Table 6-2: 14 SEER Cooling only W/Without Electric Heat
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per Standard UL 1995.
3. Fuse or HACR circuit breaker size in stalled at factory or field installed.
Table 6-1: 14 SEER Heat Pump W/Without Electric Heat
OD Fan
Motors
(each)
Supply
Blower
Motor
RLA LRA MCC FLA FLA Model kW Stages Amps
None - - None
EHK-10D 7.5/10
1
20.9/24.1 42.7/46.7 45/50
EHK-15D 11.3/15
2
31.4/36.1 55.8/61.7
60/70
None - - None
EHK-10D 7.5/10
1
20.9/24.1 48.6/52.6 50/60
EHK-15D 11.3/15
2
31.4/36.1 61.7/67.6
70/70
EHK-20D 15/20
2 41.7/48.2 74.6/82.7 80/90
None - - None
EHK-10D 7.5/10
1
20.9/24.1 51.8/55.8 60/60
EHK-15D 11.3/15
2
31.4/36.1 65/70.8
70/80
EHK-20D 15/20
2 41.7/48.2 77.8/86
80/90
1.74A 3.54A
3.92A
1.74A
110.0A
16A
208/230-3-60
Volt
Size
(Tons)
2.45A
1.08A
24.9A
048
(4.0)
208/230-3-60 13.7A 83.1A
060
(5.0)
21.4A
73A
10.4A
208/230-3-60
036
(3.0)
MCA
1
(Amps)
Electric Heat Option
Max Fuse
2
/
Breaker
3
Size
(Amps)
16.3A
Compressors (each)
OD Fan
Motors
(each)
Supply
Blower
Motor
RLA LRA MCC FLA FLA Model kW Stages Amps
None - - None
EHK-10D 7.5/10
1
20.9/24.1 29.2/33.2 30/35
EHK-15D 11.3/15
2
31.4/36.1 42.4/48.2
45/50
None - - None
EHK-10D 7.5/10
1
20.9/24.1 30.6/34.6 35/35
EHK-15D 11.3/15
2
31.4/36.1 43.7/49.6
45/50
EHK-20D 15/20
2 41.7/48.2 56.6/64.7 60/70
None - - None
EHK-10D 7.5/10
1
20.9/24.1 31.1/35.1 40/40
EHK-15D 11.3/15
2
31.4/36.1 44.2/50.1
45/60
EHK-20D 15/20
2 41.7/48.2 57.1/65.2 60/70
EHK-25D 18.8/25
2
52.2/60.2 70.2/80.2
80/90
24.9A 1.74A 3.92A
060
(5.0)
208/230-3-60 16A 110.0A
16.3A 1.08A 2.45A
048
(4.0)
208/230-3-60 13.7A 83.1A 21.4A 1.74A 3.54A
036
(3.0)
208/230-3-60 10.4A 73A
Max Fuse
2
/
Breaker
3
Size
(Amps)
Size
(Tons)
Volt
Compressors (each)
Electric Heat Option
MCA
1
(Amps)
16.6
25
22.5 35
25.7 40
16.6
25
22.5 35
25.7 40