Low voltage-fused-switch disconnector system 403                                                                         Safety 

 
B843

2       Safety

 

 
 
2.1     Intended use / guarantee

 

 

The low voltage fused disconnector sysytem is intended for use under the conditions outlined in the 
section Technical data, on Page 16. 

 

            Any use other than those outlined in this section is classed as an unintended use. 

 

           Any of the following carried out without express written approval from the manufacturer 

 

           • alterations or extensions 
           • using non-genuine spare parts 
           • repairs carried out by companies or persons not authorised by the manufacturer 

             could result in the guarantee becoming null and void.

2.2     Personnel selection and necessary qualifications

 

 

           Persons working with the switching device must 

 

           • be at least 18 years of age. 
           • have received sufficient training for the relevant tasks. 
           • be familiar and comply with the current valid rules and safety regulations. 

 

The owner must ensure that only authorised personnel work on the switching device. 

 
Personnel learning to use or being introduced to the device, or operating the device as part of training 
may only work on the switching device when supervised by an experienced member of staff! 

 
All work on the switching device may only be carried out by trained specialist personnel (DIN VDE 
0105-100) and in compliance with all valid regulations specified in the accident prevention regulations 
(UVVen).

2.3     Organisational safety

 

 

The owner must ensure that this operating and maintenance manual is always in the immediate vici-
nity of the persons responsible for assembling, operating and carrying out maintenance work on the 
switching device 

 

 8 / 16

Summary of Contents for B843

Page 1: ...HNE GMBH D 85366 MOOSBURG PHONE 49 87 61 6 81 0 FAX 49 87 61 68 11 37 http www driescher de infoservice driescher de Mounting and operating instructions for DRIESCHER Low voltage fused switch disconne...

Page 2: ...ntended use guarantee 8 2 2 Personnel selection and necessary qualifications 8 2 3 Organisational safety 8 2 4 Dangers caused by the switching device 9 2 4 1 Danger due to moving parts 9 2 4 2 Danger...

Page 3: ...al 16 Low voltage fused switch disconnector system 403 B843 3 16 CE marking The DRIESCHER low voltage products are subject to the CE marking requirement in connec tion with the Low Voltage Directive 2...

Page 4: ...he descriptions are accompanied by figures and schematic diagrams of the switching device or its assemblies 1 1 2 Use of symbols legend The following symbols are used in this manual in addition to the...

Page 5: ...azards for people and goods when handling electrical energy the expert handling of the equipment and compli ance with the applicable regulations is generally required Installation and maintenance work...

Page 6: ...ing cover M Inspection holes N Flat spring O Busbar contact P Mounting brackets for frame mounting Q Slider 3 pole R Slider 3 pole with operating handle S Terminal screw M12 caulked 6 16 Low voltage f...

Page 7: ...ng handle switchable Slider B with recessed grip above and down with inserted low voltage high rupturing capacity fuse C 1 pole switchable 3 pole switchable with operating handle 3 pole switchable Pic...

Page 8: ...st be at least 18 years of age have received sufficient training for the relevant tasks be familiar and comply with the current valid rules and safety regulations The owner must ensure that only autho...

Page 9: ...vicinity are supplied with dangerous current Touching these parts poses a risk of personal injury or material damage In the case of a fault arc extreme hazards arise high thermal energy pressure wave...

Page 10: ...ing may only be carried out by specially trained specialists Please refer to the Safety Tools instructions for use Order No 3 81301043 Insulating socket wrench scope of delievery Pic 4 10 16 Top side...

Page 11: ...system 403 Pic 5 and 6 Tightening torque 30 Nm 4 Connect the cable see chapter 3 3 2 page 13 5 Integrate the cable insulating cover L Pic 7 at the cable feeder Pic 5 403 system mounting situationon a...

Page 12: ...on system 403 Pic 9 3 Ingerate the cable insulating cover L Pic 7 on system 403 to prevent unintentional contact 4 Put system 403 on the frame 5 Fix system 403 Pic 9 10 or 11 Tightening torque 75 Nm 6...

Page 13: ...isted or bent under any circumstances The caulked connection screws S must not be removed Furthermore a connection with V direct connection terminals or flat direct connection termi nals is possible f...

Page 14: ...Removal low voltage fused switch disconnector system 403 For the disassembly of the low voltage fused switch disconnector system 403 the steps mentioned on page 11 and 12 assembly must be carried out...

Page 15: ...ss actuate quickly upwards the slider is now back in Stand by position When actuating use the recessed grip at the top and bottom of the sli der For slider 3 pole with actuating handle use both hands...

Page 16: ...g to EN 60947 3 AC 22B AC 22B AC 22B Degree of pollution 3 3 3 Rated reduction factor RDF 1 0 1 0 1 0 Temperature range 25 up to 55 C Site altitude max 2000 m over NHN Relative humidity maximum daily...