9
-
Figure 3
Universal suspension
Use of suspension even to screw spacing if heater is substituted for another type.
Proper verticality of heater can be adjusted once the connecting screws are loosened by slight turning
of the suspension.
Figure 4
If the hot water heater is mounted in a
tight, smaller space
, or in an intermediate ceiling, etc.,
you have to make sure that the connecting side of the appliance (connections to water supply,
area for electric plugging) remained accessible and no heat accumulation occurs. Free space
of up to
600 mm
from the bottom edge of the heater has to be left available under the heater.
When mounted directly under the ceiling, the distance from the ceiling has to be
50 mm
at least.
If the water heater is mounted in enclosed areas, inter
-
ceilings, built
-
in structures and
recesses, ensure
sufficient access to service fittings, electrical terminal boards, anodes and manholes. Minimum spacing from
manhole is 600 mm.
2.3
PLUMBING FIXTURE
The heater connects to water distribution pipes with ¾“ thread tubes in the bottom part
of the heater.
Blue
-
cold water supply, red
-
hot water outlet. For potential disconnection
of the heater, service water inlets and outlets must be provided with screw coupling Js 3/4“.
The safety valve is mounted on the cold water inlet identified with a blue ring.