background image

6.

If measured superheat is:
• more than required, slowly add refrigerant to obtain

required superheat.

• Less than required, slowly recover refrigerant to

obtain required superheat.

NOTE:

Each time charge is added to or removed
from the system, allow the system to run
approximately 15 minutes before
pressure/temperature readings are re-taken
and superheat calculations made.

TXV  System  Charging

1.

Operate unit for minimum of 10 minutes.

2.

Measure pressure and temperature at liquid valve
service port. Use a good thermistor or electronic
thermometer.

3.

Subtract measured temperature from saturation
temperature (of measured pressure) measured to
obtain subcooling. Refer to 

Table 4

 for saturation

temperature of R-22.

4.

The subcooling level should be as specified on the unit
specification sheet. In the absence of the specification
sheet, use 12-14°F subcooling.

5.

If measured subcooling is:
• more than required, slowly recover refrigerant to

obtain required subcooling.

• less than required, slowly add refrigerant to obtain

required subcooling.

Defrost  System  (Heat  Pumps  Only)

A defrost system consisting of a defrost thermostat

(mounted to the outdoor coil) and a defrost control board
(in the control box) provides automatic defrosting of the 

outdoor unit when required. The defrost function is
initiated and terminated based on time and temperature.
During frosting conditions, the compressor will operate for
30, 60 or 90 minutes (field adjustable, factory set for 90
minutes) before switching to the defrost mode.

In geographical areas where heavy snowfall, freezing

rain, or extensive operation in 20°F-40°F range is
expected, the setting should be changed to 30 or 60
minutes. This is performed by relocating the "RUN TIME"
jumper on the defrost board from the pins labelled "90" to
either the "30" or "60" pins.

The defrost board provides a five (5) minute time delay

for compressor short cycle protection. To bypass this
delay, short the two "TEST" terminals together for 2
seconds.

For defrost system checkout, with the system running in

the heating mode, short the two "TEST" terminals together.
The heat pump will go into the defrost mode for as long as
the "TEST" terminals are shorted together.

Unit  Maintenance

The unit should be inspected and cleaned on an annual

basis by a qualified technician. This should include
checking for adequate clearances, electrical connections,
duct connections/blockages, air filters, airflow, lubrication,
and operational performance of system. 

Coils may

require cleaning. The coil should always be cold when
cleaning. Use an alkaline-based cleaner only.
Cleaning a hot coil or using an acid based cleaner will
remove the paint from the fins and may clog the coil.

Table 4 - R-22 Saturation Temperature / Pressure Chart

Pressure

(psig)

Temp.

(°F)

Pressure

(psig)

Temp.

(°F)

Pressure

(psig)

Temp.

(°F)

Pressure

(psig)

Temp.

(°F)

Pressure

(psig)

Temp.

(°F)

Pressure

(psig)

Temp.

(°F)

19.3

-6

31.8

9

44.1

21

58.8

33

76.0

45

155.7

85

20.8

-4

32.8

10

45.3

22

60.1

34

77.6

46

168.4

90

22.4

-2

33.7

11

46.4

23

61.5

35

79.2

47

181.8

95

24.0

0

34.7

12

47.6

24

62.8

36

80.8

48

195.9

100

24.8

1

35.7

13

48.8

25

64.2

37

82.4

49

210.8

105

25.6

2

36.7

14

49.9

26

65.6

38

84.0

50

226.4

110

26.4

3

37.7

15

51.2

27

67.1

39

92.6

55

242.7

115

27.3

4

38.7

16

52.4

28

68.5

40

101.6

60

259.8

120

28.2

5

39.8

17

53.6

29

70.0

41

111.2

65

277.8

125

29.1

6

40.8

18

54.9

30

71.4

42

121.4

70

296.7

130

30.0

7

41.9

19

56.2

31

73.0

43

132.2

75

316.5

135

30.9

8

43.0

20

57.5

32

74.5

44

143.6

80

337.4

140

20407502

ISSUE 0144

       Page 6 of 8

Summary of Contents for AC10B Series

Page 1: ... of interconnecting tubing Crankcase heaters standard on all 3 phase models with reciprocating compressors AC10B D u c a n e A i r C o n d i t i o n e r UNIT DIMENSIONS MODEL SQUARE BASE HEIGHT NUMBER INCHES INCHES AC10B18 22 1 2 x 22 1 2 23 1 2 AC10B24 22 1 2 x 22 1 2 23 1 2 AC10B30 A 22 1 2 x 22 1 2 23 1 2 AC10B36 B 36TA 36F 22 1 2 x 22 1 2 27 1 2 AC10B42 A 22 1 2 x 22 1 2 31 1 2 AC10B48 A 48TA ...

Page 2: ...pter required Use of 7 8 vapor line reduces performance approximately 3 4 DUE TO OUR POLICY OF CONTINOUS IMPROVEMENT SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AC10B AC10B AC10B AC10B AC10B AC10B AC10B AC10B AC10B AC10B AC10B Model Number 18 24 30 A 36 B 36TA 36FA 42A 48 A 48TA 48FA 60 A 60T 60F P H Y S I C A L D A T A Face Area ft2 8 19 9 83 11 51 14 83 Tube Fin Material CU AI Smooth Gro...

Page 3: ... with the National Electrical Code NFPA 70 ANSI C1 1993 or current edition and Canadian Electrical Code Part 1 CSA C22 1 The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test equipment Failure to carefully read and follow all instructions in this manual can result in equipment malfu...

Page 4: ...allow for drainage of defrost water and prevent ice build up heat pump only above expected snowfall levels heat pump only DO NOT LOCATE THE UNIT on brick concrete blocks or unstable surfaces near clothes dryer exhaust vents near sleeping area or near windows under eaves where water snow or ice can fall directly on the unit Roof Top Installations If necessary to install units on a roof structure be...

Page 5: ...der valve core installed and require use of charging hoses with depressors DO NOT heat valve body above 250 degrees F Service valves must be wrapped with wet rags or otherwise protected from heat during brazing Use care to ensure no moisture enters valves or Schraeder valve cores if wet rags are used Brazing Connections WARNING FIRE HAZARD Refrigerant and oil mixture under pressure could ignite as...

Page 6: ... CAUTION BODILY INJURY HAZARD This is not a backseating valve Care must be taken to prevent dislodging retainer ring when opening valve FAILURE TO DO SO COULD RESULT IN BODILY INJURY Replace service valve cap and torque to 8 11 ft lb on 1 4 and 3 8 valves 12 15 ft lb on 5 8 and 3 4 valves 15 20 ft lb on 7 8 valves NOTE The cap is the primary seal and must be tightened to prevent leaks Torque gauge...

Page 7: ...tially be adjusted for line set lengths other than 15 feet For line sets shorter than 15 feet in length remove charge per Table 3 For line sets longer than 15 feet add charge per Table 3 Oil charge is sufficient for all line lengths Final charge adjustments must be in the cooling mode by subcooling superheat check only when outdoor ambient is above 60 F If the outdoor ambient is below 60 F adjust ...

Page 8: ...hanged to 30 or 60 minutes This is performed by relocating the RUN TIME jumper on the defrost board from the pins labelled 90 to either the 30 or 60 pins The defrost board provides a five 5 minute time delay for compressor short cycle protection To bypass this delay short the two TEST terminals together for 2 seconds For defrost system checkout with the system running in the heating mode short the...

Page 9: ...eaning filtering constant fan operation is recommended On models without a Fan Selection Switch the fan will always cycle with the outdoor unit Important System Information Your system should never be operated without a clean air filter properly installed Return air and supply air registers should be free from restrictions or obstructions to allow full flow of air On heat pump systems increasing y...

Page 10: ...rom the condenser coils WARNING SHARP OBJECT HAZARD Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves Failure to follow this warning could result in bodily injury Use a soft bristle brush with light pressure only DO NOT damage or bend condenser coil fins Damaged or bent fins may affect unit operation Painted Surfaces For maximum protection of the unit s ...

Reviews: