The GS01 gas detector has gone through rigorous reliability and functional safety
assessments and has been certified to IEC 61508:2010 Parts 1, 2, and 3.
The below listed failure rates are valid for operating stress conditions typical of an
industrial field environment similar to IEC 60654-1 with an average temperature of
40
o
C.
Table 8-1: SIL parameters GS01 detector
Parameter
GS01 Config-1, -129,
-65, -193
GS01 Config-2, -130,
-66, -194
Product Life
15 years
Safe Failure Fraction (SFF)
91%
Safe Detected (SD) failure rate [1/h]
0
Safe Undetected (SU) failure rate [1/h]
1.97 E-7
Dangerous Detected (DD) failure rate [1/h]
9.66 E-7
Dangerous Undetected (DU) failure rate [1/h]
1.00 E-7
Safety Integrity Level (SIL)
2
Diagnostic Test Interval
120 min
Safety accuracy
6
Concentration
is
not
underestimated by more
than 15%LEL or 40% of
the true concentration,
whichever is greater.
Concentration
is
not
underestimated by more
than 15%LEL or 40% of
the true concentration,
whichever is greater.
Average Probability of Failure on Demand
(PFD
AVG
) [1/h]
1.61E-3
7
Probability of dangerous Failure per Hour
(PFH) [1/h]
1.08 E-7
8
Worst
case
response
time
incl.
communication
60 sec
Fail safe values (data type Float)
NaN (0x7FC00000)
9
for the process value (PV)
“Bad” (decimal value < 64) for the PV status byte
Fail safe values (data type INT16)
-21846 (0xAAAA) for the process value (PV)
“Bad” (decimal value < 64) for the PV status byte
The calculated “Probability of Failure on Demand” assumes a “Mean Time to
Restoration” (MTTR) of 24 hours and a maintenance capability of 100%.
It is assumed that the field device is installed in a Safety Instrumented System
(SIS) operating in a Low Demand or High Demand environment per IEC 61508.
The GS01 gas detector is regarded as Type B field device per IEC 61508 with a
hardware fault tolerance of 0 (zero).
6
Assumed that the detected gas mixture is either a mixture of methane and air (Config-1 and
Config-129) or a mixture of propane and air (Config-2 and Config-130)
7
For a proof test interval of 2 years.
8
Fault detection and reaction time is 2 hours. Max demand rate is 1/200 hours.
9
Per float definition in IEEE754.