IMPORTANT
The equipment is fixed, wall-mounted and shall be installed in the position specified in these instructions (see Figure 1: Parts).
The equipment enclosure must be fully assembled and closed, with all the necessary screws/tabs and secured to a wall before
operation. Internal wiring must be routed in a manner that prevents:
- Excessive strain on wire and on terminal connections
- Loosening of terminal; connections
- Damage of conductor insulation
WARNING: Never install this equipment during a lightning storm!
Instruct the end-user to:
- Not attempt to service this product. Opening or removing covers may expose the user to dangerous voltages or other risks.
Any servicing shall be referred to trained service persons only.
- Use authorized accessories only with this equipment.
Do not dispose of the battery in fire or water. Disposing of the battery in a fire will cause rupture and explosion.
Do not dispose of the waste battery as unsorted municipal waste. Consult your local regulations and /or laws regarding recyc-
ling with regard to this lead-acid battery. Doing so will help protect the environment. Some of the materials that are found within
the battery could become toxic if not disposed of properly and may affect the environment.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Stand-
ard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited
to the specific values or not used at all as indicated below.
Program Feature or Option
Permitted in UL 864 (Y/N)?
Possible Settings
Settings permitted in UL 864
Supervision
Yes
5 minutes /60 minutes
5 minutes (see note below)
Inputs/Outputs
Yes
Fire/Burg signals
Fire related signals only
SMS Remote Control
No
Enable/Disable
Disable
NOTE: This product has been tested in accordance with UL 864 9th edition. According to this edition of the standard, the super-
vision window for reporting single-technology communicator trouble shall be set to five minutes. However, the product can be
installed in accordance with the requirements of NFPA72 2013 edition, which allows for a 60-minute supervision window.
Introduction
The 3G4010CF is a wireless communicator for UL commercial fire and/or burglary applications. The 3G4010CF send alarm
system information over a 3G (HSPA) or 2G (GPRS) network from the alarm control panel at the protected premises to a super-
vising station. The device is compatible with UL listed alarm receiver Models SG-System 5, SG- System IV, SG-SYSTEM III
(using SG-DRL3- IP line card), SG-SYSTEM II and SG-SYSTEM I-IP. This product is UL listed under requirements of UL864
9th Edition and UL1610 Standards as a Fire Alarm Communicator for central station service fire alarm – commercial and it can
be installed in certified installations in accordance with the requirements of UL827 Standard and NFPA72 2002 (Section 8.5.4
Other Transmission Technologies), NFPA72 2007 (Section 8.6.4 Other Transmission Technologies) or NFPA72 2010 Code
(Section 26.6.3.1)
Features
l
Complete solution CF kit includes tamper protection output, listed power supply and battery standby capability for 24 hours.
l
Dual-band UMTS/HSPA; Quad-Band GSM/EDGE Radio
l
Advanced Carrier Selection
l
Bi-color wireless signal indicator
l
3G (HSPA) / 2G (GPRS) / Internet communication with Sur-Gard SG-System I-IP / II / III / IV / 5
l
Compatible with listed alarm control panels that have an integrated DACT and support a 4-digit or 10-digit Contact ID com-
munication format as described in SIA DC-05 or SIA communication format as described in DC-03 standard for 300 baud.
Examples of suitable compatible alarm panels: DSC Models PC1864, PC1832, PC1616, PC4020.
l
Panel Transmission Monitoring for up to four phone numbers
l
Simulates landline
l
Switches automatically to the 3G (HSPA) or 2G (GPRS) network in the event of landline trouble (e.g., line down)
l
Four Programmable (NO/NC/SEOL) Inputs
l
Contains one 12V - 7 Ah battery
l
Case Tamper Output
l
Landline overvoltage protection
l
Four Programmable Open Collector Outputs
l
DLS support for status, firmware updates and remote debug enable
l
Remote Firmware Upgrade
3