OPERATING MANUAL - ARID-X10C FLOOR MOUNT DRYER
Revision 7/28/04
2. Press the up arrow
↑
key to increase
the set point or the down arrow
↓
key to
decrease the setting until the desired
process air temperature set point is
displayed.
3. Press the
SEL
key again to enter the
new temperature setting.
CAUTION: Do not operate this dryer below 140
degrees F (60 deg. C) or above 350 degrees F
(177 deg. C).
The High Temp Alarm condition discussed
below will initiate a “Dryer Shutdown” that cuts
power to the blower, digital controller and ELC
output relays. See Trouble-Shooting section of
this manual.
Process Air Temperature Alarms
The ELC/Digital Control system is
preprogrammed with alarm set points that will
shut the dryer down and activate the
TEMPERATURE ALARM light on the dryer
control panel and the ALM1 light on the digital
controller.
The alarm will be activated if either the process
air temperature fails to reach the set point within
the alloted time period or the temperature
exceeds the high limit. The HIGH TEMP
ALARM light will illuminate for both
conditions.
Thermocouple Failure Alarm
If a failure is detected with the Process Air
Thermocouple, the upper Process Air
Temperature display (labeled PV) on the Digital
Controller will flash and display 0000. This
alarm will be displayed if the thermocouple is
not connected or is faulty.
ALARMS
DIGITAL CONTROLLER