Specification

Max. Operating Pressure

100 PSI (689 kPa) factory rating

60 PSI (413 kPa) as per ANSI Z21.21/

CSA 6.5 C/I and 100 PSI as per 

CGA 3.9

Burst Pressure Rating

500 PSI (3447 kPa)

Ambient / Fluid Service 

Temperature

CSA   -20 °F  to  +140 °F

 

-29 °C  to    +60 °C

Factory  +5 °F  to  +140 °F

 

-15 °C  to    +60 °C

Storage Temperature

 

-40 °F  to  +185 °F

 

-40 °C  to    +85 °C

Gases

Dry, natural gas, propane, butane; 

other noncorrosive gases as well as 

waste-gases and bio-gases contain-

ing up to a maximum 0.1 % by volume 

(1000 ppm) of H

2

S, dry.

Intended for gaseous fuels only. Can-

not be used with non-compressible 

fluids (liquids) of any kind. 

(A “dry” gas has a dew point lower 

than + 15 °F and its relative humidity 

is less than 60 %.)

Materials in contact with Gas

Housing: Anodized Aluminium and 

Steel, free of non-ferrous metals 

Sealings on valve seats: NBR-based 

rubber.

°F

Electrical Ratings Available

24 VDC

Power Consumption

45 W

Operating Time

100 % duty cycle

Closing Time 

< 1 s

Opening Time 

< 1 s

Gas Connection Type

2”  flat  face  flange  per  ANSI  B16.5 

Class 150 

EN 161

HPSV 10020/604 

Normally closed automatic shutoff valve. Fast opening, fast closing.

Strainer

Built-in 1 mm stainless steel mesh 

strainer, installed upstream of the 

valve seat.

[PSI]

NEMA

Degree of Protection

NEMA 4/IP65

Suitable for hazardous locations 

Class I, Division 2, Groups C and D, 

Temperature code T4A.

[

V

]

 

[

A

]

 

[

Hz

]

 

[

VA

]

Gas

Vibration Resistance

According to MIL 810 Profile Vibration

Electrical Connection

Quick disconnect according to MIL 

ACS02A-10SL-04P-003

According to CSA C22.1 Part 1

Summary of Contents for HPSV 10020/604

Page 1: ...find the instruction also at www dungs com If these instructions are not heeded the result may be personal injury or damage to property Any adjustment and application specific adjustment values must b...

Page 2: ...wer than 15 F and its relative humidity is less than 60 Materials in contact with Gas Housing Anodized Aluminium and Steel free of non ferrous metals Sealingsonvalveseats NBR based rubber F Electrical...

Page 3: ...nsert studs tighten in a crisscross pattern to ensure uni form tightness 5 Do not overtighten studs Follow the maximum torque values listed 6 After installation is complete perform a leak test see Val...

Page 4: ...2 A and rated for at least 75 C 167 F Radiant heat must be considered as a heat source that could result in an ambient temperature higher than the rating of this valve Provide propor shielding to pro...

Page 5: ...7 05 P N 264712 Dimensions b c g e d a f Upstream 1 4 NPT Tap Downstream 1 4 NPT Tap Type Order No Dimensions inch Dimensions mm Weight lbs kg a b c d e f g HPSV 10020 604 270890 2 95 75 8 82 224 6 30...

Page 6: ...flexible hose of some convenient length provides for a more accurate leakage measurement However a 45 cut at the end of the 1 4 flexible hose will suffice but it will not likely be as accurate as the...

Page 7: ...d For ex ample when using propane divide the volume CFH of propane required for the application by the calculated value f f 0 66 for propane Use this cor rected flow rate and the flow curve on the nex...

Page 8: ...P O Box 12 29 D 73602 Schorndorf Germany Phone 49 0 7181 804 0 Fax 49 0 7181 804 166 e mail info dungs com Internet http www dungs com Karl Dungs Inc 3890 Pheasant Ridge Drive NE Suite 150 Blaine MN 5...

Reviews: