Operating, Maintenance, Commissioning

Page 10 

Weekly programmes

The weekly programme defi nes which fan level is activated at various points in time.

From a technical perspective, the ventilation unit has 4 levels - 0, 1, 2 and 3 - whereby fan 
level 0 (LST0) is equivalent to switching off the unit.

    

   EINSTELLUNGEN 

     WOCHENPROGRAMME

     

LST2  

 

Automatik

Di 8.01.08 

           08:00

  

Mo  Di   Mi   Do
Fr  Sa  So

    

Montag 

            LST0

    18:08 

bis     08:00

    

Montag 

             LST1

    08:00 

bis     18:08

    

Montag 

            LST3

    00:00 

bis     00:00

    

Di wie Mo?
JA 

NEIN    ABBRUCH

    

Enter

Enter

Enter

Enter

Enter

Enter

Enter

After commissioning, the following values apply 
for the ventilation system:

Fan level 0: Both fans are switched off

Fan level 1: 

Approx. 30% below the nominal air quantity

Fan level 2: Nominal air quantity

Fan level 3: 

Approx. 30% above the nominal air quantity

Since the nominal air quantity for the building is 
set using fan level 2, it is not necessary to set a 
time period for fan level 2. This is always active 
when no other fan level has been programmed. 
Therefore, only the settings for levels 0, 1 and 3 
are available in the menus.

Creating the weekly programme: 

The fan levels can be set for each day of the 
week. It is thus possible to set reduced venti-
lation during the nights and the weekends or to 
programme a short period of high-power venti-
lation prior to the commencement of business 
hours.

In order to access the weekly programme, press 
the "Enter" button. Select "Wochenprogramme" 
using the arrow buttons and confi rm this with 
the "Enter" button.

Use "Enter" to select and confi rm values; use 
the arrow buttons to change values.

The programme for one day of the week can be 
copied to the following day.

The example on the right illustrates the set-
ting for Monday (Montag). The settings for 
Tuesday (Dienstag), Wednesday (Mittwoch), 
Thursday (Donnerstag), Friday (Freitag), 
Saturday (Samstag) to Sunday (Sonntag) are 
made in the same way. 

Summary of Contents for aerosilent topo

Page 1: ...aerosilent topo Operating Maintenance Commissioning...

Page 2: ......

Page 3: ...er 8 Maintenance___________________________________________________________ 13 Safety notes for filter changes 13 Changing the filters 13 Commissioning ________________________________________________...

Page 4: ...consumption of the fans 180 m3 h and 150 Pa external 75 W Thermal power of the optional PWW heat register nominal air quantity and VL RL 60 45 1350 W Sound power level at nominal air quantity and 100...

Page 5: ...er application The unit is designed for the ventilation and heating optional of living rooms and lounges in passive houses and if applicable for near passive buildings depending on the calcula tion an...

Page 6: ...o set an individual weekly programme 3 level switch Selecting the fan level You use the function button to select the required fan level Once you have pressed the button the LED for the activated leve...

Page 7: ...luminated Coarse particle filter needs replacing in the unit Please refer to the Maintenance sec tion LED flashes A fault has occurred Possible causes are The supply air or extract air fan has failed...

Page 8: ...he cursor position The Enter button is used to save the values that have been set or select menu op tions Operating modes The unit can be used in 6 different operating modes which are selected using t...

Page 9: ...me for high power ventilation The time period for Party mode can be changed to a value between 15 and 120 minutes in the Settings menu The screen displays the message LST3 Party After this time period...

Page 10: ...uilding is set using fan level 2 it is not necessary to set a time period for fan level 2 This is always active when no other fan level has been programmed Therefore only the settings for levels 0 1 a...

Page 11: ...y from 18 00 to 06 00 0 24 12 18 6 Example In the following example the system is switched off during the night and over the week end High power ventilation takes place prior to business hours Weekly...

Page 12: ...of the display flashes St rung Venti Fan fault This error message appears if a fault occurs on one of the two fans For safety reasons the second fan is also deactivated Please contact your authorised...

Page 13: ...te The filter should be changed within 2 4 weeks of the Filter change message appearing Safety notes for filter changes Caution The filter change intervals are only valid for a completely run in syste...

Page 14: ...in the openings Please note the direction of insertion indicated by an arrow on the fine particle air filter Close the inspection doors and fasten the latches The contact switch 4 is activated and the...

Page 15: ...ause serious personal injury Im proper working procedures could damage unit components The initial commissioning may only be carried out by suitably qualified and authorised technicians When the contr...

Page 16: ...nicians Before setting the nominal air quantity the unit must be fully disconnected from the mains Open the latches for the inspection doors at the top of the unit Remove the cover guard from the cont...

Page 17: ...y Example Nominal air quantity 80 m h 5 OFF 6 OFF 7 OFF 8 OFF Setting the fan balance DIP switches 3 and 4 are used to set a higher air quantity for the supply air fan in compa rison to the extract ai...

Page 18: ...tion unit optional temperature set Settings on the overall system After initial commissioning of the unit check the supply and extract air valve flow rates as given in the plans Measure and record the...

Page 19: ...cian has handed over the unit to you with the following settings Please keep this information to hand in case you have any queries Customer Location Unit type Serial number Initially commissi oned on...

Page 20: ...ieeffiziente haustechniksysteme gmbh Achstrasse 42 6922 Wolfurt T 05574 47895 0 F 05574 47895 4 E mail office drexel weiss at www drexel weiss at ATU 35542007 FN 192604t Company Accounts Register Feld...

Reviews: