DualLite UFO-RP3 Instructions Download Page 2

NOTE: All the branch circuit wiring has to be ready as well as an unswitched source of power before the
fixture is installed.

From the same branch circuit.

Both AC and Emergency Ballasts must be Fed

CAUTION Battery connector has to be opened to prevent high voltage on output leads (Red and Yellow).
Wait until all

power to the emergency ballast

the installation process is completed and AC is supplying

1. AC power has to be off before installation.

2. Choose the right wiring diagram to connect the emergency ballast to AC ballast and lamp.

3. Please ensure the electrical connections conform to the National Electrical Code and local regulations if applicable.

4. Follow the diagram 1&2 to install the emergency ballast in the ballast channel.

5. Wall switch has to be connected properly (Check diagram 3), Match the violet and brown leads to connect the

to the

TBIL

The

would be on

TBIL

emergency ballast(Check diagram 4).

after the fixture is  installed properly.

DIAGRAM 1

DIAGRAM 2

UFO-RP3

DIAGRAM 3

UNSWITCHED FIXTURE

SWITCHED FIXTURE

BLACK

HOT A.C. LINE

COMMON

TBIL

WHITE

WHT/BLK

WHITE

(277V) ORG

(120V) BLK

1

1

WHT

+ RED

A C BALLAST

. .

Select proper voltage lead. Cap unused lead.

BROWN

VIOLET

WHT/RED

BLACK

HOT A.C. LINE

COMMON

TBIL

WHITE

WHT/BLK

WHITE

(277V) ORG

(120V) BLK

1

1

WHT

+ RED

A C BALLAST

. .

Select proper voltage lead. Cap unused lead.

BROWN

VIOLET

WHT/RED

UFO-RP3

6.Please search in readily visible location and stick the label with

CAUTION: This Unit Has More Than One Power  Supply

To Reduce The Risk Of Electric

Connection Point.

Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses And Emergency

Power Supplies Before Servicing.

8. The battery needs to be charged for one hour in order to have short-term  testing on the emergency function. Before having a

emergency function testing,

long-term

the battery in emergency ballast has to be charged for 24 hours.

7. Do not join the inverter connector until the fixture is completely installed and AC power is supplied to the emergency ballast.

NOTE: MARK AN APPROPRIATE LABEL ON INDICATOR LIGHT AND

TEST SWITCH AFTE INSTALLATION.

Page 2

Emergency Ballast

Ballast Channel Cover

Test Button,Indicator Light(TBIL)

Test Button,Indicator Light(TBIL)

Emergency Ballast

INSTALLATION INSTRUCTIONS

before joining the battery connector.

Reviews: