1. COMMISSIONING

1.1 Setting the torque values

The torques are set by manufacturer as instructed according to the order. The torques are
only indicated on the name plate if this is specifically requested. If no torques are specified
on the order, the smallest possible torque is set by the manufacturer. The torque can be
infinitely varied within the range given on the name plate by means of the torque scales
affixed to the unit

Use the setting screws for torque setting if torque signals are to be used (refer to fig-
ure 1.1). Loosen screw on top of the cams if torque setting is to be performed in direction
OPEN. The screw on the bottom of the cams is used for torque setting in direction CLOSE.
After unfastening the respective screw, the cams can be readjusted by turning. Turn the
cam until the desired value on the scale is aligned with the mark. Finally, fasten the
appropriate screw.

1. Locking screw for torque adjust-

ment OPEN

2. Scale with setting range for torque

in direction OPEN

3. Setting mark (in this instance

30 Nm for both directions)

4. Scale with setting range for torque

in direction CLOSE

5. Torque switch for direction OPEN

in standard version

6. Torque switch for direction CLOSE

in standard version

7. Locking screw for torque adjust-

ment CLOSE

Figure 1.1: Torque setting

4

Additional operating manual

Summary of Contents for 384771

Page 1: ...C with limit switching unit Operation and servicing instructions Part no 384771 Revision 1 0 Date April 26 2017 Keep this manual for future reference These operating manual is only valid in connection...

Page 2: ...ntents 1 Commissioning 3 1 1 Setting the torque values 4 1 2 Setting the limit positions 5 1 3 Setting the reduction gearing for multi turn actuators 6 1 4 Setting the reduction gearing for part turn...

Page 3: ...wise output drive rotation corresponds to direc tion OPEN DR and WR switches are designated for torque and limit po sition in direction CLOSE DL and WL switches are designated for torque and limit pos...

Page 4: ...if torque setting is to be performed in direction OPEN The screw on the bottom of the cams is used for torque setting in direction CLOSE After unfastening the respective screw the cams can be readjus...

Page 5: ...itions for OPEN and CLOSE use the setting screws as shown in figure 1 2 1 Setting screw for limit position OPEN 2 Setting screw for limit position CLOSED Figure 1 2 Limit switches in standard version...

Page 6: ...ti turn actuators To reset the reduction gearing according to table 1 1 loosen the fixing screw item 4 in figure 1 3 After unfastening the screw the sliding wheel can be moved up smaller angle for the...

Page 7: ...is mounted on an output drive of the actuator Figure 1 4 limit switching unit input drive gear wheel The reduction gearing is available for a range between 1 38 1 450 turns stroke The range is divide...

Page 8: ...5 40 8 5 3 1 SectionII 40 9 74 2 6 3 1 SectionII 74 3 135 7 3 1 SectionII 135 245 8 3 1 SectionII 246 446 9 3 1 SectionII 447 811 10 3 1 SectionII 812 1450 11 Table 1 1 Setting the reduction gearing...

Page 9: ...50 range III has been preset otherwise range II 4 Set the reduction gearing according to the calculated value by shifting the sliding wheel with regard to table 1 1 1 4 Setting the reduction gearing f...

Page 10: ...5 tr stroke min 0 25 0 5 1 375 2 75 6 325 Sliding wheel position 1 2 2 1 2 Turning angle Cam shaft 175 4 193 177 5 214 5 271 3 Settling time 58 5 64 3 59 1 71 5 90 4 Table 1 2 Setting the reduction ge...

Page 11: ...Notes Additional operating manual 11...

Page 12: ...DREHMO GmbH Zum Eichstruck 10 57482 Wenden Germany Phone 49 2762 9850 0 Phone service 49 2762 9850 204 Internet www drehmo com E mail drehmo drehmo com...