Three Phase Emergency Lighting Inverter User’s Manual
#018-7002-00
Fault Instructions
Fault
Indicator Display
Instructions
Charger abnormity
1# indicator shine
When battery voltage
﹤
240V and CHG control signal is on, give
alarm if battery voltage doesn’t increase at 1 hour.
Overload
1#
,
2# indicators shine
1
.
Line inverter mode 105%
~
130
%
overload, turn to bypass
after 10 mins;
2
.
Line inverter mode
>
130% load, turn to bypass immediately;
3
.
Bypass mode 130% load, cut off output after 1 min , give an
alarm
4
.
Battery mode 105%
~
130
%
load, give an alarm after 10 sec-
onds and cut off output.
5
.
Battery mode more than 130% load, alarm immediately and
cut off output.
Battery SCR de-
stroyed
1#
,
3#
,
6# indicators shine
Battery voltage
>
300V
Parallel communica-
tion abnormity
1#
,
2#
,
3#
,
6# indicators
shine
Parallel UPS communication interrupted
Bus abnormity
1#
,
4# indicators shine
Sense condition
:
PFC ON
1
.
+Bus voltage higher than 450V or - Bus voltage lower than -
450V for 80 ms.
2
.
+Bus voltage higher than 400V or - Bus voltage lower than -
400 V for 1.5 ms.
3
.
+Bus voltage lower than 230V or - Bus voltage higher than -
230V for 1.5 ms.
4
.
+Bus and - Bus absolute value difference more than 40V for 2
mins.
5
.
PFC IGBT fault
Inverter Fault
1#
,
5# indicator shine
Sense condition
:
PWM ON
1
.
Inverter voltage higher than 276V or lower than 140 V for 128
ms
Inverter output short 1#
,
2#
,
5# indicator shine
Inverter output voltage
﹤
50V, output current
>
10A more than 3
periods.
Temperature too high 1#
,
6# indicator shine
Sense that PSDR PCB radiator’s temperature higher than 75
℃
Inverter relay short
1#
,
4#
,
6# indicator shine
After Bus voltage has increased , PWM sense inverter voltage
>
80 V
Communication ab-
normity
1#
,
3#
,
4# indicator shine
Bosom CPU can’t set up communication
Fan abnormity
1#
,
2#
,
6# indicator shine
Sense fan signal abnormity
Inverter bypass short 1#
,
2#
,
3#
,
4# indicator
shine
Sense the power of inverter more than minus 800W
Table 5