Page 14
Installation and Operation Manual - Wood Stove
ENGLISH
3.1.2 With Lowered Ceiling
APPLIANCE CLEARANCES WITH SINGLE
WALL PIPE CONNECTOR
Canada
USA
A
14 ½" (368 mm)
11" (279 mm)
B
19" (483 mm)
18" (457 mm)
C
10" (254 mm)
10" (254 mm)
L
77" ( 1956 mm)
77" ( 1956 mm)
Ve
Ho
L
APPLIANCE CLEARANCES WITH DOUBLE
WALL PIPE CONNECTOR
Canada
USA
A
9" (229 mm)
9" (229 mm)
B
19" (483 mm)
19" (483 mm)
C
7" (178 mm)
7" (178 mm)
L
77" (1956 mm)
77" (1956 mm)
If the above clearances are met, then the distances measured from the flue outlet will be:
DISTANCES
16
FROM PIPE CONNECTOR
WITH SINGLE WALL PIPE CONNECTOR
DISTANCES
17
FROM PIPE CONNECTOR
WITH DOUBLE WALL PIPE CONNECTOR
Canada
USA
Canada
USA
D
18" (457 mm)
14 ½" (368 mm)
D
12 ¼" (311 mm)
12 ¼" (311 mm)
E
28 ½" (724 mm)
27 ½" (699 mm)
E
28 ¼" (718 mm)
28 ¼" (718 mm)
F
19 ¾" (502 mm)
19 ¾" (502 mm)
F
16 ½" (419 mm)
16 ½" (419 mm)
16
The pipe distances listed in this table refer to the distances obtained when the stove is installed in accordance with the appliance clearances
above mentioned.