DryAIR 2000-0250 Operator'S Manual Download Page 23

Troubleshooting

6-1

Troubleshooting

There are 2 red light(s) on the control panel, propane system (1 solid, 1 flashing); natural gas system (1 solid), which will indicate a
condition that has caused the unit to shut down.

There are 6 green lights on the control panel, which indicate the status of a sequence of functions while the unit is running.

When the burners are lit, all green lights should be on as well.  Any green light which is not on should be considered burned out.

Temperature controller, pilot valve and main valve and lights go off and on as the water heater cycles.

The terminal strip, located inside heating module behind the RAYPAK water heater panel, must be accessed to initiate troubleshoot-
ing procedures.

No power at terminal P2 on low water cut-off

Check for 120 volt power at letter P2 on low water cut-off.  If there is no power, check the following:

a)

Low water situation. Check fluid level in tank and add if necessary.

b)

Defective low water cut-off.  Replace low water cut-off.

No power at terminal #2 on low gas pressure (propane system only)

Check for 24 volt power at letter NC on low gas pressure switch.  If there is no power, check the following:

a)

Low gas pressure situation.  Check volume level in supply tanks and refill if necessary.

b)

Defective low gas pressure switch.  Replace low gas pressure switch.

No power at flow switch

Check for 24 volt power between letter C and #3 on the terminal strip.  If  there is no power, check the following:
a)

Pump not running.
- Check power and toggle switch on control panel.
- Check for 110 volts at pump motor. If correct power is confirmed at motor, but pump won't run, replace pump.

b)

Inadequate flow.
- Check that all valves are open in the fluid-transfer loop.
- Filter screen may be plugged. Use flush hose/valve attachment into a bucket, while pump is running, for a quick flush. Eventually the
system may have to be drained and the filter screen removed and cleaned by hand.

c)

Defective flow switch. - If a) and b) check out, the flow switch will need to be re-calibrated or replaced.

No power at out-going side of high limit switch

Check for 24 volt power between letter C and #4 on the terminal strip.  If there is no power, check the following:

a)

Check switch settings.  The automatic high limit should be set 10ºF higher than the set point of the temperature control.

b)

Defective high limit switch.  Replace high limit switch.

No power at out-going side of flame roll-out switch

Check for 24 volt power between letter C and #5 on the terminal strip.  If there is no power, check the following:
a)

Check manual reset button on the switch and reset; if tripped restart system and watch for a flame roll-out.

b)

Check for blockage in the heat exchanger in the form of foreign debris or soot build up.  (See the operators manual for proper cleaning
procedure)

c)

Check entire vent system for possible blockage or restriction and correct problems.

No power at temperature control

Check for 24 volt power between letter C and #7 on terminal strip.  If there is no power, check the following:
a)

Check that setting on temperature control is at desired operating temperature and the supply temperature is lower than the set point.

b)

Check well sensor (electronic), and verify that it is intact and positioned properly in its well.

c)

If a) and b) check out, replace both temperature control and well sensor.

No power at pilot valve

Check for 24 volt power between letter C and #8 on terminal strip..

a)

If no 24 volts replace Ignition Module.

No power at main burner

a)

Defective Ignition Module
- Check for power between letter C and #9 on terminal strip.  If no 24 volts replace Ignition Module.

b)

Pilot failure
- If pilot has not lit but spark is present, check manual valve in the gas line and make sure its open.  Verify that gas is present as far as
the pilot burner.  This may involve purging air from the line and checking for plugged pilot orifice.
- If no spark was present at pilot electrodes, check pilot burner for good ground.  Check condition of high voltage ignition wire and clean
pilot ignition electrodes.  Replacement of pilot burner assembly and ignition wire may be necessary.

Summary of Contents for 2000-0250

Page 1: ...70 Oct 16 03 DRYAIR INC 606 Highway Drive St Brieux SK Canada SOK 3V0 Tel 306 275 4848 1 888 750 1700 Fax 306 275 4664 dryair dryair ca DRYAIR INC 1095 N Main Street Bowling Green Ohio USA 43402 Tel 4...

Page 2: ...ed Heat Transfer 3 1 Passive Heat Transfer 3 2 Accessories 3 2 How the DRYAIR System Works 3 3 Setup 4 1 Positioning and Handling of Water Heater Module 4 1 Required Safety Clearances 4 1 Elevation Co...

Page 3: ...es inconvenience and or replacement equipment rental cost Maintenance repair or service items not related to warrantable defects Loss or damage during shipping Failure resulting from lack of or improp...

