29
6.1 Wiring Diagrams
l
Fire Alarms must be sent over both communication channels. Fire output from Fire Alarm Control Unit
must be connected to input 1 on the LE4020/LE4020CF.
l
24 hour Test Transmission must be enabled on the dialler and on the LE4020/LE4020CF.
Figure 1-7 DSC Subscribers’ Unit Fire and Cellular Transmitter Mounted in the Same Room
DSC
Subscribers’
Unit Fire
Zone
Inputs
TIP
TIP RING
PGM1
DSC Keypad
LCD4501
PK55XX
LTE/3G
Cellular
Transmitter
LE4020/LE4020CF
T1/R1
TIP/RING
Zone
Input PGM4
AUX Power
10-28V/700mA
RM1C ULC
Relay
PC5003C
PC4050CR
cabinet
LTE/3G (HSPA)
PSTN
AC Input
AC Input
PC4020
PC1864
PC1832
PC1616
RM1C ULC
Relay
LE4020/LE4020CF cabinet
Outputs
Fire
Supervisory
Trouble
Fire Alarm Control Unit
Note:
For PowerSeries
NEO panel refer to
Installation Guide
29005157.
For PowerSeries Pro
panel refer to Installation
Guide 29010346.
Notes:
l
Power for LE4020 must be provided from Fire Alarm Control Unit or separately listed power supply
rated for the application (10-28V/700mA).
l
All wiring connections must be run in a metallic conduit.
l
Phone Line Monitoring (TLM) must be enabled.
l
Phone Line trouble is indicated by the Blue LED on the LE4020/LE4020CF.
l
Connect PGM4 output from the LE4020/LE4020CF (Trouble Conditions) to a zone input on the Sub-
scriber Unit for supervision of the GSM Transmitter.
l
24hour Test Transmission over phone line (PSTN) and LE4020/LE4020CF must be enabled.
l
Fire Alarm must be sent over both communication channels.
l
On the Subscribers’ Unit, program PGM1 for PC1616/PC1832/PC1864 as System Event (Section [009]
as type 10; Section [501] Fire Event option 2 ON). An alternate option is to program PGM1 as Zone
Follower (Section [009] = 29) and assign Fire Zone to PGM1 in Section [551]. Ensure Bit 3 is on in
[501]. In this case, a restored fire alarm condition does not require the DSC control panel to be reset.
For PC4020, program PGM1 as type 49 Steady Fire ([00070049]).
l
Dry contact outputs from ULC Listed Fire Alarm Control Unit must be connected to zone inputs on the
ULC Listed DSC subscribers' Unit Fire.
l
Refer to detailed diagrams.