Level Sensor Assembly (F and S style)
FLOAT
Installation:
Install the float with retaining fastener (“e-clip”) for the “
F
” style probe and install the float with retaining
fastener (“R-clip”) for the “
S
” style probe as shown.
“F” style probe with (“e-clip”)
“S” style probe with (“R-clip”)
Sensor Installation – Tri-Clamp Flange style
NOTE:
The Rigid Level sensor in this style requires a
minimum tank bottom clearance of 3/8”. Tank bottom
clearance is defined as the distance from tank bottom
surface to the bottom of the tube on the level sensor.
STEP 1:
Install O-ring assembly
(1)
.
STEP 2:
Mount level sensor with clamp assembly
(2)
as
shown.
COMPLETED ASSEMBLY
NOTE:
Extreme temperatures have an effect on level sensor
length. In high temperatures, level sensor length will
expand. In low temperatures, level sensor length will
contract.
MINIMUM TANK BOTTOM CLEARANCES:
“B”
style: 1/2”,
“F”
and
“S”
style: 3/8”