Drolet AUSTRAL NG1800 Owner'S Manual Download Page 19

19 

CHIMNEY CONNECTOR 

Your chimney connector (commonly called stove pipe) and chimney must have the same 
diameter as the stove’s exhaust outlet. The stove pipe must be made of aluminized or cold roll 
steel with a minimum 24-gauge thickness (0.021" or 0.53 mm).  It is strictly forbidden to use 
galvanized steel. 
 

The

 

following

 

recommendations

 

may

 

be

 

useful

 

for

 

the

 

installation

 

of

 

your

 

chimney

 

connector:

 

 

 

Your

 

chimney

 

connector

 

should

 

be

 

assembled

 

in

 

such

 

a

 

way

 

that

 

the

 

male

 

end

 

(crimped)

 

faces

 

down

 

to

 

prevent

 

creosote

 

dripping

 

outside

 

the

 

joints.

 

Attach

 

each

 

of

 

the

 

sections

 

to

 

one

 

another

 

with

 

three

 

equidistant

 

metal

 

screws.

  

Also

 

use

 

three

 

equidistant

 

metal

 

screws

 

to

 

attach

 

the

 

connector

 

to

 

the

 

stove’s

 

exhaust

 

collar.

  

See

 

Figure

 

2.3

 

(A)

 

and

 

Figure

 

2.3

 

(B).

 

 

The

 

pipe

 

must

 

be

 

short

 

and

 

straight.

  

All

 

sections

 

installed

 

horizontally

 

must

 

slope

 

at

 

least

 

¼

 

inch

 

per

 

foot,

 

with

 

the

 

upper

 

end

 

of

 

the

 

section

 

toward

 

the

 

chimney.

 

See

 

Figure

 

2.3

 

Detail

 

B.

 

 

To

 

insure

 

a

 

good

 

draft,

 

the

 

total

 

horizontal

 

length

 

of

 

the

 

connector

 

should

 

never

 

exceed

 

8'

 

to

 

10'

 

(2.4

 

to

 

3.04

 

m).

   

In

 

the

 

case

 

of

 

vertical

 

installation,

 

the

 

total

 

length

 

of

 

the

 

connector

 

can

 

be

 

much

 

longer

 

and

 

connected

 

without

 

problem

 

to

 

the

 

chimney

 

at

 

the

 

ceiling

 

level.

 

 

There

 

should

 

never

 

be

 

more

 

than

 

two

 

90

 

degrees

 

elbows

 

in

 

the

 

whole

 

connector

 

and

 

chimney

 

system.

 

Never

 

start

 

with

 

a

 

90

o

 

elbow.

  

Always

 

go

 

up

 

vertically

 

for

 

at

 

least

 

2

 

feet

 

from

 

the

 

flue

 

spigot

 

before

 

using

 

a

 

90

o

 

elbow.

 

 

The

 

connector

 

must

 

not

 

pass

 

through

 

any

 

combustible

 

material,

 

nor

 

may

 

it

 

pass

 

through

 

a

 

concealed

 

space

 

(such

 

as

 

an

 

attic,

 

roof

 

space,

 

or

 

closet).

 

If

 

passing

 

through

 

a

 

wall,

 

ceiling,

 

or

 

into

 

a

 

masonry

 

chimney,

 

use

 

either

 

chimney

 

components

 

listed

 

for

 

that

 

specific

 

use,

 

or

 

means

 

acceptable

 

to

 

local

 

authorities

 

having

 

jurisdiction

 

over

 

the

 

installation.

 

 

Installation

 

of

 

a

 

"barometric

 

draft

 

stabiliser"

 

(fireplace

 

register)

 

on

 

a

 

connector

 

is

 

not

 

recommended.

 

 

FIGURE 2.3 (A) Connecting Sections 

Summary of Contents for AUSTRAL NG1800

Page 1: ...by STOVE BUILDER INTERNATIONAL INC 250 de Copenhague Saint Augustin de Desmaures Qu bec G3A 2H3 Tel 418 878 3040 Fax 418 878 3001 www drolet ca This manual is available for free download on the manuf...

Page 2: ...IRST FIRES 28 IGNITION 28 HEATING 29 RELOADING 30 CREOSOTE FORMATION AND NEED FOR REMOVAL 30 USE OF THE BYPASS DAMPER 31 ASH DISPOSAL 32 FAN BLOWER OPERATION 32 MAINTENANCE 33 GLASS 33 GASKETING 33 PA...

Page 3: ...operty damage bodily injury or even death Consult your municipal building department or fire officials about restrictions and installations requirements in your area and the need to obtain a permit Ke...

Page 4: ...x D x H 23 3 4 x 35 x 31 1 4 603 x 889 x 794 mm 23 3 4 x 34 x 31 3 8 603 x 864 x 797 mm 23 3 4 x 34 x 30 3 8 603 x 864 x 772 mm 23 3 4 x 35 x 30 1 4 603 x 889 x 768 mm Combustion Chamber Baltic Myriad...

Page 5: ...load of seasoned cordwood inserted inside the firebox The EPA output on the other hand is what has been obtained during emissions testing The EPA test procedure requires that a special type of wood be...

Page 6: ...Use a chimney thermometer installed at a distance of approximately 18 inches on the flue pipe above the stove Flue gases should reach at least 350 F before you close the stove s primary air intake com...

Page 7: ...o supplied screws 2 Slide the ash pan in position Side Panels and Ash Lip Installation 3 Start by fixing the front part of the decorative side in the two clips welded on the sides of the fire box 4 Th...

Page 8: ...8 AUSTRAL LEGEND AND MYRIAD Ash Pan Installation...

Page 9: ...justed periodically to provide an air tight fit To adjust Remove the lock pin spring pin by pulling and turning it using pliers wise grip Turn the handle counter clock wise one turn to increase pressu...

Page 10: ...D TO DEPRIVE THE FIRE OF OXYGEN CALL THE FIRE DEPARTMENT DO NOT CONNECT TO ANY AIR DISTRIBUTION DUCT OR SYSTEM A SOURCE OF FRESH AIR INTO THE ROOM OR SPACE HEATED SHALL BE PROVIDED WHEN REQUIRED DO NO...

Page 11: ...305 mm 9 229 mm 18 10 457 254 mm 21 533 mm 18 457mm 48 1220 mm 84 213 cm Legend 15 6 381 155 mm 12 305 mm 9 229 mm 18 10 457 254 mm 21 533 mm 18 457 mm 48 1220 mm 84 213 cm Myriad 15 7 381 178 mm 23...

Page 12: ...12 FIGURE 1 3 Clearances to combustible materials and floor protection...

Page 13: ...tove s required clearance if such clearance is smaller than 8 inches 203 mm Note 2 Only required under the horizontal section of the connector Must exceed each side of the connector by at least 2 inch...

Page 14: ...iles or an equivalent non combustible material on fire proof supports spaced out at least 1 25 mm by non combustible spacers see graphic 3 50 33 Ceramic tiles or an equivalent non combustible material...

Page 15: ...d combustible ceiling B 20 in 500 mm minimum C 1 in 25 mm minimum D Between 1 in and 3 in 25 mm and 75 mm E 3 in 75 mm minimum F 18 in 457 mm minimum 1 Shielding 2 Non combustible spacers 3 Ceiling pr...

Page 16: ...3 A 1 in 25 mm minimum 1 Combustible wall 2 Non combustible spacers 3 Non combustible support 4 Ceramic tile or non combustible material _______________________________________________________________...

Page 17: ...ombustible wall 2 Non combustible spacers 3 Brick __________________________________________________________________ Graphique 6 A 1 in 25 mm minimum 1 Combustible wall 2 Non combustible spacers 3 0 0...

Page 18: ...the installation of your chimney 1 Do not connect this unit to a chimney flue serving another appliance 2 It must rise above the roof at least 3 0 9 mm from the uppermost point of contact 3 The chimne...

Page 19: ...er foot with the upper end of the section toward the chimney See Figure 2 3 Detail B To insure a good draft the total horizontal length of the connector should never exceed 8 to 10 2 4 to 3 04 m In th...

Page 20: ...tween the stove and chimney See figure 2 4 A The use of two 45 degree elbows See figure 2 4 C is often preferable to a single 90 degree elbow See figure 2 4 B because less turbulence is created in the...

Page 21: ...pressure gauge the reading should be between 05 07 inches of water column w c at a medium high fire A draft measure of less than 03 w c will cause operational difficulties while too much draft greate...

Page 22: ...22 TYPICAL INSTALLATIONS FACTORY BUILT CHIMNEY ROOF FLASHING 18 CLEARANCE WALL SUPPORT WALL RADIATION SHIELD RAIN CAP Wall installation CEILING SUPPORT RADIATION SHIELD Vertical installation...

Page 23: ...t thimble or construct your own brick thimble If you are using a masonry chimney it is important that it be built in compliance with the specifications of the Building Code in your region It must norm...

Page 24: ...24 FACTORY BUILT THIMBLE...

Page 25: ...25 BRICK THIMBLE...

Page 26: ...her heating appliances smell do not operate properly suffer smoke roll out when opened or back drafts occur whether or not there is combustion present 3 Opening a window slightly on a calm windless da...

Page 27: ...he wood must have dried for 9 to 15 months such as the humidity content in weight is reduced below 20 of the weight of the log It is very important to keep in mind that even if the wood has been cut s...

Page 28: ...u are overheating The smoke resulting from the paint curing process is not toxic IGNITION After making sure that the stove air intake controls are fully open completely pull out towards you place seve...

Page 29: ...INING OF THE FIREBOX NEVER STORE WOOD WITHIN STOVE INSTALLATION CLEARANCES OR WITHIN THE SPACE REQUIRED FOR CHARGING AND ASH REMOVAL DO NOT BUILD THE FIRE TOO CLOSE TO THE GLASS BURNING SOLID FUELS GE...

Page 30: ...r if not already included is highly recommended to maximize your unit s efficiency CREOSOTE FORMATION AND NEED FOR REMOVAL When wood is burned slowly it produces tar and other organic vapours which co...

Page 31: ...mpletely and then open the bypass damper Wait for approximately 10 to 15 seconds and open the stove door Close the bypass damper when you are finished reloading Never leave the bypass damper open unde...

Page 32: ...WITHOUT OPERATING THE STOVE THE ASH PAN CAN BECOME VERY HOT WEAR GLOVES TO PREVENT INJURY NEVER BURN THE STOVE WITH THE ASH TRAP OPEN THIS WOULD RESULT IN OVER FIRING THE STOVE DAMAGE TO THE STOVE AN...

Page 33: ...sold The glass should be washed only when cold Under normal operating conditions the glass is designed to stay clean Glass cleaning may be required when burning damp wood Furthermore small creosote o...

Page 34: ...or this purpose simply scrub the surface to be repainted with fine sand paper clean it properly and apply thin coats 2 of paint successively Refer to page 18 of the present manual for the paint curing...

Page 35: ...35 BRICK LAYOUT ITEM PART DESCRIPTION QTY 1 29015 4 X 9 BRICK 21 2 PL36022 4 X 5 3 8 BRICK 1 3 PL36054 4 X 9 BRICK CUT 2 4 SE16059 ASH DUMP CAP 1...

Page 36: ...nd labour costs covered by this warranty are limited according to the table below The manufacturer at its discretion may decide to repair or replace any part or unit after inspection and investigation...

Reviews: