Dungs GGAO-A4-4 Installation Instructions Download Page 4

4 … 5

MC • Karl Dungs

, Inc.

 • GGA

O

...A4 • Edition 2016.02 • P/N 271843

1. Remove the clear cover from the switch.

2. Use 14 or 16 AWG wire rated for at least 75 °C.

3. Route the wires through the conduit connector.

4. Connect the wiring to the appropriate screw terminals.

5. Replace the clear cover from the switch.

Switching function

As pressure rises above 

setpoint:

1 NC opens, 2 NO closes

As pressure falls below 

setpoint:

2 NO opens, 1 NC closes

Wiring

Operation & Adjustment

Adjusting the Set Point

1. Remove the clear cover 

 from the switch.

2. Adjust the switch to the desired set point by turning the 

dial. The black arrow on the dial indicates the set point 

.

3.  After adjusting the set point, verify that the pressure switch 

operates as intended by using an accurate pressure gauge 

connected upstram of the switch.

4. Replace the clear cover.

Automatic Reset and Operation

The NC contact of the GGAO-A4... breaks when pressure 

rises above the set point. It makes automatically when pres-

sure falls below set point.

All  wiring  must  comply  with  local  electrical 

codes, ordinances and regulations.

Do not exceed the switch ratings given in the 

specifications and on the switch.

Medium Pressure