59
/
96
10.2 Parameter lists
10.2.1 Configuration
10.2.1.1 System settings
Table 25:
System settings parameters
Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
1
Configuration
-
-
Everybody
Nobody
-
1-1
System
-
-
Everybody
Nobody
-
1-1-1
Information
-
-
Everybody
Nobody
-
1-1-1-1
Order number
Full text (max. 18 characters)
<empty>
Everybody
Service
-
1-1-1-2
Type series
Full text (max. 30 characters)
<empty>
Everybody
Service
-
1-1-1-3
Production number
Full text (max. 18 characters)
<empty>
Everybody
Service
-
1-1-1-4
System name (for Bluetooth)
Full text (max. 30 characters)
BOOSTERCONTRO
L
Everybody
Service
-
1-1-2
General
-
-
-
-
-
1-1-2-3
Operating mode
Operation on frequency inverter
Frequency driven
Everybody
Service
Y
Mains operation
1-1-2-4
Frequency inverter type
KSB PumpDrive2 (Eco)
PumpDrive2
Everybody
Service
Y
DP Var(+)
Danfoss MicroDrive
Danfoss MidiDrive
Danfoss AquaDrive
1-1-2-5
Frequency control type
Multi-pump operation
Multi-pump operation Everybody
Service
Y
Single-pump operation
1-1-2-6
Pump groups
Pump-group control
Base-load pump
control
Everybody
Service
Y
Pump-group and jockey-pump control
Base-load and peak-load pump control
1-1-3
Number of pumps
-
-
Everybody
Nobody
-
1-1-3-1
Total number of pumps
1 … 6
3
Everybody
Service
Y
Summary of Contents for Hydro-Unit Utility Line F
Page 29: ...29 96 1 2 Fig 12 PE connection 1 Earthing terminal 2 Location of power connection ...
Page 58: ...58 96 ...
Page 92: ...92 96 T Tank 79 Timers 73 W Warnings 9 Warranty claims 7 ...
Page 93: ......
Page 94: ......
Page 95: ......