SETUP AND CONFIGURATION
Object list
Table 17-1:
Object List
Property
Description
Range/Type
R/W
Device Object
APDU_Timeout
Time between retransmissions in milliseconds. This device does not support
retransmissions, so this always reads as “0”.
0
R
App Software Version
Controller Firmware Version (assembled by firmware)
XX.XrYY (“X” = version; “Y” = revision)
String
R
Database_Revision
Increases if the settings change
16 bit
R
Daylight_Savings_Status
Daylight savings status of host controller
True/False
R
Description
Description of controller or location
32 Bytes
R/W
Device Address Binding
Address binds
List
R
Firmware_Revision
BACnet Firmware Revision
String
R
Local_Date
Date of host controller in format YYYY-MM-DD-DOW
YYYY-MM-DD-DOW
R
Local_Time
Time of host controller in format HH:MM:SS
HH:MM:SS
R
Max APDU Length Accepted
The maximum APDU length supported by this device is 480.
16 bit
R
Max Info Frames
The value specifies the maximum number of information frames the node
may send before it must pass the token.
1
R/W
Max_Master
Number of the highest addressed node
1…127
R/W
Model_Name
“X2-abcde-BAC” (assembled by firmware)
a = number of loops
b = number of passive inputs
c = number of universal inputs
d = number of binary outputs
e = number of analog outputs
String
R
Number_of_APDU_Retries
Number of retransmissions. This device does not support retransmissions,
so this always reads as “0”.
0
R
Object_Identifier
Device object identifier (CO06…CO09)
22 bit
R/W
Object_Name
Name of device
32 Bytes
R/W
Object_Type
The value is always “Device” for the device object
10 bit
R
Protocol_Objects_Supported
The enumeration of the supported object types
List
R
Protocol_Services_Supported
The enumeration of the supported services
List
R
Protocol_Version
BACnet protocol version number
1
R
Protocol_Revision
BACnet protocol revision number
14
R
Segmentation_Supported
This device does not support segmentation, so this always reads as “NO_
SEGMENTATION (3)”.
0…3
R
System_Status
Current physical and logical status supported:
• OPERATIONAL (0)
• DOWNLOAD_REQUIRED (2) (IF INT. EEPROM CONF. ERRORS)
• NON_OPERATIONAL (4) (IF INT. I2C BUS ERRORS)
0…5
R
UTC_Offset
Offset to UTC time in case UTC time synchronization is used
-780…780
R/W
Vendor_Identifier
561
R
Vendor_Name
Vector Controls GmbH
String
R
Object_List
List of all objects currently implemented in the device
List
R
17
DRISTEEM TCI AND TRI2 HUMIDISTAT INSTALLATION, OPERATION, AND MAINTENANCE MANUAL