background image

 

This manual can be modified without any warning 

4

Due to the detecting units feature of being able to rotate on all axes, it is also possible to 
place the sensor on a slanting wall upwards without using further clamps, however 
detection from lower beams should be lost. Reducing the mounting height can 
compensate for this loss.

 

 

 

 
For a sure and repeatable detection, it is suggested to install the sensor in order to have 
the intruder that moves accross the beams and not toward the sensor. 
 
The more interesting feature of this infrared sensor is to have two different and completely 
independent detection heads that can be orientated separately. This allows the infrared 
sensor to function in “OR/AND” mode. If turned to “OR”, when one of the two sensors 
detect a movement, an alarm is triggered. When turned on “AND” mode

,

 only detection by 

both sensors will create an alarm signal. Furthermore it is possible to select the priority of 
the head that triggers the alarm. This means higher security and less risk of “unwanted 
alarms”. The optical range is 8m per ray. 
 

Sensor use: 

Mount the sensor taking account of a max coverage area of 8 m in distance and a max. 
angle of 100° (see fig. 1). 
 
Fix the bottom of the sensor with the 4 fisher screws included (Ø6mm – screw 3,5x35mm 

– see points  

  in figure). 

Insert the extension for the Tamper protection (see  

  in figure). 

Drill the sensor case in the point  

  and pass through the hole the signalling wires to be 

connected to the wireless transmitter. 
Put the wireless transmitter in the empty case behind the sensor and fix the sensor with 

the 3 included screws (2,9x19mm – see points  

 ) 

 
To set the sensitivity of the detectors, start from a minimum setting condition i.e. 

regulation trimmers turned in an anticlockwise direction

 and 

detectors placed at the 

lowest possible position.

 Increase gradually the range of detection only in the area you 

want to protect, in order to avoid the risk of detecting insignificant movements and 
unnecessary alarms. 
 

AFTER POWERING THE SENSOR, IT IS ACTIVATED AND STABILIZED ONLY 20 
SECONDS AFTER THE END OF FLASHING RED LED’S. 

D

C

B

A

 

Summary of Contents for DIRVE K

Page 1: ...the product in order to use all its capacities DIRVE K LOW CONSUMPTION IR OUTDOOR DUAL SENSOR MANUAL VERSION 0 5 The above symbol guarantees that the item complies with EU norms EUROPEAN COMMUNITY on...

Page 2: ...IRVE K sensor can be fixed at heights between 50 and 250 cm on vertical surfaces walls or posts using the anchor clamp and protection item STAK Obviously the detection units MUST be oriented horizonta...

Page 3: ...with the A beam upper detecting unit and ends in the AND time by detecting the B beam This function permits a directional detection in other words it allows the sensor to detect an approach towards t...

Page 4: ...at triggers the alarm This means higher security and less risk of unwanted alarms The optical range is 8m per ray Sensor use Mount the sensor taking account of a max coverage area of 8 m in distance a...

Page 5: ...This manual can be modified without any warning 5 A B A C D D A B A...

Page 6: ...It is mandatory to respect the position of the different colors because they have different purpose and if they are scrambled it is not guaranteed a good weather protection BLACK O RINGS 1 2 3 4 Mount...

Page 7: ...Open Buzzer enabled JP7 Alarm Blue Led Closed led enabled Open led disabled IR HEADS RANGE TRIMMERS R25 Upper IR Head Sensitivity setting of upper head Turn in clockwise direction to increase the ran...

Page 8: ...ection leds alarm led and buzzer if JP4 is closed useful during the test of the detection area OFF Normal use DIP5 Continuous Transmission ON the sensor make a cyclic switch of the alarm output with 1...

Page 9: ...CONSUMPTION Stand by 15uA ALARME 10mA SIGNALLING 1 LED for upper head 1 LED for lower head 1 LED for alarm transmission ALARM INPUTS 2 sensible elements with selectable OR AND mode TEST Test function...

Reviews: