L2000641 Installation guide for DucoBox Silent (Revision H | 13.07.2020)

3

Press ‘HIGH’ or ‘LOW’ to activate the configuration mode for 30 minutes�

Then close the cover firmly.

Which configuration mode should I choose?

Button

Air calibration using 'HIGH'

This method is standard and has the 

lowest consumption� Recommended 

in the majority of homes�

Air calibration using 'LOW'

This method offers a boost mode 

but may give rise to more noise 

and higher consumption�

Low mode (10%)

Low mode (14-33%)*

Medium mode (50%)

High mode (100%)

High mode (100%)

Boost mode (143-333%)*

The percentages in the table indicate what percentage of the flow rate configured will be extracted�

The configuration mode chosen does not affect the operation of the AUTO mode�

* In the ‘LOW’ configuration, the percentage in low mode and boost mode is dependent on the type of 

home (see section "06�D Setting type of home" on page 11) and limited to the maximum achievable 

ventilation system flow rate�

HIGH

LOW

4

Close the DucoBox cover� 

Ensure it forms an airtight seal with the DucoBox�

5

Select the duct with the highest flow rate and restriction�

6

Measure at the vent and adjust the DucoBox rpm until the desired flow rate is 

obtained� This can be done in two ways:

• Using the   (lower) and   (higher) buttons on a paired User controller or CO

2

/

Humidity Sensor*�

• Using the ‘DOWN’ and ‘UP’ buttons on the DucoBox� This requires the cover to 

be removed temporarily� Always close the cover after every measurement.

Pressing the buttons once is equal to 1% (= approximately 2 to 3 m3/h per press of the button depending 

on the restriction in the ducts)�

 / 

 / 

7

Now measure the other vents� The flow rate from these other vents must only be 

adjusted at the vents themselves.

8

Repeat steps 

6

 and 

7

 until the desired flow rate has been obtained at each vent�

9

Exit configuration mode� This can be done in two ways:

• Long-press ‘AUTO’ on a paired User controller or CO

2

/Humidity sensor* until 

the 4 LEDs light up white briefly and then turn yellow again�

• Press ‘ENTER’ in the DucoBox and then immediately close the cover on the 

DucoBox� If the cover was not closed, you can pull the plug out of the power 

socket for a few seconds after closing the cover in order to reboot the DucoBox�

The DucoBox will now perform a calibration by speeding up high� This may take up 

to 1�5 min� Calibration will be complete once the DucoBox slows down the ‘AUTO’ 

button LEDs on the User controllers / CO

2

/Humidity sensors* will turn white, as 

will the LED on the DucoBox�

ENTER

* Depending on the software version of the User controller / CO

2

/Humidity sensor�

Summary of Contents for 0000-4250

Page 1: ...Installation guide ENGLISH DucoBox Silent Connect Product version 17xxxx and above Step by step instructions duco tv L2000641 Revision H 13 07 2020 ...

Page 2: ...home 11 06 E Pairing components 12 06 F Removing replacing components 12 06 G Tips 13 07 Air calibration 13 07 A Air calibration procedure for DucoBox Silent Connect 13 07 B Checking 15 08 Maintenance service 15 09 Warranty 15 Vero Duco Handelsstraat 19 8630 Veurne Belgium tel 32 58 33 00 33 fax 32 58 33 00 44 info duco eu www duco eu DUCO HANDELSSTRAAT 19 VEURNE B 8630 09 See www duco eu for info...

Page 3: ...ts stale air with excessive CO2 content or humidity On the other it is the system master or brain of the system It receives and interprets signals from slave components measure ments from sensors or manual input on the basis of which it controls the ventilation system It is inadvisable to connect the DucoBox via a duct or directly to an extractor hood regardless of type This usually causes exces s...

Page 4: ...SEC in kWh m an SEC class Trade mark Duco Model reference 0000 4250 0000 4455 DucoBox Silent Connect Indoor outdoor air tightness in m h Annual electricity consumption AEC in kWh electricity a Annual heating saved AHS in kWh primary energy a DucoBox Silent Connect Declared maximum external leakage rates in Mixing rate in Position and description of visual filter warning Instructions to install reg...

Page 5: ...nsumption SEC in kWh m an SEC class Trade mark Duco Model reference 0000 5133 DucoBox Silent Connect 325 Indoor outdoor air tightness in m h Annual electricity consumption AEC in kWh electricity a Annual heating saved AHS in kWh primary energy a DucoBox Silent Connect 325 Declared maximum external leakage rates in Mixing rate in Position and description of visual filter warning Instructions to ins...

Page 6: ...old 3355 4290 5536 average 1715 2193 2830 warm 776 992 1280 Specific energy consumption SEC in kWh m an SEC class Trade mark Duco Model reference 0000 5132 DucoBox Silent Connect 225 Indoor outdoor air tightness in m h Annual electricity consumption AEC in kWh electricity a Annual heating saved AHS in kWh primary energy a DucoBox Silent Connect 225 Declared maximum external leakage rates in Mixing...

Page 7: ... 125 mm upward from 30 m h 100 mm less than 30 m h Or an equivalent based on a specific duct calculation p e for ducts placed in floor screed Make sure that the total counter pressure in the ducts is as low as possible preferably 150Pa and that the airspeed in every duct does not exceed 3 m s 1 7 8 9 10 2 3 4 5 6 DISCLAIMER no rights can be derived from this document All tips are only advisory All...

Page 8: ...ni cation Print see page 10 RF RF Wired RF 24 VDC 24 VDC 24 VDC 230 VAC 230 VAC A A B B GND GND B A GND POWER SUPPLY User controller User controller Max 99 Wired 25 RF Tronic vent Tronic vent 230 VAC 230 VAC DucoBox Silent Connect RF obstacle free zone Do not place any obstacles causing RF interference or other devices with an RF connection within a radius of at least 30 cm around the RF component...

Page 9: ...ed The cable required is a 5 x 0 75 mm data cable We strongly advise using a shield ed cable This is to prevent any interference that may affect the data communi cation Any Tronic grilles will be supplied with a 5 x 0 25 mm cable which can be connected via a splicing terminal block DUCO WIRED Power supply 24 VDC Wiring 5 x 0 75 mm 5 x 0 25 mm from Tronic grilles Maximum distance up to 300 m Maximu...

Page 10: ... can be done using the Duco Network Tool This us er friendly software also enables problems in the system to be pinpointed The Duco Network Tool is issued to every installer after attending a free training course at the Duco Academy Please refer to our website or your Duco dealer for further information Only in Belgium and the Netherlands 06 B Installer User mode To add components to the network r...

Page 11: ...tting type of home Setting the type of home and number of occupants correctly will provide the ventilation system with a better basis to adjust the mid position There are two types of home low rise e g a house and high rise e g a flat Configuration of this component is obligatory in the Netherlands The standard setting for a DucoBox is as a low rise home for 4 or more occupants Setting type of hom...

Page 12: ...ch a button of the component must be pressed controls component X 06 F Removing replacing components Removing paired components from the network or replacing is only possible within 30 minutes after the component is paired in or is restarted Restarting can be done by disconnecting the power for a moment After a time span of 30 minutes remove and replace operations are ignored This is valid for all...

Page 13: ...r information about determining ventilation flow rates 07 A Air calibration procedure for DucoBox Silent Connect The air calibration procedure must be carried out on a calm day no more than wind force 2 leaves rustling feel ing the wind in one s face Air calibrating the DucoBox Silent Connect 1 Set all exhaust vents so they match the desired flow rate in accord ance with the table below Proper pre...

Page 14: ... rate is obtained This can be done in two ways Using the lower and higher buttons on a paired User controller or CO2 Humidity Sensor Using the DOWN and UP buttons on the DucoBox This requires the cover to be removed temporarily Always close the cover after every measurement Pressing the buttons once is equal to 1 approximately 2 to 3 m h per press of the button depending on the restriction in the ...

Page 15: ...after 15 minutes 08 Maintenance service Please refer to the maintenance instructions at www duco eu and view the videos on duco tv for more information For service problems as a user Please contact your installer Keep the serial number of your product to hand For service problems as an installer Please contact your Duco products seller Keep the serial number of your product to hand 09 Warranty All...

Page 16: ...16 ENGLISH L2000641 Installation guide for DucoBox Silent Revision H 13 07 2020 Installed by L2000641 Document last modified on 13 07 2020 revision H ...

Reviews: