFF ON LOW LOW OFF CLOSED 18 15 MID OFF OFF ON LOW LOW ON OPEN 18 15 MID OFF OFF OFF LOW...