background image

Page 6

60706-133

8290-01

7. Check all electrical connections in the system to be ener-

gized by the generator. Make sure the connections are cor-
rect and are tight.

8. Make sure all loads are turned off. Do not start the genera-

tor under load.

GENERATOR STARTING PROCEDURE

1.  With the power take-off drive disengaged, start the engine

which will drive the generator. Run the engine long enough
to warm it up before proceeding, so that it will run smoothly
and achieve full power under generator load.

2. With engine idling, engage the power take-off drive.

3. Watch the voltmeter on the generator and slowly increase

engine speed until the output reaches approximately 260
volts, in green portion of voltmeter scale.

4.  With engine and generator running smoothly, switch on

the electrical load while watching the voltmeter.

NOTE: Equipment Damage
If the load includes motors turn them on one at a time, highest
starting current motor first, next highest second, etc.

Readjust engine throttle to keep generator output under load
at 240V (in green portion of voltmeter scale). If engine is
equipped with speed governor, it may automatically readjust
the throttle as the load changes and keep the generator output
at the proper level. However, some governors are not sensitive
enough to maintain proper output under changing load, and in
such cases the throttle will have to be manually readjusted .

GENERATOR SHUTDOWN PROCEDURE

1. Switch off electrical load.

2. Reduce speed of engine driving generator to idle.

3. Disengage power take-off drive, and allow generator to

coast to a stop.

WARNING: Personal Injury
Never try to manually stop the generator.  Always let it coast
until it stops.

5. Shut off the engine.

4. Disconnect drive shaft (tumbling bar)

power take-off end first, then generator end.

Figure 6

Figure 7

3. Make sure the drive shaft (tumbling bar) is assembled with

its universal joint knuckles “synchronized,” as illustrated in
Figure 7. If knuckles are not synchronized, the bar will chat-
ter when rotating, which will cause the generator output
voltage to flicker.

DANGER: Personal Injury

POWER TAKE-OFF MUST BE DISENGAGED AT THIS TIME.

4. Couple the tractor to the generator with the drive shaft (tum-

bling bar). Couple the tumbling bar to the generator input
shaft first, then to the power take-off shaft. Check align-
ment, tractor, power take-off shaft (tumbling bar), and gen-
erator input shaft should form a straight (or nearly straight)
line, with less than 15° misalignment between the shafts.
Misalignment will cause generator output voltage to flicker.

CAUTION:

Make sure that all tumbling bar lock pins are engaged and
that all safety shields are in place before operating the PTO
generator.

5. Make sure no binding exists in generator or gear box. If

binding is found, locate the cause and correct it before pro-
ceeding.

6. Make sure that the electrical loads to be driven by the gen-

erator will not draw more current than the ratings of the
generator receptacle or cord set which will supply the cur-
rent.

Summary of Contents for 64864011

Page 1: ...60706 133 12PTOC 3 25PTOC 3 Tractor Drive PTO Generators OWNERS MANUAL INSTALLATION AND OPERATION INSTRUCTIONS SAFETY FIRST READ THIS MANUAL BEFORE OPERATING YOUR GENERATOR ...

Page 2: ...terial or workmanship under normal standby use average less than 50 hours per month and service For warranty service return the product within 36 months from the date of purchase transportation charges prepaid to your nearest factory authorized service station or the WINCO factory There is no other express warranty To the extent permitted by law any and all warranties including those of merchantab...

Page 3: ...sible explosion and or fire a Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate 3 DEADLY EXHAUST GAS Exhaust fumes from any engine contain carbon monoxide an invisible odorless and deadly gas that must be mixed with fresh air a Operate only in well ventilated areas b Never operate indoors 4 NOISE HAZARD Excessive noise is not only tiring b...

Page 4: ...isassembled in bag 5 Remove the four bolts which hold down the generator feet to the pallet 6 Lift the generator from the pallet by means of the lifting eye on the top of the generator 7 Inspect the generator carefully for freight loss or damage If loss or damage is noted at time of delivery require that the person making the delivery make note of the loss or damage on the freight bill or sign the...

Page 5: ...ce The retainer pin will protrude approximately 3 8 when fully seated See Figure 1 7 Repeat steps 4 through 6 for each brass pin Make sure to connect the neutral lead cable identified and color coded in conformance with the applicable local electrical codes to the large diameter pin N on the plug WARNING Electrical Shock DURING THE NEXT STEP THE LOAD DISCONNECT PLUG SHOULD NOT BE PLUGGED INTO ITS ...

Page 6: ...SONALINJURY IF THE GENERATOR IS TO BE USED AS A STANDBY POWER SOURCE A SPECIAL DISCONNECT SWITCH MUST BE INSTALLED TO SEPARATE THE GENERATOR AND THE COMMERCIAL POWER LINES THE DISCONNECT MUST ISOLATE THE GENERATOR FROM THE COMMERCIAL POWER LINES AND THE LOAD WHEN THE GENERATOR IS ON STANDBY AND MUST ISOLATE THE COMMERCIAL POWER LINES FROM THE LOAD AND THE GENERATOR WHEN THE GENERATOR IS SUPPLYING ...

Page 7: ...motor not its starting current which is a lot higher Motor starting current requirements vary greatly by motor size and type Repulsion induction type motors are the easiest to start typically using 1 1 2 to 2 1 2 times as much current to start as to run capacitor type motors usually require 2 to 4 times as much current to start as to run split phase type motors are the hardest to start normally us...

Page 8: ...HUTDOWNPROCEDURE 1 Switch off electrical load 2 Reduce speed of engine driving generator to idle 3 Disengage power take off drive and allow generator to coast to a stop WARNING Personal Injury Never try to manually stop the generator Always let it coast until it stops 5 Shut off the engine 4 Disconnect drive shaft tumbling bar power take off end first then generator end Figure 6 Figure 7 3 Make su...

Page 9: ...nd generator mount ing hardware should be tight Clean and inspect the generator after storing it for long periods and after using it in extremely dusty conditions or in severe weather such as rain or blowing snow Lubrication The generator bearings are factory lubricated and sealed and require no further lubrication The generator input shaft should be cleaned and lubricated with a thin film of grea...

Page 10: ...d of the armature are the generator output slip rings For proper generator output the surface of the slip rings must have a smooth shiny highly polished finish Normal brush seating will transfer a shiny black finish that will seat the copper surface This finish should not be removed unless it becomes dull or begins to build up Under sustained use it is advisable to check and if necessary polish th...

Page 11: ...Either a high or low resistance reading will be obtained 7 Reverse the meter leads black lead to the DC NEG and red to the AC terminals each in turn An opposite reading should be observed 8 Check each terminal to the case An open circuit very high resistance reading should be observed A battery powered test light may be used Follow the same proce dures described above A good diode element will all...

Page 12: ...ine if necessary 4 Incorrect field excitation 4 Check for worn brushes and weak or broken brush springs No load output low replace as required Check input AC voltage to rectifier Check rectifier output DC voltage to positive DC brush If no DC voltage is present at the brush replace the rectifier Check for dirty slip rings Clean them if they are dirty High voltage 1 Engine speed too fast 1 Check en...

Reviews: