Lighting Inverter Maintenance Manual
Date: 05/28/2020
complete self diagnostic capabilities and LCD Monitoring
lighted environment
prior
to an emer-
gency.
The three phase power supplies are able to do a 5 minute battery run the first of every
month except for New Year’s day when the test is for 90 minute. The testing can be enabled by
going to the Autorun screen and selecting Yes or No with the Menu Forward or Menu Reverse but-
ton. When the battery test happens the rectifier is turned off, and the batteries will sustain the load
on the output. If the voltage dips too low the test is terminated prematurely, and a entry is record-
ed in the alarm log accordingly. Two minutes into the battery run test the voltage, power date, and
time are logged in the battery log. This is a feature that is standard in our 3
-
phase power supplies.
Water Dots are placed on every shelf and door panel to indicate if moisture is present or has got
inside the unit. The Dots are originally white in color but will turn red when water is absorbed.