Operating Instructions (Cont.)
7.
Allow the 1 minute self-test to end (or press the test switch
again to cancel self-test cycle).
8.
Press the test switch again. Verify that the "Lamp Fail" LED
and the "Service Alert" LED are not illuminated.
Operation
SPECTRON electronics operation is fully automatic. Accidental
discharge of the unit battery prior to energization is prevented by
an AC lockout circuit. The unit's green "Operating Status" LED,
located on the Spectron display panel, illuminates to indicate
the presence of AC power. The unit's red "Service Alert" LED
will blink after application of AC power if the battery connection
is not completed. During normal operation, the unit's charging
circuit maintains the battery at full capacity and the Spectron
Controller constantly monitors charger performance. Should the
terminal voltage vary from design parameter values, the unit's
red "Service Alert" LED will blink , indicating a malfunction of
the battery or charger. Upon interruption of normal AC power,
or brownout condition, the Spectron Controller automatically
switches the emergency lighting load to the battery. Emergency
power will be provided for a minimum of 90 minutes. During
emergency operation, the battery is protected from deep
discharge by a low voltage battery disconnect circuit. Upon
return of normal AC power, a 15 minute retransfer delay holds
the unit in emergency operation mode allowing utility voltage
to stabilize prior to reconnection. The charger will then begin a
recharge cycle. A temperature compensated float type charger
is provided in LZ models utilizing Pure-Lead or Lead-Calcium
batteries. This charger is designed to adjust charging voltage
with changes in ambient temperature to maximize the life and
performance of the unit's batteries. LZ Series models utilizing
Nickel-Cadmium batteries require no temperature compensation
as they utilize a constant current type charger design to maintain
the unit's batteries. The charger will bring the battery to full
capacity within acceptable U.L. time standards. The Spectron
Controller automatically initiates a one minute discharge/
diagnostic test every 28 days ± 3.5 hours and a 30-minute
discharge/diagnostic test every 6 months ± 1 day. These tests
exercise the unit’s battery to optimize its capacity and allows
the SPECTRON Controller to analyze emergency operation
performance. Any malfunction of the unit’s transfer circuit or
emergency lamps will cause the red "Service Alert" LED on
the unit's display panel to blink. During normal operation, all
red "Service Alert" LED blinking indications of unit malfunction
remain latched until corrected and retested. A manual test
switch allows a user programmable 1, 5, 30 or 60-minute
diagnostic/discharge test at any time. During all automatic and
user initiated self-tests, the unit's green "Operating Status" LED
will blink to indicate a diagnostic cycle in process.
2.
Using a pen or a small screwdriver, select the proper load
range by pressing the appropriate rocker switch to the left as
shown in the Fig. 1 example above.
CAUTION: Only one rocker must be selected.
3.
With a small screwdriver, turn the Lamp Sense Adjust
potentiometer fully
clockwise
.
4.
Press the unit test switch once. The emergency lamps will
illuminate and a 1 minute self-test will begin. The green
"Operating Status" LED on the unit's Spectron control
panel will also begin to flash. The "Lamp Fail" LED located
on the charger/distribution board (see Fig.1) should not be
illuminated at this time. If "Lamp Fail" LED is illuminated,
select the next lower load range. Example: If load range "4"
was selected, select load range "3".
5.
Slowly turn the "Lamp Sense Adjust" potentiometer
counterclockwise
until the "Lamp Fail" LED on the charger/
distribution board illuminates. Then turn the adjustment pot
back clockwise
just slightly beyond
the point where the
"Lamp Fail" LED turns off to avoid false failure indications. At
this point, the red "Service Alert" LED on the unit's Spectron
control panel will begin a repetitive cycle of flashing 5 times
followed by a pause ("lamp fault" service alert).
6.
While the self-test is still in progress, disconnect one of the
emergency lamp wires from the charger/distribution board.
The "Lamp Fail" LED on the charger/distribution board
should turn on. Reconnect the lamp wire and observe that
the "Lamp Fail" LED goes out. If "Lamp Fail" LED remains
illuminated, turn the "Lamp Sense Adjust" potentiometer fully
clockwise and repeat step 5.
1
2
3
4
OPEN
Lamp Fail LED
Lamp Sense Adjust
Potentiometer
Example:
Press here to select load
"RANGE" switch setting "1".
*
Fig. 1
Charger Distribution Board
Spectron
®
Self-Diagnostic Electronics Option
0601570 E
currentlighting.com/dual-lite
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 2 of 2
Rev 06/06/22
spectronopinstr-units-0601570_e-092508_R01