65
/
96
10.2.1.3 Input / outputs
Table 27:
Input/output parameters
Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
1-3
Inputs/outputs
-
-
Everybody
Nobody
-
1-3-1
Analog inputs
-
-
Everybody
Nobody
-
Note: To change a function, the
function first has to be removed by
changing it to 'No function'. To set a
function all pumps have to be set to
"Manual OFF" (2-2).
-
-
Everybody
Nobody
-
1-3-1-1
1-3-1-2
1-3-1-3
Input 1
Input 2
Input 3 (extension board)
No function
None
Everybody
Service
-
Pressure sensor on suction side
Pressure sensor on discharge side
Pressure sensor at tank
Setpoint
1-3-2
Analog outputs
-
-
Everybody
Nobody
-
Note: To change a function, the
function first has to be removed by
changing it to 'No function'. To set a
function all pumps have to be set to
"Manual OFF" (2-2).
-
-
-
-
-
1-3-2-1
1-3-2-2
Output 1
Output 2
None
None
Everybody
Service
-
Pump speed
Suction-side pressure
Discharge-side pressure
Tank-filling proportional valve
Tank-filling additional proportional valve
Tank level height
1-3-3
Digital inputs
-
-
Everybody
Nobody
-
Note: To change a function, the
function first has to be removed by
changing it to 'No function'. To set a
function all pumps have to be set to
"Manual OFF" (2-2).
-
-
-
-
-
Summary of Contents for Hydro-Unit Utility Line F
Page 29: ...29 96 1 2 Fig 12 PE connection 1 Earthing terminal 2 Location of power connection ...
Page 58: ...58 96 ...
Page 92: ...92 96 T Tank 79 Timers 73 W Warnings 9 Warranty claims 7 ...
Page 93: ......
Page 94: ......
Page 95: ......