DSC SYSTEM MASTER PC4000 System Manual Download Page 6

4

CAUTION:
When used to power a module, the “RLY 1 COM”
terminal of the PC4204 must be connected to the
“RED COMBUS” terminal of the module only. The
positive (RED) conductor of the COMBUS must be
left unconnected to the module that is powered by
the PC4204. The “BLK COMBUS” of the module
should be run common to the negative (“BLK”) of
the COMBUS. Use of a power source other than the
PC4204 power supply module to supply additional
power to the PC4000 system is not recommended.

The COMBUS is a four conductor cable to which all
modules and keypads are connected in parallel.
Connections to the COMBUS do not have to be home-
run. For example if a storage building had an 8 zone
expander (PC4108) and a keypad (LCD4500) located
in it, the zone expander and keypad could be spliced
together and run back on a single 4 wire cable to the
nearest point on the COMBUS.

Mounting the Panel

Select a dry location close to an unswitched AC source,
a ground connection and a telephone connection for
mounting the Main Control Cabinet.

Remove the PC4000 printed circuit board, mounting
hardware, and keypad from the cardboard retainer
inside the large cabinet. Before attaching the cabinet to
the wall, press the five white nylon printed circuit board
mounting studs into the cabinet from the back.

Pull all cables into the cabinet and prepare them for
connection before mounting the circuit board to the
back of the cabinet. Press the circuit board down onto
the mounting studs.

There is room in the Main Control Cabinet (PC4001C)
for any two modules (PC4108, PC4116, PC4216 or
PC4400). Modules requiring power (AC and battery
PC4204) must be installed in the large Expander
Cabinet (PC4002C). This enclosure will accommodate
one module (PC4108, PC4116, PC4216 or PC4400) and
a powered output (PC4204) or any three modules. A
small Expander Cabinet (PC4003C) is available for a
single module that does not require external power.

Once the wiring is completed power the system up by
first connecting the battery followed by the AC
transformer. All LCD4500 keypads should display the
message ‘PC4000 DSC Ltd.’. Press a key on any
keypad that is to be assigned to Partition 1. The keypad
will beep and display the message ‘4500 Mod. #1' and
the keypad is automatically assigned to Partition 1.

Enroll every module to the system. Make sure you put
down the number of each module enrolled. Refer to the
Programming Manual for the required procedure.

When enrolling any PC4108 or PC4116 zone expander
module make sure to note the zones which you
assigned to the module.

This information is very important if it becomes
necessary to Add or Delete zones to or from a
Partition. Zones 1 through 16 are assigned to Partition
1 by default. This can be changed later in Installer
Programming.

In Book 2 (Programming Work Sheets) you will find a
four page System Overview section. Fill in the
information as each module is enrolled. These sheets
are designed to be left in the panel so if future service
is required, the location and assigned number of each
module will be readily available.

Once all modules are enrolled perform a diagnostics
check on the panel to determine if any problems are
present (See - DIAGNOSTICS).

Programming the System

The PC4000 has the capability to operate as 8 separate
alarm systems called Partitions. Dividing the panel into
Partitions will allow you to control access to specific
areas.

When the PC4000 is first powered up all zones on the
main board and User Codes are assigned to Partition 1.
If no other Partitions are required the entire system will
be considered Partition 1. This is important to keep in
mind as often in programming the panel will require you
to enter the Partition to program.

For example, when programming entry and exit times,
you must select the menu option ‘ADD/EDIT PAR’. The
keypad will then prompt you for the Partition to add or
edit. You must select Partition 1 for a system that has no
additional Partitions.

The factory default setting for all options is provided
in the Programming Work Sheets as well as page
reference numbers, chart reference numbers and the
programming ‘HOTKEYS’ for the option to allow quick
programming.

Complete the Programming Work Sheets located in
Book 2. Having this information prepared before
programming the panel will speed up the process
considerably.

All information for the 16 zones on the main panel may
be entered in the Programming Work Sheets.
Any zone expanders on the system will include a similar
sheet and the information should be completed for these
as well.

There is no set order in which the panel must be
programmed, however, if you use the following guideline
it may simplify the programming of the panel for the first
time.

Summary of Contents for SYSTEM MASTER PC4000

Page 1: ...SYSTEM MANUAL PC4OOO Book 4 Jan 11 1993 Software Version 1 3 ...

Page 2: ...anges or modifications not expressly approved by Digital Security Controls Ltd could void your authority to use this equipment This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generat...

Page 3: ...04 relay output module is available for installations requiring additional power beyond the 500 mA supplied by the PC4000 main panel This module comprises a 12 volt DC power supply of 1 5 Amp capacity and four 12 volt relays with form C contacts which will provide switched outputs under any of the 23 options available in the list of programmable outputs The PC4204 connects to the COMBUS via four w...

Page 4: ...indicators 8 4216 modules with 16 outputseach Switched Auxiliary Output Programmable for 1 of 23 options Supervised Alarm Output Bell Output 700 mA fused at 5 Amps 12 VDC unregulated Steady or Pulsed Output Programmable for 1 of 23 options Event Buffer 512events Date and time stamp 8 True Partitions Separate or shared zones from other partitions Individual keypads per partition minimum 1 keypad In...

Page 5: ... to an on site printer that will record the identity of the system description of the occurrence alarm trouble etc arm disarm by user date and time The PC4216 module provides up to 16 programmable outputs each of which may be programmed to trigger on up to 21 different options It is also used to display zones on a graphic annunciator When used in this manner all 16 outputs must be used to display ...

Page 6: ...ition 1 Enroll every module to the system Make sure you put down the number of each module enrolled Refer to the ProgrammingManualfortherequiredprocedure When enrolling any PC4108 or PC4116 zone expander module make sure to note the zones which you assigned to the module This information is very important if it becomes necessary to Add or Delete zones to or from a Partition Zones 1 through 16 are ...

Page 7: ...elephone cord into the RJ31 X jack If a DTS 1 is being used to monitor communicator transmissions connect it to the telephone line and place the DTS 1 in the line mode by pressing the red LINE LOCAL button Arm the panel wait for the exit delay to expire and trip a detector on an instant circuit Wait for the communication to complete Disarm the panel and check with the monitoring station to confirm...

Page 8: ......

Page 9: ... frequency Switched Auxiliary Supply Output Programmable for several options Battery 12 volt 4 Ah minimum rechargeable gel cell or sealed lead acidbattery Transformer 16 5 VAC 40VA Output Voltage Typically with normal AC on and a fully charged battery the output voltage will be 13 8 VDC With AC off and the battery discharging the voltage will go below 10 volts and then battery cutoff will occur pr...

Page 10: ......

Page 11: ...d 1 5 Amp output PC4216 Low Current Output Module 16 output low current module Up to 9 modules on system 1 module programmable for all 16 outputs 1 of 23 options for each 8 modules programmable as alarm annunciators or zone followers Four wire QUAD hook up to COMBUS Nominal current draw of 35 mA Provides Tamper and Trouble Reporting Codes Low COMBUS supervision to PC4000 Main Board PC4400 RS 232 I...

Page 12: ......

Page 13: ...11 ...

Page 14: ...12 ...

Page 15: ... is a 3A maximum switch to ground A small relay a buzzer or other DC operated device may be connected between the 12 VDC AUX positive terminal and the PGM switched negative terminal to interface with controlled devices COMBUS Terminals RED BLK YEL and GRN Connect the red wire of the COMBUS to the RED terminal the black wire to the BLK terminal the yellow wire to the YEL terminal and the green wire...

Page 16: ......

Page 17: ...Codes are used for arming and disarming the control panel for viewing the armed disarmed status of the partitions for programming additional security codes and for entering user functions In the disarmed state entering a Master Code will cause a nine selection menu to be displayed as follows 0 Arm Partition 1 Arm Diff Part 2 Disarm Diff Part 3 View Partitions 4 Set System Time 5 Set System Date 6 ...

Page 18: ...ad buzzer will stop The correct security code must be entered before the allowed entry time expires To change the entry time see Installers Programming Command 8 If an alarm occurred while the panel was armed the View Memory message will be on the display with the zone name for the zone that caused the alarm The display will keep those messages on for two minutes or until the key is pressed to ret...

Page 19: ...tored Initiating a bell comm test will check the battery voltage AC Trouble There is no audible annunciation on AC power failure The system Trouble light will come ON but the audible indication will not sound until there is a low battery condition Transmission delay can be programmed for 000 to 255 minutes Aux Supply Troub An Aux trouble is generated if the aux fuse on the main panel opens or if t...

Page 20: ...o program additional access codes of any type The PC4000 has 128 access codes In the Installer s Programming Section these codes are divided up and assigned to partitions or are turned into System Master Codes which have control over all partitions This must be done before the user can program the access code and the code type The first code is the System Grand Master Code Only the Installer can c...

Page 21: ...de When selected the keypad will display Enter Digits and what is currently programmed for that access code Enter in the 4 digit code Do not press or while entering the access code If you do not wish to change the code use the keys to exit When you have finished entering the code if you are programming System Master codes the keypad will return to selecting which System Master code to program If y...

Page 22: ...Auto Arm Upon selecting the Auto Arm Control function the Auto Arm Control menu will appear on the LCD keypad 0 Auto Arm 1 Auto Arm Time Auto Arm toggles Y or N to enable or disable the Auto Arm function Auto Arm Time is the time the partition will automatically arm itself every day NOTE The Auto Arm time is a 24 hour clock and times must be entered as two digit numbers E g HH 01 02 10 11 23 24 MM...

Page 23: ...long the outputs are activated and see Util Req Code for programming whether a utility output requires an access code to be activated Installers Programming Commands 8 Installer sCode The PC4000 is completely programmed from the keypad by using commands in the 8 section The commands are described in detail in the Programming Manual At home Arming 9 AccessCode Entering 9 before the arming code arms...

Page 24: ......

Page 25: ...r end into the DB 25 modular jack adapter Connect the DB 25 modular jack into the RS232 serial port of the printer See the PC4400 wiring diagram Power up the printer then the PC4000 and PC4400 If the PC4400 is already enrolled and the printer is on line the PC4400 will begin transmitting to the printer The following is a sample of a printout from the serial printer Partition Label Date Time Event ...

Page 26: ...emory until they are ready to be printed When the printer is brought back on line the PC4400 will send the new events to the printer If 384 new events occur before the printer is brought back on line 384 events 75 of the buffer the PC4000 will send the Buf Near Full reporting code to the monitoring station See Maint Rep Codes in the Programming Flow Charts for programming the Buf Near Full reporti...

Page 27: ...nected to the tip and ring terminals on the panel A DTS 1 must be connected to the lines and in the local mode Program the downloading access code and panel I D code Program a zone for Forced Answer See Zone Type in the Programming Guide This zone is only meant to be temporary to initiate downloading It can later be changed back to the required zone type Make sure the access code and panel I D cod...

Page 28: ...is and shall be in lieu of any and all other warranties whether expressed or implied and of all other obligations or liabilities on the part of Digital Security Controls Ltd This warranty contains the entire warranty Digital Security Controls Ltd neither assumes nor authorizes any other person purporting to act on its behalf to modify or to change this warranty nor to assume for it any other warra...

Page 29: ... 1993 Digital Security Controls Ltd Toronto Canada Tel 800 387 3630 FAX 905 760 3034 ...

Page 30: ...29000223R0 ...

Page 31: ...amming Work Sheets Used by the installer to record installer s programming and system layout Book 3 PC4000 Programming Manual Explains each section of installer s programming Book 4 PC4000 System Manual Introduces the PC4000 explains the hookup and wiring and user s programming and functions 1 PC4000 Main Control Board 1 LCD4500 Remote Keypad 1 Main Control Cabinet 1 Hardware Package EOL Resistors...

Page 32: ...icated with the monitoringstation 10 European Pulse Dialing Page 24 An option to use American pulse dialing or European pulse dialing 11 Second Master Reporting Codes Page 27 The Second Grand Master Access Code now has its own opening and closing reporting codes when it is used to arm and disarm 12 PC4216 Zone Follower Option Page 30 The PC4216 can follow any group of 16 zones When a zone is open ...

Reviews: