Set the input and output ranges with DIP switches (● = ON) as indicated in the following table:
● = ON
Factory settings: all switches in position OFF
LED indication
The transmitter has a green and a red/yellow LED on front panel.
LED
Announcement
green
continuous
Power LED, normal operation
green
flashing
Over/under range on input
yellow
quick flashing
Teach-In mode active
yellow
slow double flashing
Commissioning Function active
red
flashing
Sensor break or configuration error
red
continuous
Device error, replacement is necessary
Input
DIP S1
● = on
1 2 3 4 5
Pt100
●
Pt1000
●
Ni100
●
●
Resistor
●
2-wire
●
3- wire
4- wire
●
●
●
●
Potentiometer
●
●
Type J
●
Type K
CJC internal
●
CJC external (Pt100)
●
CJC off
●
●
± 100mV
●
●
●
mV x 10
●
●
●
PC (USB) Setting
Output
DIP S2
7 8 9 10
0 … 20 mA
●
4 … 20 mA
●
0 … 10 V
●
●
0 … 5 V
Characteristic
rising
●
falling
Error Message
signalize
●
not signalize
Start Value
End Value
DIP S1
DIP S2
DIP S2
6 7 8 9 10 °C
°F
Ω
Poti
mV 1 2 3 4 5 6 °C
°F
Ω
Poti mV
1 2 3 4 5 6 °C
°F
Ω
Poti
mV
●
-200
-328
0
0%
-100
●
-150
-238
100 10%
-/-
●
650
1202
2100 70%
-10
●
-175
-283
50
1%
-90
●
-125
-193
150 15%
-/-
●
●
675
1247
2200 71%
-15
●
●
-150
-238
100 2%
-80
●
●
-100
-148
200 20%
-/-
●
●
700
1292
2300 72%
-20
●
-125
-193
150 3%
-70
●
-75
-103
250 25%
-/-
●
●
●
725
1337
2400 73%
-25
●
●
-100
-148
200 4%
-60
●
●
-50
-58
300 30%
-/-
●
●
750
1382
2500 74%
-30
●
●
-75
-103
250 5%
-50
●
●
-25
-13
350 35%
-/-
●
●
●
775
1427
2600 75%
-35
●
●
●
-50
-58
300 6%
-45
●
●
●
0
32
400 40%
-/-
●
●
●
800
1472
2700 76%
-40
●
-25
-13
350 7%
-40
●
25
77
450 45%
-/-
●
●
●
●
825
1517
2800 77%
-45
0
32
400 8%
-35
●
●
50
122
500 46%
-/-
●
●
850
1562
2900 78%
-50
●
●
25
77
450 9%
-30
●
●
75
167
550 47%
-/-
●
●
●
875
1607
3000 79%
-55
●
●
50
122
500 10%
-25
100
212
600 48% 100
●
●
●
900
1652
3100 80%
-60
●
●
●
75
167
550 11%
-20
●
●
●
125
257
650 49%
95
●
●
●
●
925
1697
3200 81%
-65
●
●
100
212
600 12%
-15
●
●
150
302
700 50%
90
●
●
●
950
1742
3300 82%
-70
●
●
●
125
257
650 13%
-10
●
●
●
175
347
750 51%
85
●
●
●
●
975
1787
3400 83%
-75
●
●
●
150
302
700 14%
-5
●
●
●
200
392
800 52%
80
●
●
●
●
1000
1832
3500 84%
-80
●
●
●
●
175
347
750 15%
0
●
●
●
●
225
437
850 53%
75
●
●
●
●
●
1025
1877
3600 85%
-85
●
200
392
800 20%
5
●
250
482
900 54%
70
●
●
1050
1922
3700 86%
-90
●
●
225
437
850 25%
10
●
●
275
527
950 55%
65
●
●
●
1075
1967
3800 87%
-/-
●
●
250
482
900 30%
15
●
●
300
572
1000 56%
60
●
●
●
1100
2012
3900 88%
-/-
●
●
●
275
527
950 35%
20
●
●
●
325
617
1050 57%
55
●
●
●
●
1125
2057
4000 89%
-/-
●
●
300
572
1000 40%
25
●
●
350
662
1100 58%
50
●
●
●
1150
2102
4100 90%
-/-
●
●
●
350
662
1500 45%
30
●
●
●
375
707
1150 59%
45
●
●
●
●
1175
2147
4200 91%
-/-
●
●
●
400
752
2000 50%
35
●
●
●
400
752
1200 60%
40
●
●
●
●
1200
2192
4300 92%
-/-
●
●
●
●
450
842
2500 55%
40
●
●
●
●
425
797
1250 61%
35
●
●
●
●
●
1225
2237
4400 93%
-/-
●
●
500
932
3000 60%
45
●
●
450
842
1300 62%
30
●
●
●
1250
2282
4500 94%
-/-
●
●
●
550
1022
3500 65%
50
●
●
●
475
887
1400 63%
25
●
●
●
●
1275
2327
4600 95%
-/-
●
●
●
600
1112
4000 70%
60
●
●
●
500
932
1500 64%
20
●
●
●
●
1300
2372
4700 96%
-/-
●
●
●
●
650
1202
4500 75%
70
●
●
●
●
525
977
1600 65%
15
●
●
●
●
●
1325
2417
4800 97%
-/-
●
●
●
700
1292
-/-
80%
80
●
●
●
550
1022
1700 66%
10
●
●
●
●
1350
2462
4900 98%
-/-
●
●
●
●
800
1472
-/-
85%
90
●
●
●
●
575
1067
1800 67%
5
●
●
●
●
●
1375
2507
5000 99%
-/-
●
●
●
●
900
1652
-/-
90%
-/-
●
●
●
●
600
1112
1900 68%
0
●
●
●
●
●
1400
2552
-/-
100%
-/-
●
●
●
●
●
1000
1832
Teach In
●
●
●
●
●
625
1157
2000 69%
-5
●
●
●
●
●
●
1425
2597
Teach In
Error diagnostic function on output
(other output ranges react analogous to the table)
Characteristic
Error
Output
Underrange
Overrange
Sensor break /
invalid setting
rising
S2-9 OFF
signalize
S2-
10 = OFF
0 … 20 mA
4 … 20 mA
0 … 10 V
0 … 5 V
0 mA
3.8 mA
0 V
0 V
20.5 mA
20.5 mA
10.25 V
5.125 V
22 mA
22 mA
11 V
5.5 V
not signalize
S2-
10 = ON
0 … 20 mA
4 … 20 mA
0 … 10 V
0 … 5 V
0 mA
4 mA
0 V
0 V
20 mA
20 mA
10 V
5 V
0 mA
4 mA
0 V
0 V
falling
S2-9 ON
signalize
S2-
10 = OFF
0 … 20 mA
4 … 20 mA
0 … 10 V
0 … 5 V
20.5 mA
20.5 mA
10.25 V
5.125 V
0 mA
3.8 mA
0 V
0 V
22 mA
22 mA
11 V
5.5 V
not signalize
S2-
10 = ON
0 … 20 mA
4 … 20 mA
0 … 10 V
0 … 5 V
20 mA
20 mA
10 V
5 V
0 mA
4 mA
0 V
0 V
0 mA
4 mA
0 V
0V