DISABLE
After the pa
ssword has been in
ser
ted the menu
DISABLE will be shown.
The
Di sa ble
op tion can di sa ble or Ena ble the loop de -
vi ces (in put or out put de vi ces), the Out puts and the SW
zo nes of the Fire Con trol pa nel.
+
When a de vi ce at le ast is di sa bled, the Di sa ble
LED will be glo wing, and any Alarm or Fa ult, re la -
ted to the di sa ble de vi ce, will be ignored.
The di sa ble and ena ble mo des are as fol lows:
Input De vi ces
A di sa bled in put de vi ce (De tec tor,
Input mo du le, Con ven tio nal Zone mo du le,
Addres sa ble
Call-po ints) will not ge ne ra te ALARM or FAULT sta tus.
Ø
To cle ar ALARM sta tus ge ne ra ted by a in put de vi ce -
RESET
the fire con trol pa nel.
Out put De vi ces
ALARM or FAULT sta tus will not ac ti -
va te di sa bled out put de vi ces (Out put mo du les, Addres -
sa ble Si rens).
Ø
To stop the out put de vi ces ac ti va ted by FAULT sta -
tus -
Di sa ble
the de vi ces con cer ned.
Ø
To stop the out put de vi ces ac ti va ted by an ALARM
sta tus -
RESET
the fire con trol pa nel.
+
Out put de vi ces ena bled du ring ALARM or FAULT
sta tus (pro gram med), will be ac ti va ted im me dia -
tely.
The Di splay in Fi gu re 48 show how to se lect the de vi -
ces to Di sa ble/Ena ble.
In this pha se
:
Alpha nu me ric key pad
Use the Alpha nu me ric key pad
to se lect the Di sa ble/Ena ble op tions.
Use the
1
key
to se lect the
Di sab. List
(see Fi gu re 48).
Use the
2
key
to se lect the
Di sa bled
op tion of Loop de -
vi ces.
Use the
3
key
to se lect the
Di sa bled
op tion of SW zo -
nes.
Use the
4
key
to se lect the
Di sa bled
op tion of Out puts.
Cur so r Keys
No fun ction is re la ted to
UP
Key;
No fun ction is re la ted to
Down
Key;
No fun ction is re la ted to
Right
Key;
No fun ction is re la ted to
Left
Key.
ESC Key
Use
ESC
key to can cel the ope ra tion and to
step back to pre vio us page.
ENTER key
No fun ction is re la ted to
ENTER
key.
Fun ctio n Keys
No fun ction is re la ted to
F1
key;
No fun ction is re la ted to
F2
key;
No fun ction is re la ted to
F3
key;
No fun ction is re la ted to
F4
Key.
DISABLE
47
Master control panel l2-stat: DISABLE
1=Dis. list 2=device 3=SW zone
7=Conv.Zone
Control Panel name
Access Level
Options
4=Output 5=Network 6=telecom
This symbol shows the presence
of the connection between the
User Interface and the Main Board
Control panel
Status
Fi gu re 48
Di splay DISABLE menu
firealarmresources.com
Summary of Contents for AFD2000