6-20
EN50160 Power Quality
EN50160 Power Quality (for strict EN50160 monitoring only)
Advanced setup
options for
EN50160
EN50160 is a statistical analysis of power quality data based on the EN standard. The
statistical package called Quality of Supply (QOS) is built into the 4400, with
monitoring and setup protocols set to determine voltage measurement compliance
required for EN50160 monitoring. The EN50160-required measurement parameters
include Power Frequency, Supply Voltage Variations, Rapid Voltage Changes, Supply
Voltage Unbalance, Harmonic Voltage, Interharmonic Voltage, and Mains Signalling.
The monitoring site is said to be IN COMPLIANCE if the statistical value over one (1)
week for the specified parameters is 95% or greater.
EN50160 Options setup allows users to define up to five mains signalling frequencies
below 3 KHz. Users can also select pre-defined values for main voltage characteristics
of electricity supplied by Low Voltage (LV) and Medium Voltage (MV) public
networks.
NOTE
EN50160 is defined for the electricity supplied at the supply terminals, and does not
deal with the supply system or consumer’s installation or electrical equipment itself.
Since the standard deals with the voltage characteristics which can be expected in
public distribution networks, other aspects essential for supply quality (i.e. short circuit
power) are not treated within the scope of the standard. EN50160 standard is applicable
only under normal operating conditions of the supply system.
EN50160
optional settings
Continued on next page
Action...
Result...
STEP 1: From the Choose
Monitoring Mode screen, select
EN50160 Power Quality, then
press Next to display Advanced
Options for EN50160.
• If the default settings for the
EN50160 PQ monitoring are
acceptable without change,
press
Next
. The Site Name/
Memory Card screen will
appear. See pages 5-20 to 5-23.
• To review and/or modify
threshold settings for EN50160
monitoring, press
EN50160
Options
. Proceed to Step 2 on
page 6-21.
• Press
Cancel
to quit and return
to Start menu.
MARK112b
www.
.com
1.800.561.8187
Summary of Contents for PowerGuide 4400
Page 13: ...xiii Dranetz PowerGuide 4400 www com information itm com 1 800 561 8187 ...
Page 14: ...xiv www com information itm com 1 800 561 8187 ...
Page 78: ...4 16 www com information itm com 1 800 561 8187 ...
Page 136: ...6 22 www com information itm com 1 800 561 8187 ...
Page 158: ...7 22 www com information itm com 1 800 561 8187 ...
Page 196: ...9 16 www com information itm com 1 800 561 8187 ...
Page 206: ...A 10 www com information itm com 1 800 561 8187 ...
Page 226: ...C 8 www com information itm com 1 800 561 8187 ...
Page 228: ...D 2 www com information itm com 1 800 561 8187 ...
Page 252: ...F 4 www com information itm com 1 800 561 8187 ...
Page 262: ...MARK201 LEVEL 200 Scope Mode MARK202 MARK205 G 9 www com information itm com 1 800 561 8187 ...