Page 4: ...1700 Each warranty claim should only refer to one Serial or Production Schedule numbered unit Warranty parts are to be tagged with warranty claim number When claiming for warranty labour the allowabl...

Page 5: ...working with heat transfer fluid DOWFROST HTF BOSS CHILL PG Fluid handling precautions Ventilation Good general ventilation should be sufficient for most conditions Respiratory protection No respirat...

Page 6: ...adverse effects on the mother should have no effect on the fetus REPRODUCTIVE EFFECTS In animal studies has been shown not to interfere with reproduction 4 FIRST AID EYE Flush eyes with plenty of wate...

Page 7: ...vailable oxygen is limited as in a fire or heated to very high temperatures by hot wire or plate carbon monoxide and other hazardous compounds such as aldehydes might be generated HAZARDOUS POLYMERIZA...

Page 8: ...and may differ from one location to another it is the buyer s responsibility to ensure that its activities comply with federal state or provincial and local laws The following specified information is...

Page 9: ...HYSICIAN No specific antidote Treatment of exposure should be directed at the control of symptoms and the condition of the patient 5 FIRE FIGHTING MEASURES FLAMMABLE PROPERTIES Refer to section 9 PHYS...

Page 10: ...PERSONAL PROTECTION RESPIRATORY PROTECTION Atmospheric levels should be maintained below the exposure guideline PROTECTION When respiratory protection is required for certain operations use an approv...

Page 11: ...OR UNUSED UNCONTAMINATED PRODUCT the preferred options include sending to a licensed permitted recycler reclaimer incinerator or other thermal destructive device As a service to its customers Dow can...

Page 12: ...als are not trained in the use of this hazard rating system You should be familiar with the hazard communication programs applicable to your workplace RECOMMENDED USES AND RESTRICTIONS Intended as a h...

Page 13: ...he ideal way to heat and or dry enclosed structures Their compact and mobile design allows them to be positioned where required on the job site The efficient fan coil design provides a high rate of he...

Page 14: ...store or deploy other distribution lines used in DRYAIR portable heating applications The reel can also be secured onto its own transport trailer The trailer s no clog opening directly under the hose...

Page 15: ...ansfer fluid flows through the transfer coil where heat is transferred to the air being drawn through the coil by the fan The coil is specially designed for optimum heat transfer without adding any mo...

Page 16: ...stem Consider cabinet positioning in relation to portable heat exchanger positioning Required Safety Clearances The water heater module is a heating appliance therefore safe heat and exhaust clearance...

Page 17: ...ize will result in inadequate and inconsistent fuel delivery DRYAIR will not be responsible for faulty system operation if the recommended tank size is not used Connect the propane supply line to the...

Page 18: ...pure Dowfrost HTF or Boss Chill PG heat transfer fluid used in the DRYAIR system is made up of a blend of 95 97 Propylene glycol 5 Dipotassium phosphate and deionized water see Safety Concerns section...

Page 19: ...low Electrical Check Power up Make sure the gas supply is closed off and control panel toggle switchws are in the OFF position Supply power to the system Fluid Circulation System Start up The DRYAIR w...

Page 20: ...o 3 4 full at all times during this process Note that there may be a certain amount of air in the system HTF levels may change as air is displaced from the system Add HTF fluid to maintain 1 4 to 3 4...

Page 21: ...e switch 7 2 to the ON position All the indicator lights should be on except the operator light which will come on when the burner is on The spark igniter will immediately begin its attempt to light t...

Page 22: ...ug in another portable heat exchanger fan Repeat the first 3 steps with another portable heat exchanger until the return temperature gauge 8 1 does not rise to above 130 F At this point the water heat...

Page 23: ...If a and b check out the flow switch will need to be re calibrated or replaced No power at out going side of high limit switch Check for 24 volt power between letter C and 4 on the terminal strip If t...

Page 24: ...ter heater cabinet Ventilate the water heater cabinet Find and correct the leak before turning on any power or trying to re light the water heater Soap test the union for leaks Check heat transfer flu...

Page 25: ...awer If any parts of the burners or their retainers are damaged or worn replace them For water heaters out of service for more than 60 days disassemble and clean the pilot with a soft brush Make sure...

Page 26: ...should be cleaned using warm water and a soft bristled brush Reassemble and ensure that all fittings are tight The extracted heat transfer fluid can be reused Air will have to purged from the system...

Reviews: