background image

 

 

 

7. OPERATING INSTRUCTIONS 

 
7.1 MEASURES TO BE TAKEN PRIOR TO START-UP

 

 

The unit may be put into operation by specialized personnel. 

 

Using the pump submerged in fluids or in a particularly aggressive or explosive/flammable environment is prohibited 
unless it has been prepared ahead of time by the supplier for this purpose. 

 

Use gloves and eye protection as required by the lubricant safety data sheet. 

 

DO NOT use lubricants that are aggressive to NBR gaskets. If you are unsure, contact the Dropsa S.p.A technical office 
for a detailed list of recommended lubricants. 

 

Never ignore health hazards and always follow sanitary regulations. 

 

Always use suitable piping for the operating pressure. 

 

Check the integrity of the pump; 

 

Check  the  lubricant  level  in  the  reservoir  (min/max  indication  on  the  reservoir),  in  case  of  low  level,  proceed  as 
described in Section 

7.3 Filling the reservoir

 

Ensure that the pump operates at operating temperature and that the pipelines are free of any air bubbles; 

 

Check the correct connection of electrical devices.

 

To determine the maximum operating pressure, it is necessary to know the pressure drop of the pipeline connected to the 
pumping elements. 
As an example, the following diagram shows the pressure drop of the delivery pipeline flow by unit length depending on 
the  operating  temperature  and  for  a  particular  type  of  lubricant  (in  this  case  NLGI  00  grease  with  160cSt  base  oil  and 
NLGI2 grease with a 180 cSt base oil)

 

Depending on these variables to achieve a proper supply to the delivery point, it is always necessary to ensure that the 
pipeline pressure loss plus the pressure required at the lubrication point does not exceed the maximum pressure supplied 
for pump delivery.

 

The maximum pressures corresponding to the delivery point of the pumping element, taking into consideration the most 
severe operating conditions are as follows, taking the toughest operating conditions into consideration: 

 

1÷12  pumping elements =  80 bar (1160 psi) 

13÷24  pumping elements =  50 bar (725 psi) 

25÷36  pumping elements =  35 bar (507 psi) 

 

Summary of Contents for PoliPUMP eco

Page 1: ...ng and Maintenance Manual Original Instructions Manual drawn up in accordance with EC Directive 06 42 C2291IE WK 24 19 Dropsa products can be purchased from Dropsa bracnhes and authorized distributors...

Page 2: ...UNPACKING 6 6 2 INSTALLATION OF PUMPING ELEMENTS CAPS 6 7 OPERATING INSTRUCTIONS 8 7 1 MEASURES TO BE TAKEN PRIOR TO START UP 8 7 2 USE 9 7 3 FILLING THE RESERVOIR 9 8 PROBLEMS AND SOLUTIONS 10 9 MAIN...

Page 3: ...ions and in various types of machinery for use with grease Any use other than the use intended shall be deemed to be in non compliance with requirements 2 2 SPECIFICATIONS The PoliPUMP eco electric pu...

Page 4: ...pumping element 80bar 1 160psi Reservoir capacity 2 litres 0 53 gallons Grease consistency NLGI00 NLGI2 Protection degree IP 69 Temperature of use 10 C 60 C 14 F 140 F Storage temperature 20 C 80 C 4...

Page 5: ...GREY 5 notches 0 10cc cycle BLACK 6 notches 0 13cc cycle Push in outlet 4 Notches Pump replacement cap included within the scope of supply Stirring paddle with wiper reservoir Input power cable gland...

Page 6: ...ition by distributing them evenly over the holes on the pumping element holder cylinder No MOUNTING POSITIONS No MOUNTING POSITIONS No MOUNTING POSITIONS 1 1 13 13 25 25 2 1 7 14 13 19 26 25 31 3 1 5...

Page 7: ...e pipes and wires have been properly fastened and protected from any possible impact Verify that the grease used is fit for operating temperatures especially at temperatures below 0 C If in doubt cont...

Page 8: ...temperature and that the pipelines are free of any air bubbles Check the correct connection of electrical devices To determine the maximum operating pressure it is necessary to know the pressure drop...

Page 9: ...the maximum level line If this happens you will note a spill of lubricant from the underside of the lid which acts as an air vent 7 4 HOW TO USE If there are no regulations foreseen the pump is electr...

Page 10: ...e time The pump begins the greasing phase but ends it immediately Defective motor or high output absorption Allow to cool for a few minutes and try again If the problem persists replace the gear motor...

Page 11: ...s the periodic inspections the frequency and the intervention that the maintenance will have to carry out in order to ensure the efficiency of the system over time CHECK FREQUENCY INTERVENTION Attachm...

Page 12: ...888274 ECO 0888275 ECO 0 04cc cy cle 0888453 0 13cc cycle 0888456 OPTIONAL SPARE PARTS PART NUMBER DESCRIPTION PART NUMBER DESCRIPTION 5717300 Nylon tube 4x3 low pressure 0888257 Pump replacement cap...

Page 13: ...ND TRANSPORT Before shipment the pumps are carefully packed inside a cardboard box During transport and storage of the equipment pay attention to the direction indicated on the box Upon receipt check...

Page 14: ...ISO 12100 Electrical safety requirements EN 60204 1 The hazards that have not been entirely eliminated but that have been deemed acceptable are listed below During the maintenance phase low pressure s...

Reviews: