Dungs HPSV 10020/604 Installation Instructions Manual Download Page 1

1 … 8

MC • Karl Dungs

, Inc.

 • HP

SV 10020/604 • Edition 2017.05 • P/N 264712

CSA Certified: File No. 1010989

ANSI Z21.21 / CSA 6.5

C/I Marking 

CGA 3.9

HPSV 10020/604

High Pressure Safety 

Shutoff Valve

Installation Instructions

Table of Contents

Table of Contents  . . . . . . . . . . . . . . . . . . . . . . . . Page 1

Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 1

Attention . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 1

Specification  . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2

Installation Position  . . . . . . . . . . . . . . . . . . . . . . Page 3

Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3

Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 4

Painting Valve  . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 4

Protection from Radiant Heat . . . . . . . . . . . . . . Page 4

Dimensions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 5

Valve Leakage Test . . . . . . . . . . . . . . . . . . . . . . . Page 6

Flow Curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7

Accessories & Replacement . . . . . . . . . . . . . . . Page 8

Approvals

1, 2, 3 ... 

= Action 

= Instruction

Explanation of symbols

On  completion  of  work  on  the 

safety  shutoff  valve,  perform  a 

leakage and function test.

Please read the instruction be-

fore installing or operating. Keep 

the instruction in a safe place. You 

find the instruction also at www.

dungs.com If these instructions 

are not heeded, the result may 

be personal injury or damage to 

property.

Any adjustment and application-

specific adjustment values must 

be  made  in  accordance  with 

the  equipment  manufacturers 

instructions.

Attention

Check the ratings in the specifi-

cations verify sure that they are 

suitable for your application.

This product is intended for instal-

lations covered by, but not limited 

to, the following fuel gas codes: 

CSA  B149.1  (for  Canada),  the 

International Fuel Gas Code, and 

NFPA 54 or the following equip-

ment codes and standards: CSA 

B149.3 (for Canada) or NFPA 37.

The installation and maintenance 

of  this  product  must  be  done 

under the supervision of an ex-

perienced and trained specialist. 

Never perform work if gas pres-

sure  or  power  is  applied,  or  in 

the presence of an open flame.

[

V

] [

A

]

[

Hz

]

 

[

VA

]

IFGC

CSA

UL

ANSI

NFPA

Safety

first

O.K.

Warning:  During  normal  op-

eration, coil is getting hot. (max. 

176 °F / 80 °C)

USA

CDN

Summary of Contents for HPSV 10020/604

Page 1: ...find the instruction also at www dungs com If these instructions are not heeded the result may be personal injury or damage to property Any adjustment and application specific adjustment values must b...

Page 2: ...wer than 15 F and its relative humidity is less than 60 Materials in contact with Gas Housing Anodized Aluminium and Steel free of non ferrous metals Sealingsonvalveseats NBR based rubber F Electrical...

Page 3: ...nsert studs tighten in a crisscross pattern to ensure uni form tightness 5 Do not overtighten studs Follow the maximum torque values listed 6 After installation is complete perform a leak test see Val...

Page 4: ...2 A and rated for at least 75 C 167 F Radiant heat must be considered as a heat source that could result in an ambient temperature higher than the rating of this valve Provide propor shielding to pro...

Page 5: ...7 05 P N 264712 Dimensions b c g e d a f Upstream 1 4 NPT Tap Downstream 1 4 NPT Tap Type Order No Dimensions inch Dimensions mm Weight lbs kg a b c d e f g HPSV 10020 604 270890 2 95 75 8 82 224 6 30...

Page 6: ...flexible hose of some convenient length provides for a more accurate leakage measurement However a 45 cut at the end of the 1 4 flexible hose will suffice but it will not likely be as accurate as the...

Page 7: ...d For ex ample when using propane divide the volume CFH of propane required for the application by the calculated value f f 0 66 for propane Use this cor rected flow rate and the flow curve on the nex...

Page 8: ...P O Box 12 29 D 73602 Schorndorf Germany Phone 49 0 7181 804 0 Fax 49 0 7181 804 166 e mail info dungs com Internet http www dungs com Karl Dungs Inc 3890 Pheasant Ridge Drive NE Suite 150 Blaine MN 5...