Front Panel Configuration
29
8.1 ACCESSING THE FRONT PANEL EDITOR (FPE)
To enter the ‘configuration mode’ press Press and hold the
button
NOTE:- To exit the front panel configuration editor and activate your changes, press and hold the
button. Ensure you have saved any changes you have made by pressing the button first.
NOTE:- When the editor is visible, it is automatically exited after 5 minutes of inactivity to ensure
security.
8.1.1 EDITING A PARAMETER
Press
(+) to select the next parameter or
(-) to select the previous parameter
When viewing the parameter to be changed, press the
button. The value begins to flash.
Press
(+) or
(-) to adjust the value to the required setting.
Press
the save the current value, the value ceases
flashing.
Press and hold the
button to exit the editor, the
configuration icon
will be removed from the display.
:
8.2 ADJUSTABLE PARAMETERS (CONFIGURATION EDITOR)
When viewing the configuration editor, Press
to select the required ‘page’ as listed below.
Front Panel Configuration Editor (Factory default settings are shown in bold italicised text)
CONFIGURATION PARAMETERS – MODULE (Page 1)
101
Contrast
000 (%)
102
Display mode
Icon only (1), English (0)
n
103
S1 Option
Generator (1), Mains (0)
104
S1 Summary screen phase display
1-3
105
S2 Option
Generator (1), Mains (0)
106
S2 Summary screen phase display
1-3
107
Lamp test at power up
On (1), Off (0)
108
Power up in auto
On (1), Off (0)
109
Enable transfer by buttons
On (1), Off (0)
110
Test mode
On Load (1), Off Load (0)
CONFIGURATION PARAMETERS – APPLICATION (Page 2)
201
Breaker Type
Scheme B (1), Scheme A(0)
202
Check Sync
On (1), Off (0)
203
Return to Programmed Transition
On (1), Off (0)
204
Display mode
Icon only (1), English (0)