background image

Contatto

ModDALI

Groups

This tab features a grid where each ballast, on the selected
line, can be assigned to one or more groups. This choice
can be done by clicking on each cell located at the inter-
section between the desired ballast (the columns) and the
desired group (the rows). A X
symbol   will   be   shown   in   the
related cell.
In   the   example   of   the   figure
on this side, the group 1 con-
tains   the   ballasts   1-2-5,   the
group 2 the ballasts 1-3 and
the group 3 the ballasts 2-4-5.
The button Deselect remove all the X symbols on the grid.
The execution of the assignment of the groups (clicking on
the button Start) will take in account only the ballast dese-
lected by the X symbol. A timer icon will inform that the op-
eration is running. At the end of the procedure, the normal
mouse icon will be restored.
The time required by this procedure is about:

T = 8sec + (0,5sec x “nr. of X in the window”)

If   the   procedure   has   not   been   successfully   executed,   a
warning message will be shown; in this case the procedure
has to be repeated.

The correctness of the changes made can be checked by
switching on and off the ballasts using the buttons identified
as 0 (off) and I (on); the buttons on the top side act on the
single ballast, the buttons on the left side act on the groups
and the two big buttons 0 and I switch off and on all the bal-
last on that line.
The buttons From File and To File allow to store and recall
the settings of the groups; take in account that it is not pos-
sible to read, from ModDALI module, the current settings of
the groups, therefore it is strongly recommended to save
them into a file for future modifications.

Global Settings

In this tab it is possible to set, for all ballasts on the select-
ed line, the following parameters:

MIN

: minimum brightness value (0-100%); enabling the Re-

set check box, the default value will be restored (1%).

MAX

: maximum  brightness value  (0-100%); enabling the

Reset check box, the default value will be restored (100%).

BUS F.

: the brightness value (0-100%) to be recalled by

ballasts during bus  failure conditions on  

Contatto

  and/or

DALI bus; the value 101 means that the outputs will keep
the last value .

Ramp

: the ramp value in seconds.

Pwr On

: the brightness value (0-100%) to be recalled by

ballasts at their power up; the value 101 means that the
value outputted before the power off will be recalled.

Preset

: writing a value (0 to 100) and clicking on the button

on the right side, the brightness will be forced to that value.

M1 

¸

 M16

: the value to be loaded into the 16 presets; the

button on the right side allows to recall the related preset
stored into the ballast.

Enter in this tab the desired parameters and then click on
Start to send the configuration. A timer icon will inform that
the operation is running. The time required by this proce-
dure is about 15 seconds. If the procedure has not been
successfully executed, a warning message will be shown;
in this case the procedure has to be repeated.

Status

DUEMMEGI

 s.r.l. - Via Longhena, 4 - 20139 MILANO

Tel. 02/57300377 - Fax 02/55213686 – 

www.duemmegi.it

Rel.: 2.4 October 2017

Page 7 of 9

Summary of Contents for CONTATTO ModDALI

Page 1: ...ALI module provides a 5 way terminal blocks for the connection to Contatto bus a 2 way terminal block for the supply voltage of DALI section and a 9 way terminal blocks for the connection to the 4 DAL...

Page 2: ...llowing table gives some rules for the MINIMUM ca ble section As said above no special cables are required for the 4 DALI lines provided that they have double insula tion In any case the distance betw...

Page 3: ...ballast will not be under stood the value 129 will be reported If the brightness level of each ballast on each DALI line is required by the application a script for MCP is available for this purpose c...

Page 4: ...t level The code 113 enable again the polling the current status of the polling is re ported bu the point 11 of the input channel if enabled At the module power up or after a reset the polling is alwa...

Page 5: ...ting parameters of each DALI channel and to perform some diagnostic functions The setting up is performed via the Contatto bus and MCP through a specific configuration panel which can be opened select...

Page 6: ...tion of the mapping procedure pressing the but ton Start will take place only for the ballasts selected by the related checkbox A timer icon will inform that the oper ation is running At the end of th...

Page 7: ...ake in account that it is not pos sible to read from ModDALI module the current settings of the groups therefore it is strongly recommended to save them into a file for future modifications Global Set...

Page 8: ...ry each scenery will be a file Commands This tab provides a several commands belonging to DALI protocol this section is addressed to highly qualified staff so it is recommended not to use it if you ar...

Page 9: ...d the wiring of the Contatto bus line and the re lated devices must be performed according to the recommenda tions of the manufacturers reported on the specific data sheet of the product and according...

Reviews: