The recommended output options for the PC4612(A) are (21), (22),
(48), (55), (56), (57). Their descriptions are listed below.
4.3 Recommended Output Options
Zone Alarm (21)
For zones that are programmed as burglary, the zone alarm output will
activate the LED when the selected burglary zone has gone into
alarm.The LED will remain on until the partition is armed again.
Zone Follow (22)
For zones that are programmed as Fire or Fire Supervisory, the zone
follow output will turn on the LED when the fire zone is in alarm, or
when the fire supervisory zone is off-normal (zone shorted). The LED
will only turn off when the zone has been restored and a fire reset has
been performed.
Outputs 1-10 have red LEDs and are intended for fire/burglary alarm
zone annunciation. Outputs 11-12 have yellow LEDs and are intended
for fire supervisory zone annunciation.
NOTE:
Use Options 21 or 22 for output numbers 01-10 and option 22
only for output numbers 11-12.
Fire Zone Tbl. (48)
The output will activate when a fire zone is bypassed, or when a fire
zone trouble condition is detected. The output will deactivate when the
zone is unbypassed or the trouble is restored.
Use this option for
PC4612(A) output number 13.
Common Fire Tbl. (55)
The output activates when any of the following troubles are detected
by the panel. The output deactivates when the trouble is cleared:
• Any system AC or battery trouble (PC4020, PC4820, PC4204,
PC4701)
• Any system communicator trouble (TLM1, TLM2, FTC, LINKS)
• Ground Fault trouble
NOTE:
Use this option for PC4612(A) output number 15.
Bell Trouble (56)
The output activates for a trouble (open or short) on any supervised
system bell output (PC4010/4020 or PC4702). The output deactivates
when the trouble is cleared.
Use this option
for PC4612(A) output
number 14.
AC Status (57)
The output will be ON when AC power is present on the PC4010/
4020, as well as all enrolled modules (PC4204, PC4820, PC4702). If
the PC4010/4020 or any module loses AC power, the AC Fail Delay
timer will start (see your PC4010/4020 Installation Manual for more
information). When the timer expires (or if it is programmed to be 0),
if the AC is still missing, the output will turn OFF. An AC Fail trouble
condition will be generated. When AC power is restored, the output
will again wait for the AC Fail Delay timer to expire. If the AC power
is still on at the end of the delay, the output will turn ON.
Use this
op-
tion for PC4612(A) output number 16.
4.4 Finishing
Make sure you label each of the 12 zone lights in the space provided
on the annunciator. When you have finished installing and program-
ming the PC4612(A), instruct the end-user of the system how to inter-
pret events using the annunciator.
PC4612(A) Programming
PC4612(A) Module No.:
l__________l__________l
[000703XX]
PC4216 Options
XX = module# [Enter 01 - 09]
Custom Group No:
l__________l__________|
[000704XXYY]
PC4216 Custom
XX = custom group # [Enter 01 - 09]; YY = output # [Enter 01 - 16]
Output#
PC4612 LED
Recommended
Option
Output
Option
Zone
1
1
21 or 22
l__________l__________l
l________l________ l________l_
Select zone 001-128 (PC4020), 001-064 (PC4010)
2
2
21 or 22
l__________l__________l
l________l________ l________l_
Select zone 001-128 (PC4020), 001-064 (PC4010)
3
3
21 or 22
l__________l__________l
l________l________ l________l_
Select zone 001-128 (PC4020), 001-064 (PC4010)
4
4
21 or 22
l__________l__________l
l________l________ l________l_
Select zone 001-128 (PC4020), 001-064 (PC4010)
5
5
21 or 22
l__________l__________l
l________l________ l________l_
Select zone 001-128 (PC4020), 001-064 (PC4010)
6
6
21 or 22
l__________l__________l
l________l________ l________l_
Select zone 001-128 (PC4020), 001-064 (PC4010)
7
7
21 or 22
l__________l__________l
l________l________ l________l_
Select zone 001-128 (PC4020), 001-064 (PC4010)
8
8
21 or 22
l__________l__________l
l________l________ l________l_
Select zone 001-128 (PC4020), 001-064 (PC4010)
9
9
21 or 22
l__________l__________l
l________l________ l________l_
Select zone 001-128 (PC4020), 001-064 (PC4010)
10
10
21 or 22
l__________l__________l
l________l________ l________l_
Select zone 001-128 (PC4020), 001-064 (PC4010)
11
11
22
l__________l__________l
l________l________ l________l_
Select zone 001-128 (PC4020), 001-064 (PC4010)
12
12
22
l__________l__________l
l________l________ l________l_
Select zone 001-128 (PC4020), 001-064 (PC4010)
13
Zone Trouble
48
l__________l__________l
14
Bell Trouble
56
l__________l__________l
15
System Trouble
55
l__________l__________l
16
AC On
57
l__________l__________l
©2002 Digital Security Controls Ltd.
Toronto, Canada •
www.dsc.com
Tech Support: 1-800-387-3630 (Canada & US) or 905-760-3036
Printed in Canada 29002625 Rev 003
Direct all comments concerning this publication to
For Zone
Alarms
(Red)
For Fire Supervisory
(Yellow)
Yellow
Green