Dungs DMA Installation Instructions Download Page 2

2 … 3

Mounting the DMK/6 to a shutoff valve

1. Turn off the gas supply.
2. Refer to the flow direction on the valve housing. 
3.

 

Note:

 Aluminum to Aluminum connection:

    Coat inner and outer threads with a suitable 
    lubrcant before sealing the inner and outer threads.
4.

 

DO NOT

 use any part of the DMA or the mounting 

    bracket of the DMK/6 assembly as a lever to 
    tighten! Use appropriate sized wrench.
5. Tighten connections. Use the chart below for 
    torque specifications.
6. Perform a complete leak test after installation.

Mounting DMA to a DMK/6 butterfly valve

1. Remove the clear cover from the DMA
2. Insert the shaft from the DMA into the linkage 
    of the DMK/6 until the motor is flush on the DMK/6 
    mounting plate. snug the set screw with a 2.5 mm 
    allen wrench.  Torque to 15 lb-in.
3. Insert the M5 X 55 mounting bolts (supplied) 
    through the DMA motor mounting holes. Take care 
    not to break the plastic covers off of the bolt holes. 
    Hand tighten the 8mm hex nuts that are supplied.
    Torque the bolts to 45 lb-in.

 

                         DMK

 

707 

710 

712 

715 

      720

 

  

                   Max. lb-in

 560 

750 

875 

940 

     1190

 

MOUNTING

Wiring the DMA

1. Remove all power supplies.
2. Use minimum AWG #16 class 1 wiring for all terminals.
3. Remove cover to access the terminal block. 
4. 

Only use the specified terminals. Terminal 8 must 

    be the + input and terminal 10 must be the - input.

Terminal Block for DMA

WIRING

5. The cover has an intergrated protective barrier that  
    physically separates the wiring from the moving 
    adjustment switches and cams. Wiring must be
    properly routed so that the cover can be installed.
6. For terminals 8 and 10, use properly sheilded wires, that
    are grounded on both sides, and run through conduit 
    containing only low voltage (24V) wiring.