Karl Dungs, Inc

524 Apollo Drive,Suite 10 Lino Lakes, MN 55014  U.S.A.  

Phone: (651) 792-8912  Fax: (651) 792-8919  Website: www.dungs.com  E-mail: [email protected]

1 … 3

Max. Body Pressure

  15 PSI (1000mbar)

Mounting Position

  Mulitpoised

Ambient Temperature for DMK

  +5° F to +140° F (-15° C to 60° C)

Actuator angle

  90 degrees from open to closed  

Approvals

  UL Listed Component: File No. MH18741

  Commonwealth of Massachsetts Approved Product

  Approval code G1-1107-35

Max. Contact Rating for Auxiliary Switch

  1.5 Amps at 120 Vac 50/60 Hz

Enclosure Rating

  NEMA Type 1 enclosure (standard with DMA)
  NEMA Type 4 enclosure avaliable (Part #D240 456)

Input Control 

    

  4 to 20 mA 

Position Feedback or Slave Output

 

  4 to 20 mA; 500 ohm maximum impedance.
  Resistence across terminals 8 & 10 is 250 Ohms.

Ambient Temperature Rating

  +15 °F to +120 °F (-10 °C to 50 °C)

Approvals

  UL Recognized Component: File No. E142163
  CSA Certified: File No.157406-1378915

  Commonwealth of Massachsetts Approved Product

  Approval code G1-1107-35

The 

DMK/6 

butterfly control valve actuates from 0 to 90 

degrees in either direction; it is not a tight shut-off valve. 
Input-side male thread and output-side female thread en-
able assembly directly to DUNGS shutoff valves. 

Gases

  

Natural gas, propane, butane, noncorrosive gases,

  and air.  Suitable for up to 0.1% by volume, dry H

2

S. 

Max. Pressure

   7 PSI (500mbar) MH194167

Max. Differential Pressure

   1.5 PSI (100mbar)

DMA 
Motor Actuator
Installation Instructions

 

The 

DMA

 actuator drives from 0 to 90 degrees via 4-20 mA 

input signal. It can move in any direction and stop anywhere 
over the entire 90 degree stroke.

Electrical Rating

   110-120 Vac (+10 / -15%) 50-60 Hz

Max. Power Rating

   2.0 VA Holding, 5.4 VA Operating

Max. Torque Ratings
 

Timing   

Holding  

Operating

 

 

12.4 in-lb 

5.3 in-lb

 

12 

 

24.8 in-lb  

8.9 in-lb  

 

30 

 

26.5  in-lb  

17.7in-lb 

Position Resolution 

   0.08mA resolution; minimum of 0.45° per step

DMA ACTUATOR SPECIFICATIONS

DMA/DMK Installation Manual - P/N 80118 - Ed. 01/08

DMK/6
Butterfly Control Valve
Installation Instructions 

ATTENTION

 • Read these instructions carefully.
 • Failure to follow them and/or improper installation may     

    cause explosion, property damage and injuries.

 • Installation must be done with the supervision of a 

    licensed burner technician.

 • Check the ratings in the specifications to make sure that 

    they are suitable for your application.

 • Never perform work if gas pressure or power is applied,       

    or in the presence of an open flame.

 • Once installed, perform a complete checkout including  

    leak testing.

 • Verify proper operation after servicing.
 • The system must be installed, used, and maintaned to

    meet all applicable national and local code requirements 
    such as but not limited to NFPA 86,CSD-1, ANSI Z21.13,
    UL 795, NFPA 85, or CSA B149.3. 

DMK BUTTERFLY VALVE SPECIFICATIONS

Burnerparts.com